FAN FILTER UNIT
INSTALLATION INSTRUCTIONS
Airflow Setpoint BFC
Step 1: Determine if BFC will be controlled using local control, BAS analog voltage signal, or BACnet. The control mode can be
confirmed by observing the cycling status readout on the LCD.
NOTE: The control hierarchy is BACnet > BAS > Local. The control mode is based on the highest level of control provided.
Step 2: For Local or BACnet control, determine the setpoint from the appropriate airflow formula for your model in the tables below.
If BFC is being controlled by BAS analog voltage signal, refer to "ECMSC Airflow Setpoint" section for proper input voltage (Note
this will be 2X the VDC value shown in the tables).
Set-point (ECM%) ranges from 0% - 100%
Supply - Constant Flow – Clean Filters (Forward Curved)
Voltage Velocity 24x24 24x36
Volt FPM BTR - FC RSR - FC BTR - FC RSR - FC
115 45-135 ECM% = (CFM/3.35) - 44 ECM% = (CFM/2.33) - 46 ECM% = (CFM/5.03) - 44 ECM% = (CFM/4.13) - 38
240 45-135 ECM% = (CFM/3.38) - 42 ECM% = (CFM/2.33) - 46 ECM% = (CFM/5.06) - 44 ECM% = (CFM/4.06) - 39
277 45-135 ECM% = (CFM/3.31) - 43 ECM% = (CFM/2.35) - 42 ECM% = (CFM/5.08) - 43 ECM% = (CFM/4.12) - 37
Voltage Velocity 24x48
Volt FPM BTR - FC RSR - FC
115 45-135 ECM% = (CFM/6.94) - 42 ECM% = (CFM/5.42) - 42
240 45-135 ECM% = (CFM/6.91) - 42 ECM% = (CFM/5.45) - 41
277 45-135 ECM% = (CFM/6.97) - 41 ECM% = (CFM/5.37) - 41
Supply - Constant Torque – Clean Filters (Backwards Curved)
Voltage Velocity 24x36 24x48
Volt FPM BTR - BC RSR - BC BTR - BC RSR - BC
115 45-135 ECM% = (CFM/15.74) - 14 ECM% = (CFM/15.29) - 12 ECM% = (CFM/17.03) - 16 ECM% = (CFM/18.1) - 12
240 45-135 ECM% = (CFM/15.78) - 14 ECM% = (CFM/13.76) - 15 ECM% = (CFM/16.09) - 18 ECM% = (CFM/18.28) - 12
277 45-135 ECM% = (CFM/15.56) - 14 ECM% = (CFM/13.99) - 14 ECM% = (CFM/15.68) - 19 ECM% = (CFM/17.92) - 12
Supply - Constant Torque – Clean Filters (Forward Curved)
Voltage Velocity 24x24 24x36
Volt FPM BTR/FC RSR/FC BTR/FC RSR/FC
115 45-90 ECM% = (CFM/10.87) - 13 ECM% = (CFM/10.23) - 11 ECM% = (CFM/10.93) - 15 ECM% = (CFM/10.73) - 15
90-135 ECM% = (CFM/7.26) - 26 ECM% = (CFM/7.72) - 18 ECM% = (CFM/6.78) - 41 ECM% = (CFM/8.12) - 25
240 45-90 ECM% = (CFM/10.82) - 13 ECM% = (CFM/11.28) - 8 ECM% = (CFM/11.3) - 13 ECM% = (CFM/11.58) - 12
90-135 ECM% = (CFM/7.27) - 26 ECM% = (CFM/7.84) - 17 ECM% = (CFM/6.92) - 39 ECM% = (CFM/8.75) - 22
277 45-90 ECM% = (CFM/9.93) - 15 ECM% = (CFM/10.32) - 10 ECM% = (CFM/11.02) - 16 ECM% = (CFM/11.12) - 14
90-135 ECM% = (CFM/7.26) - 26 ECM% = (CFM/7.71) - 18 ECM% = (CFM/7.74) - 33 ECM% = (CFM/7.92) - 26
Voltage Velocity 24x48
Volt FPM BTR/FC RSR/FC
115 45-90 ECM% = (CFM/11.84) - 17 ECM% = (CFM/12.86) - 13
90-135 ECM% = (CFM/7.43) - 48 ECM% = (CFM/7.82) - 37
240 45-90 ECM% = (CFM/11.78) - 17 ECM% = (CFM/12.72) - 13
90-135 ECM% = (CFM/7.42) - 48 ECM% = (CFM/7.86) - 36
277 45-90 ECM% = (CFM/11.74) - 17 ECM% = (CFM/12.79) - 12
90-135 ECM% = (CFM/7.33) - 49 ECM% = (CFM/7.67) - 38
10 priceindustries.com | FAN FILTER UNIT - ManualFAN FILTER UNIT - Manual | priceindustries.com