Prolon T1000 Series Installation instructions

HARDWARE GUIDE
Digital Sensor - T1000 Series
Specifications and Operational Guide
REV. 6.2.3
PL-HRDW-T1000-F-EN
www.proloncontrols.com |info@proloncontrols.com
17 510, rue Charles, Suite 100, Mirabel, QC, J7J 1X9

2
REV. 6.2.3 / PL-HRDW-T1000-F-EN
Table of Contents
General Information............................................................................................................................ 4
Description ..................................................................................................................................................................... 4
Part Number Selection ................................................................................................................................................ 4
Installation ..........................................................................................................................................5
Power and Communication.................................................................................................................6
Auxiliary Analog Input ................................................................................................................................................ 6
Operation.............................................................................................................................................7
Hint Display .................................................................................................................................................................... 7
Changing the Setpoint ........................................................................................................................ 8
Schedule Override...............................................................................................................................8
Navigating Menus ...............................................................................................................................9
Menu Structure.................................................................................................................................. 10
T1000 Options and Visualisation Menus............................................................................................................... 10
VAV Controller: Visualisation Displays ................................................................................................................... 11
VAV Controller: Configuration Menus (Top Level).............................................................................................. 11
VAV Controller: Configuration Menus - Temperature........................................................................................ 12
VAV Controller: Configuration Menus - Damper................................................................................................. 12
VAV Controller: Configuration Menus - Pressure................................................................................................ 13
VAV Controller: Configuration Menus - Outputs ................................................................................................ 13
VAV Controller: Configuration Menus - Radiant Floor.......................................................................................14
VAV Controller: Configuration Menus - Other.....................................................................................................14
VAV Controller: Configuration Menus - Calibration........................................................................................... 15
VAV Controller: Configuration Menus - Network................................................................................................16
Technical Specifications.................................................................................................................... 17
Compliance ........................................................................................................................................ 18
FCC User Information.................................................................................................................................................18
Industry Canada .........................................................................................................................................................18
Overall Dimensions ........................................................................................................................... 19

3
REV. 6.2.3 / PL-HRDW-T1000-F-EN
Table of Figures
Figure 1 - Opening Tab ..................................................................................................................................................... 5
Figure 2 - Terminal Block Pinout .................................................................................................................................... 5
Figure 3 - Terminal Block.................................................................................................................................................. 6
Figure 5 - Connecting the Auxiliary Input................................................................................................................... 6
Figure 4 - RJ45 Pinout ....................................................................................................................................................... 6
Figure 7 - Touch Pad Feedback....................................................................................................................................... 7
Figure 6 - Touch Pad Controls......................................................................................................................................... 7
Figure 8 - Touch Pad Hint................................................................................................................................................. 7
Figure 9 - T1000 Size Diagram ...................................................................................................................................... 19

4
REV. 6.2.3 / PL-HRDW-T1000-F-EN
Description
The T1000 digital sensors are designed for operation in conjunction with the ProLon VAV or HPS
controllers, to which they provide zone temperature, setpoint and occupancy override information.
The T1000 digital sensors also provide an access point from which to visualize and configure any
parameter on the connected VAV controller through an on-screen menu system.
The T1000 features a circular capacitive touch pad, graphic LCD screen with backlighting and an auxiliary
analog input.
Part Number Selection
General Information
PL-T1000-WGL
Casing Color:
W = White
B = Black
Label Color
GL = Grey Label
WL = White Label

5
REV. 6.2.3 / PL-HRDW-T1000-F-EN
1. Open casing to remove back cover by pushing on the tab located underneath the thermostat.
(Figure 1)
2. Pull wire(s) through central hole of back cover.
3. Screw in the back cover to the wall.
4. Connect wires:
•If using twisted pair wires:
- Pull out the screw terminal blocks.
- Remove 1 cm insulation from the end of each wire.
- Connect the wires to the terminal blocks and re-connect the terminal blocks. (Figure 2)
•If using CAT5 cable:
- Plug the cable into the RJ45 jack of the T1000 (if CAT5 cable is opened at the controller, refer to
Figure 4 for pinout of the T1000's RJ45 jack).
5. Reconnect top cover.
Installation
IMPORTANT: Do not install the thermostat under the following conditions:
•Any location exposed to direct sunlight
•On an outside wall
•Near an air discharge grill
•In a location where vertical air circulation is restricted
•Near a dimmer switch
INT A
INT B
Figure 1 - Opening Tab Figure 2 - Terminal Block Pinout

6
REV. 6.2.3 / PL-HRDW-T1000-F-EN
Power and Communication
The T1000 is typically powered by the same controller it is communicating with. It has two different
connector types available for your choice of preferred wiring method.
• The first is a 4-pin, screw-type terminal block suitable for a 4 wire connection
•The second is an RJ45 connector intended for standard CAT5 cable
Through either of these connection methods, the T1000 is powered (24 VAC Class 2) and communicates
over Modbus RTU (RS485, 57600 bps) as a Modbus Master.
Auxiliary Analog Input
The T1000 has an auxiliary analog input which can be used to connect another thermistor. The T1000 can
be configured to use this alternate temperature reading for a variety of functions, including temperature
averaging or radiant floor slab temperature. The alternate thermistor (10KΩ type 3) can be connected to
the auxiliary input using the “AUX IN” and “COM” pins.
COM
24 VAC
B (-)
A (+)
INT A
INT B
Figure 3 - Terminal Block
Figure 5 - Connecting the Auxiliary Input
Figure 4 - RJ45 Pinout

7
REV. 6.2.3 / PL-HRDW-T1000-F-EN
The T1000 is controlled using the circular touch pad on the bottom half of the thermostat. The touch
pad uses capacitive sensing technology to detect finger proximity. There are no moving parts to push or
rotate. The T1000 is controlled using simple scrolling, tapping or holding motions, performed around the
circle of the touch pad. The center of the circle is unused.
Hint Display
At the bottom of the screen, a circle representing the touch pad is displayed, with hints on how to
navigate and modify settings, as well as providing feedback as you manipulate the touch pad. Hints are
context-sensitive and will only display where logical.
Operation
Scroll clockwise or
counterclockwise
to adjust or navigate
Tap here to
ENTER
Tap here to
go BACK
Figure 6 - Touch Pad Controls
Figure 7 - Touch Pad Feedback Figure 8 - Touch Pad Hint
The black arc
follows your nger
Hold your nger over
highlighted areas to use
special features

8
REV. 6.2.3 / PL-HRDW-T1000-F-EN
Changing the Setpoint
Schedule Override
Scroll or tap
(any direction)
Heat SP
Cool SP
Adjust your setpoint
by scrolling clockwise
or counterckwise
View current zone
temperature
Home Screen Setpoint Screen
Tap anywhere
(or simply wait)
return to
Home Screen
The sun icon is
displayed when
overridden
OVERRIDE ACTIVE
(Occupied mode)
The moon icon indicates
unoccupied mode
Scroll clockwise
to override
67.5
79.5
67.5
79.5
First, go to the Setpoint Screen.

9
REV. 6.2.3 / PL-HRDW-T1000-F-EN
Navigating Menus
Menu
75.1
Tap here to
go BACK
SCROLL clockwise or
counterclockwise
to navigate through the
current menu level
Tap here to
ENTER
Active Menu
75.1
Hold left
for 8 sec
Conguration
Menu
Hold right
for 5 sec
Options and
Visualisation Menu
Configure
From the Home Screen.

10
REV. 6.2.3 / PL-HRDW-T1000-F-EN
Menu Structure
The T1000 has two menu systems: The first is dedicated to the general options of the T1000 thermostat
as well as visualization of the status of the controller to which it is connected. The second menu system
is dedicated entirely to the configuration settings of the controller to which it is connected. These menu
structures are outlined below.
T1000 Options and Visualisation Menus
Starting from: T1000
Home Screen
75.1
Hold ‘right’
for 5 sec
Temp Unit
Aux Input
Reset Tstat
Sound
Backlight
Language
Rounding
Type
Software Version
Hardware Version
Status 1
Status 2
Status 3
Device Type
Software Version
Hardware Version
Device #
Device Name
Reset Device
Options
About me
Visualize
Device

11
REV. 6.2.3 / PL-HRDW-T1000-F-EN
VAV Controller: Visualisation Displays
VAV Controller: Configuration Menus (Top Level)
Visualize
Zone Temperature
Active Zone Setpoints
Occupancy Status
Zone Demand
Damper Position
Air Flow Reading
Status of all Outputs
Supply Air Temperature
Outside Air Temperature
Discharge Air Temperature
Air Flow SP
Radiant Flow Cycle %
CO2 Reading
Status 1
Status 2
Status 3
Starting from: T1000
Home Screen
75.1
Hold ‘left’
for 8 sec
Temperature
Damper
Pressure
Outputs
Radiant Floor
Other
Network
Calibration

12
REV. 6.2.3 / PL-HRDW-T1000-F-EN
VAV Controller: Configuration Menus - Temperature
VAV Controller: Configuration Menus - Damper
Temperature
Deadband
PropBand
Cool Integral
Heat Integral
Min Heat
Max Heat
Min Cool
Max Cool
Heat Oset
Cool Oset
Heat SP Lim
Cool SP Lim
Heat Scale Lim
Cool Scale Lim
Enable
Value
PI Control
SP Limits
Unocc Mode
Scale Lim
Sched Override
Damper
Source
Damp Unocc Mode
Supply DB Min
Supply DB Max
Damper Prop
Damper Di
Duct Heater SP
Min Heat Opening
Min Vent Opening
Max Damp Opening
Standby Min Pos
CO2 Min Pos
Opening Dir
Halomo
Openig Delay
Enable
Value
Damper
Movement
Damper
Setup
Override

13
REV. 6.2.3 / PL-HRDW-T1000-F-EN
VAV Controller: Configuration Menus - Pressure
VAV Controller: Configuration Menus - Outputs
Duct Heater
Radiant Floor
FPB Output
FPB Mode
Source SP mode Sp Value Control Band
Enable
Value
Rev Act
Pulsed
Range
Special Function
Output 1
Output 2
Output 3
Output 4
Output 5
Setup
Override
Signal
Pressure
Min Vent SP
Max Vent SP
Min Vent Heat SP
Min Vent CO2
Diameter
K Factor
Sensor
Flow Di
Damper Speed
Flow SP
Duct Setup
Sensitivity

14
REV. 6.2.3 / PL-HRDW-T1000-F-EN
VAV Controller: Configuration Menus - Radiant Floor
VAV Controller: Configuration Menus - Other
Other
Unocc Over Time
Morn WarmUp
Max Receive Time
Analog Input Mode
CO2 Hi Lim
CO2 Calib
Timing
Inputs
Radiant Floor
Proportional
Integral
Min Slab Temp
Max Slab Temp
Min Slab Temp
Cycle Length
Outside Cuto
Calibration
Limits
Unoccupied
Mode
PI Loop
Setup

15
REV. 6.2.3 / PL-HRDW-T1000-F-EN
Calibration
Zone
Supply
Oset
Corr Factor
Auto-Calibrate
Temperature
Ventilation
VAV Controller: Configuration Menus - Calibration

16
REV. 6.2.3 / PL-HRDW-T1000-F-EN
Network
Max Master
Instance
Max Send Time
Min Send Time
Group Code 1
Group Code 2
Group Code 3
Group Weight 1
Group Weight 2
Group Weight 3
Global Weight
Math Enable
Math 1 Source
Math 1 Group
Math 2 Source
Math 2 Group
Math 3 Source
Math 3 Group
Math 4 Source
Math 4 Group
Math 5 Source
Math 5 Group
Poll Rate
List Refresh
Unoccupied Mode
Net Baud
Net Parity
Net Stop Bits
INT Baud
INT Parity
INT Stop Bits
Math Functions
Group Codes
Lon*
BACnet
COM Port
VAV Controller: Configuration Menus - Network
*Available only with a C1000.

17
REV. 6.2.3 / PL-HRDW-T1000-F-EN
Technical Specifications
Supply: 24 VAC ±10%, 50/60 Hz, Class 2
Power Consumption: 5 VA max
Inputs: 1 analog input (Thermistor 10K type3), 10 bit resolution
Outputs: None
Screen: LCD 80x130 pixels with backlighting
Interface: Circular capacitive touch pad
Sound: Audible feedback during user interactions
Microprocessor: Atmel 32 bits, 60 MHz, 256K bytes Flash memory
Connection: Screw-type terminal blocks (16 AWG max) and RJ45 modular jack
Dimensions: 3.23" x 4.96" (82mm x 126mm)
Weight: 0.22 lb (0.1 kg)
Environment: 32-122 ºF (0-50 ºC)
Mounting: Standard electrical box 2" x 4"
Certification: FCC Part 15: 2012 class B
The performance specifications are nominal and conform to acceptable industry standards. ProLon Inc. will
not be liable for damages resulting from misapplication or misuse of its products.

18
REV. 6.2.3 / PL-HRDW-T1000-F-EN
Compliance
• FCC Compliant to CFR47, Part 15, Subpart B, Class B
• Industry Canada (IC) Compliant to ICES-003, Issue 5: CAN ICES-3 (B)/NMB-3(B)
• RoHS Directive (2002/95/EC)
FCC User Information
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two condi-
tions: (1) this device may not cause harmful interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation.
Caution: Any changes or modifications not approved by ProLon can void the user’s authority to operate
the equipment.
Note: This equipment has been tested and found to comply with the limits for a Class B digital device,
pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against
harmful interference in a residential installation. This equipment generates, uses and can radiate radio
frequency energy and, if not installed and used in accordance with the instructions, may cause harmful
interference to radio communications. However, there is no guarantee that interference will not occur in a
particular installation. If this equipment does cause harmful interference to radio or television reception,
which can be determined by turning the equipment off and on, the user is encouraged to try to correct
the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver
is connected.
• Consult the dealer or an experienced radio/TV technician for help.
Industry Canada
This Class (B) digital apparatus meets all the requirements of the Canadian Interference-Causing
Equipment regulations.
Cet appareil numérique de la Classe (B) respecte toutes les exigences du Réglement sur le matériel
brouilleur du Canada.

19
REV. 6.2.3 / PL-HRDW-T1000-F-EN
© Copyright 2018 ProLon. All rights reserved.
No part of this document may be photocopied or reproduced by any means, or translated to another language without prior written
consent of ProLon. All specications are nominal and may change as design improvements are introduced. ProLon shall not be liable for
damages resulting from misapplication or misuse of its products. All trademarks are the property of their respective owners.
REV. 6.2.3
PL-HRDW-T1000-F-EN
Overall Dimensions
Figure 9 - T1000 Size Diagram
4.96"
(126 mm)
3.23"
(82 mm)
1.10"
(28 mm)
RJ45
Other manuals for T1000 Series
1
Table of contents
Other Prolon Accessories manuals