Profort MultiGuard User manual

QUICK GUIDE for multiGuard® DIN9 3G
Ver. 4.01 www.profort.com
Pg. 1
Installation
1. Prepare a SIM card so that the PIN code is 1234 or is deactivated. Mount the card in the unit. The
unit now has password 1234 or runs without a password. The card is mounted as shown below.
2. Connect inputs, outputs and power cable (230V/12-24V AC/DC). If necessary a rechargeable 9V
battery.
3. Turn on the power. A diode is lit. After approx. 20 sec. the diode flashes approx. every 2 sec. and the
unit is ready.
multiGuard DIN9 interior
DIP-switch for analog input
1 ON: 0-10 VDC
2 ON: 0/4-20 mA
3 ON: PT-100
4 ON: Profort temperature sensor
All OFF: digital input
Voltage
Output: AC max. 230 VAC, 6A
DC max. 30 VDC, 6A
Input, digital: max. 24 VDC
max. power 2 mA
Input, analog: max. 0-10 VDC
Only connect voltage when the
DIP-switch 1 is on, and 2-4 are
off

SET-UP
www.profort.com
Pg. 2
Set-up on PC via COM-port or USB
1. Connect to PC via the unit RS232 by a RS232 cable or a USB-RS232, or connect to PC via
the unit USB-port and wait until driver is installed. You can find driver under ‘Download’
on www.profort.com.
2. Install the Profort PC program on a computer with Windows. Download the program from
www.profort.com. Start the program and enter the product key specified on the webpage.
3. Enter the number on the COM-port that the PC uses.
4. Check that “Connection to GSM-unit” appears in the status line. Restart PC if connection
fails.
5. Fill in the rest of the set-up program and complete it by transferring the information to the
unit.
Additional help: press F1 in the program, see the manual on the CD or www.profort.com

CONTROL
Ver. 4.01 www.profort.com
Pg. 3
Set-up with text message
1234 = password, 0 = zero, space counts as a character and is therefore important. Do not fill in password if
PIN is disabled on SIM-card.
Define the unit
phone number and
change password, if
necessary
1234 N0 88888888 yyyy
ID-TEXT
(N0 = N + zero)
1234 = current password, N0, 88888888=mobile
number of the unit.
Alternately yyyy=new four-digit password.
Alternately ID-text: First text in all messages from
the unit (max. 32 characters).
Receivers
Add
1234 N1 11111111
Adds receiver 11111111 in space no. 1 to receive
alarm as text message. yy yy yy yy
1234 N2 11111111 #
Adds receiver 11111111 in space no. 2 to receive
alarm as telephone call with tones.
Additional spaces (25 total):
N2..N9, NA (10), NB (11) .. NP (25),.
Delete
1234 N1
Deletes receiver in space no. 1
Text on input
Add
1234 A0 BREAK TEXT
TEXT on input 0 by open/break. (A0..A7)
1234 L0 END TEXT
TEXT on input 0 by close/make. (L0..L7)
Delete
1234 A0
Deletes TEXT for input 0 by open/break.
(A0..A7)
1234 L0
Deletes TEXT for input 0 by close/make. (L0..L2)
Only alarm if text
is added
1234 CT
The unit ignores input that has no text attached.
Add analog input 1
(V1) and 2 (V2)
1234 V1 S yyyy zzzz
Set-up of the scale (yyyy = zzzz): (V1 .. V2)
0-10 V (DIP-switch 1=ON) 0 10
0-20 mA. (DIP-switch 2=ON) 0 20
4-20 mA. (DIP-switch 2=ON) -5 20
PT100. (DIP-switch 3=ON) -309 115
Profort PTC. (DIP-switch 4=ON) -132 63
Add 2: Alarm
points
1234 V1 M 5 30
The unit sends alarm e.g. when temperature
passes 5 and 30 degrees C.
Add text in LOW
interval
1234 V1 A LOW TEMP
Alarm text in LOW interval (below 5 degrees
C.)
Add text in
MEDÌUM interval
1234 V1 L NORMAL TEMP
Alarm text in MEDIUM interval (between 5 and
30 degrees C.)

SET-UP
www.profort.com
Pg. 4
Add text in HIGH
interval
1234 V1 B HIGH TEMP
Alarm text in HIGH interval (higher than 30
degrees C.)
Activate output in
case of alarm
1234 G1
(G1 = 10 secs., G2 = 20 secs., G3 = 30 secs., G4 =
1 min, G5 = 2 mins, G6 = 4 mins, G7 = 8 mins, G8
= 16 mins og G9 = constant.)
Sets the relay output to activate in case of alarm on
an input. Output is determined by zone.
Output follows
state on input
1234 GA
Indicates that the output follows the corresponding
input if text is added.
Notice: input signal has higher priority than
command S0 (S + zero) and B0 (B + zero
Deactivate output
in case of alarm
1234 G0
Output is not activated in case of alarm (G+null)
Add macro 0 for
return of
temperature
1234 M0 TEMP <V1 R>
The unit returns value on analogue 1 (e.g.
temperature) when a text message with the word
‘TEXT’ is sent (‘1234’ omitted in macros).
Additional help: see the manual on the CD or on www.profort
Control with call from telephone
Call the unit. Press 1234 (password) when the connection is established, and await two ‘beeps’. Press the
desired code and hang up.
Code examples:
*0x (x = 0-3 for output 0-3) Pulses output x for 10 sec.
*1x (x = 0-3 for output 0-3) Opens output x
*2x (x = 0-3 for output 0-3) Closes output x
x (x = 0-9 for macro 0-9) Performs macro x
If a call is received and # is pressed
during playing of voice message The message is not sent to the
following in the receiver list

CONTROL
Ver. 4.01 www.profort.com
Pg. 5
Control with text message
Connect/disconnect
the unit
1234 ON
Inputs are activated, red diode flashes
1234 OF
Inputs are deactivated, red diode turns off
Activation of
output x
1234 S0
Closes output 0. (S0..S1)
1234 B0
Breaks output 0. (B0..B1)
1234 P0
Pulses output 0 for 10 secs. (P0..P1)
Download
1234 OK
Downloads information about GSM transmission power
and battery level
Example: OK>>OK SQ: xx%
xx = transmission power in percentage. 25 % is smallest
acceptable value
1234 V1 R
Downloads measurements on analogue input 1. (V1 ..
V2)
Connection to the
Internet
1234 EH USERNAME
GPRS traffic starts
1234 EH
GPRS traffic stops
Additional control
The unit can also be controlled by use of the PC program and all functions can be controlled directly on the
Internet.
On the print there’s a button with the following three functions:
1. If button is pressed down while power supply is connected, a “beep” is heard after 7 secs. This resets
the multiGuard DIN9 to default settings.
2. If button is pressed down during normal operations a “beep” is heard after 7 secs. If button is
released immediately hereafter, macro 1 is performed. If no function has been saved on macro 1,
nothing happens.
3. If button is pressed down after 7 secs., an additional “beep” will be heard after 14 secs. The
‘sabotage’ alarm is hereby activated.
See more in the manual or log on Internet management via www.profort.com

VOICE MESSAGE
www.profort.com
Pg. 6
Record messages
1. Call the unit
2. Await a tone
3. Type in a password (e.g. 1234), optional
4. Await two tones
5. Type in no. of the message that needs to be recorded, e.g. #8 (for general message)
6. Await a tone
7. Record message
8. Await two tones
9. The call can be ended or a new voice message can be recorded, e.g.:
10. Press #1 (opens for input 1)
11. Await a tone
12. Record the voice message for input 1
13. Repeat point 9-11 for more messages, if needed
14. Hang up
If “send different voice messages by break and close” or command 1234 W2 is selected, point 6-7 is
performed twice. First record message for ‘break’ (3 secs.), await tone, record message for ‘close’ (3 secs.).
In case of incorrect password the unit disconnects and you’ll have to dial up again.
Codes for recording of voice
messages
#8 General message 6 sec.
Digital inputs
#0 for input 0 6 sec.
#1 for input 1 6 sec.
#2 for input 2 6 sec.
#3 for input 3 6 sec.
#4 for input 4 6 sec.
#5 for input 5 6 sec.
#6 for input 6 6 sec.
#7 for input 7 6 sec.
Analog inputs
#91: analog input 1 6 sec.
#92: analog input 2 6 sec.
System alarm
#94: power failure 3 sec.
#95: power ok 3 sec.
#96: sabotage 3 sec.
#97: connecting 3 sec.
#98: disconnecting 3 sec.

SPECIFICATIONS
Ver. 4.01 www.profort.com
Pg. 7
Power supply
230V AC min. 0,1A
12-24V AC/DC min 0,5 A
NB! Supply must not come into contact with the ground.
Usage
Approx. 30 mA when resting (supplied with 12 V)
5 W supplied with 230 V
Outputs
Max. 6 A at 230V AC
Max. 6 A at 35V DC
10VDC output supply. Max 100 mA.
Inputs, digital
Max. 1V, 2 mA (GND)
Min. 18V max 30 V (24V DC)
Inputs, analog
0-10V DC
0/4-24mA
PT-100
Profort temperature sensor (007995)
Serial connections
RS232 for setup or connection to e.g. PLC Modbus for external units, e.g. energy meters
Counter
Max. 20Hz. Max. 1 mio. counts
Dimension
9 DIN-modules
157x86x57 mm
Weight: 360 g.
Temperature
–20 °C - +55 °C
Voice memory
90 sec.
Antenna
1 internal antenna for GSM modem

OTHER PRODUCTS IN THE SERIES
www.profort.com
multiGuard® DIN6
2 relay outputs
4 digital inputs
1 analog input
230V/12-24V power supply (acquisition)
9V re-chargeable back-up battery (acquisition)
DIN-rail with six modules
Modbus interface
multiGuard® Master RF
8 relay outputs
8 digital inputs
4 analog inputs
Wireless 868 Mhz receiver
230 V / 12-24 V power supply
9 V rechargeable back-up battery (acquisition)
Modbus interface
IP-65 box
Touch display for set-up and programming
multiGuard® Remote IO
1 relay output
2 senders of infrared codes for heat pump control
3 digital inputs
1 built-in temperature and humidity sensor
1 recorder for infrared codes
12 VDC power supply (inclusive)
3,6 V Li-ion back-up battery (inclusive)
Design box for wall mount
Plug for external IR-transmitter
IP-65 box for multiGuard® DIN4/6/9-series
Waterproof box
DIN-rail for 4/6/9 modules
3 PG inputs