manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Pulsar
  6. •
  7. Controllers
  8. •
  9. Pulsar ULTRA 5 Instruction manual

Pulsar ULTRA 5 Instruction manual

Pulsar Quick Start Manual - Ultra 5
Congratulations on your purchase
of a Pulsar Ultra 5!
This quality system has been developed
with the latest digital ultrasonic tech-
nology for liquids, slurries, and solids.
No more noise and beam angle issues.
It provides non-contacting level, vol-
ume, advanced pump control, differen-
tial level, and open channel flow with 5
user-defined relays. Comes standard
with 110VAC and 24VDC with an iso-
lated 4-20 mA output.
LIQUIDS and SOLIDS
• Mount the transducer away from any obstructions, fal-
ling water/solids, rough walls, pumps, switches, etc…
• Visualize looking down the echo path of the transducer
and seeing a nice clear shot (2’+ dia.) to the very bot-
tom during fill and empty cycles.
• Ensure the maximum level does not come within the
minimum dB blanking distance.
• Confirm the inside of the standpipe is smooth and does
not have any protrusions at the weld.
• Do not hang the transducer by the cable.
• Typically, mount the dB transducer 1/2 the tank radius.
(Call Pulsar Technical Support for Special Service
Passcode and Instructions 850-609-1777.)
LIQUIDS
• Dome top tanks will require Gain & Algorithm change.
• If reading false level, use P21 and set true distance
SOLIDS
• Consult factory if the silo is extremely dusty—we can
increase the return signal strength (even during fill).
• DATEM may map-out the true echo. Use P21 to set
true distance and turn “Update Datem” off!
• If acoustically noisy, change Algorithm to Largest.
TRANSDUCER WIRING
TERMINAL IF SPLICING (shielded pair)
RED = POWER RED = BLACK
WHITE = SIGNAL WHITE = WHITE
BLACK & GREEN = 0V BLACK & GREEN = SHIELD
• Use any standard, 2 conductor/shielded pair for splic-
ing (recommend 18 AWG gauge, UV protected)
• Use 16 AWG gauge if going 500 - 3,000 ft cable run.
• Transducer shield is required - do not cut or float!
• Battery is actually the 24VDC terminals.
• If I.S. Zone 0 is required, consult factory for details.
Above wiring diagram is on the back of terminal cover.
0-8 ft .5-10 ft 1-20 ft 1-33 ft 1.7-50 ft 2-82 ft 3-132 ft
Mach3 dB 3 dB 6 dB 10 dB 15 dB 25 dB 40 Aiming Kit
Pulsar, Inc., PO Box 799, Shalimar, FL 32579 Phone: (850) 609-1777 Fax: (850) 651-4777 support@pulsar-us.com
Press to close enclosure!
TRANSDUCER INSTALLATION TROUBLESHOOTING
QUICK START PROGRAMMING
1. Enter Program Mode
( press and hold each button until the dash appears)
2. Choose “Ultra Wizard”
a. For Level or Volume (Level only, no pump
control, differential level, or open channel flow)
“Select Apps.” (default is Level)
“ Currently Level/Vol., 0 to Reset”
“Quick Setup” (go to step 3a)
b. For Pump, Differential, or Flow
(Unit needs to be reset)
Select Apps.: 1=Level/Vol 2=Pump/Diff 3= Flow
(“Loading” will require up to 2 minutes)
“Quick Setup” (Pump/Diff go to 3b, Flow go to 3c)
3a. Choose “Quick Setup” (LEVEL Pg. 34)
Press “Enter” and choose “Application”:
1= Level 2= Volume
(Always hit “Enter” to save and confirm by seeing “Saved”)
“Control” (Relay will Energize ON & DeEnergize OFF)
“Alarm” (Relay will DeEnergize ON & Energize OFF)
Choose how many of each, set to corresponding relay, and
choose what type “Control” or “Alarm” it is.
If no relays are used, then type “0” and “Enter” for each.
“Wait…” could take up to 30 seconds.
“Xducer” Choose the transducer being used: 1=dB3 2=dB6
3=dB10 4=dB15 5=dB25 6=dB40 7=dBS6 8=dBMach3
“Material” Choose 1= Liquid or 2= Solid
“Measurement Units” Choose 1=m 2=cm 3=mm 4=ft 5=in
“Empty Level” Enter the distance from the face of the
transducer to the bottom of the vessel/tank (sets 4mA)
“Span” Enter the distance from the bottom of the tank/vessel
(Empty Level) to the top or 100% point (sets 20mA)
For Volume, go to the Ultra 3 manual on Pg. 37 and answer:
“Vessel Shape”, “Vessel Dim.”, “Vol. Units”, “Max Vol.”
“For More Options Hit Enter” (Calibration is done, step 4!)
“Run Mode?”
3b. Choose “Quick Setup” (PUMP/DIFF Pg. 104)
Press “Enter” and choose “Application”:
1= Level 2= Pump Down 3= Pump Up 4=Differential (screen)
(for Differential Control Relay Setup, follow menu on page 106)
“No. Of Pumps” Choose # of pumps and set to Relay #.
(Pump Relay will Energize ON & DeEnergize OFF)
“Pump Duty” Choose 3 for “Alt Duty Assist” (Alternating Lead/
Lag Routine is the most common) and set to Relay #.
“No. Of Alarms” Choose # of Alarms based on remaining open.
(Alarm Relay will DeEnergize ON & Energize OFF)
Choose how many of each, type of Alarm, and set to Relay #.
If no relays are used, then type “0” and “Enter” for each.
“Wait…” could take up to 30 seconds.
“Xducer” Choose the transducer being used: 1=dB3 2=dB6
3=dB10 4=dB15 5=dB25 6=dB40 7=dBS6 8=dBMach3
“Material” Choose 1= Liquid or 2= Solid
“Measurement Units” Choose 1=m 2=cm 3=mm 4=ft 5=in
“Empty Level” Enter the distance from the face of the
transducer to the bottom of the vessel/tank (sets 4mA)
“Span” Enter the distance from the bottom of the tank/vessel
(Empty Level) to the top or 100% point (sets 20mA)
“For More Options Hit Enter” (Calibration is done, go to step 4!)
3c. Choose “Quick Setup” (FLOW Pg. 198)
“PMD Type” Primary Measuring Devices to choose from:
1= Exponential (most commonly used: 1=Rectangular Weir
2=Trapezoid 3=Venturi 4=Parshall Flume 5=Leopold
6=V-Notch Weir 7=Other) 2= Never use (European) 3= Never
use (European) 4= Area Velocity 5= Special (Palmer Bowlus,
H-Flume, or V-Notch Angle) 6= Universal (32 pt curve-fit)
“Calculation” Choose the method to calculate Flow:
1=Absolute (may require K factor, Exponent, Dimensions, etc.)
2=Ratiometric (most common, requires Max Head vs. Max Flow)
“Alarm” (Relay will DeEnergize ON & Energize OFF)
If no relays, type “0” & “Enter” (Totalizer relay setup on pg 254)
“Wait…” could take up to 40 seconds.
“Xducer” Choose the transducer being used: 1=dBMach3
2=dB6 3=dB10 4=dB15 7=dBS6
IMPORTANT: dB3 will not work in FLOW! Call Pulsar ASAP.
“Volume Units” 1=liters 2=cubic m 3=cubic ft 4=UK Gallons
5=US Gallons 6=Million Gallons
“Time Units” 1= /sec 2= /min 3= /hour 4= /day
“Measurement Units” Choose 1=m 2=cm 3=mm 4=ft 5=in
“Empty Level” Enter the distance from the face of the
transducer (bottom of dBMach3 cone) to the 0% Flow of the PMD
“Minimum Head” (usually set to 0, Pg. 260– sometimes for weirs)
“Max Head” Distance from 0% Flow to Max Flow (updates Span)
“Totalizer Enable” Choose 1 (On) for Totalizer to be viewed
using the Sigma Hot Key
“TotalizerR” Choose 1 (On) to display Totalizer in Run Mode.
“Totalizer Mult” pick 1 (/1000) for MGD and 7 (*1000) for gpm
“Max Flow” used in Ratiometric. At Max Head, what is the flow?
“For More Options Hit Enter” (Calibration is done, go to step 4!)
4. Calibration is done, go into Run Mode!!!
NOTE about Relays. Quick Setup assumes ON and OFF
setpoints based on level percentages. For Example:
High Alarm is “ON” at 85% and “OFF” at 80% of level
Low Alarm is “ON” at 10% and “OFF” at 15% of level
Pump 1 (Pump Down) is “ON” at 50% and “OFF” at 20%
Pump 2 (Pump Down) is “ON” at 70% and “OFF” at 20%
Consult manual for more information on Relays.

Other manuals for ULTRA 5

2

Other Pulsar Controllers manuals

Pulsar blackbox 130 User manual

Pulsar

Pulsar blackbox 130 User manual

Pulsar Masterpiece Replay 216 User manual

Pulsar

Pulsar Masterpiece Replay 216 User manual

Pulsar ULTRA 5 User manual

Pulsar

Pulsar ULTRA 5 User manual

Pulsar Blackbox Instruction manual

Pulsar

Pulsar Blackbox Instruction manual

Pulsar UltraTWIN User manual

Pulsar

Pulsar UltraTWIN User manual

Pulsar ZERO 4001 User manual

Pulsar

Pulsar ZERO 4001 User manual

Popular Controllers manuals by other brands

Aaeon AEC-VS01 manual

Aaeon

Aaeon AEC-VS01 manual

Neutron Lime-4.0-NA user manual

Neutron

Neutron Lime-4.0-NA user manual

Smartgen GENSET CONTROLLER MGC310 user manual

Smartgen

Smartgen GENSET CONTROLLER MGC310 user manual

SSK CYPRES 2 quick guide

SSK

SSK CYPRES 2 quick guide

Omron SYSMAC C20K installation guide

Omron

Omron SYSMAC C20K installation guide

Viridian EV EPC E32F21 manual

Viridian EV

Viridian EV EPC E32F21 manual

POL-EKO SMART quick start guide

POL-EKO

POL-EKO SMART quick start guide

Sensor Access IC2001 manual

Sensor Access

Sensor Access IC2001 manual

Contest CTLTAPE user guide

Contest

Contest CTLTAPE user guide

ComAp L151006001 installation manual

ComAp

ComAp L151006001 installation manual

Grundfos PM 2 Installation and operating instructions

Grundfos

Grundfos PM 2 Installation and operating instructions

AUMA SAVEx 07.2 Operation instructions

AUMA

AUMA SAVEx 07.2 Operation instructions

STORK TRONIC ST181-LM4KAR.112 instructions

STORK TRONIC

STORK TRONIC ST181-LM4KAR.112 instructions

Nexen STC600 user manual

Nexen

Nexen STC600 user manual

Lencore G41 Installation & operation manual

Lencore

Lencore G41 Installation & operation manual

Lennox HYDRON Series Installation, operation & maintenance manual

Lennox

Lennox HYDRON Series Installation, operation & maintenance manual

DIMLUX MAXICONTROLLER user manual

DIMLUX

DIMLUX MAXICONTROLLER user manual

Emerson Fisher 4195KA instruction manual

Emerson

Emerson Fisher 4195KA instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.