Section 3 Installation Detail
3.1PREPARATION
The fire feature will require both gas and electrical power. Make sure gas and electricity is turned off
before installing pipes and wires. Install the control panel and gas piping as shown in Figure 1: Natural
Gas, Figure 2: Propane Gas.
Note: Piping and fire bowl/ fire pit construction is different for natural gas and propane gas. Internal gas
lines must be clean and free from any dirt, debris, or contamination.
1. The gas piping and electrical conduit must be installed underground between the control
panel/gas meter and the fire feature. Please consult with a gas professional for proper gas pipe
and fitting sizing. Using smaller piping over long lengths will result in a diminished flame due to
pressure drop/piping resistance.
2. Maintain good piping practice by keeping pipe length and elbows to a minimum to eliminate
unnecessary pressure drops. IMPORTANT: Corrugated flex gas lines should not be used
underground as permanent piping. Rigid pipe should always be used for permanent installation.
3. The gas piping must be reduced to 3/4″ pipe at the fire feature with the means to shut off the
gas supply from the gas meter.
4. Install a ¾” to 1/2” reducer at the fire feature “stub-out” riser. The gas and electric risers should
not be more that 3” to 4” above the installation surface.
5. Install the 1/2” flare to ½” NPT fitting into the reducer fitting/pipe. You may place a manual shut
off valve between the elbow and the reducer for future maintenance. Test gas piping for leaks
Note: The gas and electrical connection should be located at or near the center of each fire bowl/table.
For the electrical, you will need 2 wires and a ground to the appliance.
6. Install wiring (14 or 16 ga) underground between the control panel and the burner assembly. DO
NOT USE BELL OR SPRINKLER WIRE. Lower gauge wire is not capable of carrying the current
needed to operate the appliance. Follow the wiring diagram in Section 6. The appliance should
be wired to a switch or dry contact on the 120 VAC side of the transformer.
NOTE: A light switch, emergency switch, relay contact, mechanical timer should always be installed on
the 120 VAC side of the transformer in order to operate the fire feature. The 12 VAC side may be wired
as far as 50 feet away from the transformer using 14-gauge wire.
7. Only place your fire feature on a level surface and ensure piping is centered, anchor if not
directly on the ground.
8. Take the 1/2” flex hose (provided) and tighten to the flare fitting from the supply line. Do not
kink or make a tight radius bend on the gas hose as it may restrict the flow of gas.
9. There are several vents and drainage holes in the fire bowl/table which must not be blocked. The
electrical and gas pipe hole is sealed such that water cannot penetrate the coping surface under
the bowl and will flow freely away and out to the edges.