
TM
Venting Installation
For proper and safe operation this appliance needs air for
combustion and ventilation. DO NOT block or obstruct air
openings on the appliance, spaces around the appliance, or
air openings communicating with the appliance area.
DO NOT block the flow of combustion and ventilation air.
To provide for necessary oxygen for proper combustion,
opening must be provided to allow outside air to enter the
space in which the heater is located. Enclosed spaces,
such as equipment rooms, must be vented at the blower for
combustion air. The size of air openings must be based on
all gas-burning equipment installed in the space involved.
Provisions for adequate combustion and ventilation air
in accordance with Section 5.3, Air for Combustion and
Ventilation, of the National Fuel Gas Code, ANSI Z223.1, or
Sections 7.2, 7.3 or 7.4 of the CAN/CGA B149 Installation
Codes, or applicable provisions of the local building codes.
The burner should be initially set up and serviced at regular
intervals (preferably at the beginning of and mid-way through
high use period) by a trained serviceman using the proper test
instruments. Failure to maintain the correct burner settings
may result in inefficient gas consumption, premature wear of
burner components, or explosion hazard.
Venting
The GX Series Humidifiers are a Category 3 Appliance.
The purpose of venting the gas humidifier is to completely
remove all products of combustion and ventilation gases to
the outside air, without condensation in the stack.
When connecting the humidifier to a gas vent or chimney,
the installation shall be in accordance with Part 7, Venting
of Equipment, of the National Fuel Gas Code, ANSI Z223.1,
or Section 7, Venting Systems and Air Supply Appliances,
of the CAN/CGA-B149 Installation Codes, the local building
codes, and the vent manufacturer’s instructions.
Do not reduce the vent diameter, and avoid short turns in
the vent piping. Use the exhaust manifold vent size shown
on page 15.
Allow for removal of air intake and exhaust connections for
heat exchanger cleaning and regular maintenance. Maintain
a 1/4-inch-per-foot pitch for horizontal runs. Maintain proper
support of vent connections and joints. Observe clearances
(in accordance with applicable codes) from all combustible
materials, and obtain an approved cap for the stack outlet.
The bottom of the cap must be one stack diameter above the
top of the stack.
Inspect for proper and tight construction. Any restrictions
or obstructions must be removed. An existing chimney may
require cleaning.
Chimney or vent must extend at least 3 feet above its
passage through a roof and at least 2 feet above any ridge
within 10 feet of the chimney (local codes apply).
Minimum clearance from the vent connector to combustible
material is 6 inches unless the combustible materials are
protected in accordance with applicable codes.
PURE Humidifier requires humidifiers be connected to vent
systems sufficient for use with Category 3 Appliances (listed
to UL Standard 1738 or ULC-S636). Any condensate formed
is acidic and could cause corrosion of the vent materials.
This humidifier must not be connected to a chimney flue
servicing a separate appliance designed to burn solid fuel.
If condensation is noticed in the field, a condensate trap
should be installed in the venting system.
Never connect this humidifier to a chimney.
Venting into an unlined masonry or concrete chimney is
prohibited by code.
Insulation must be added to any vent connector which will be
exposed to ambient temperatures of 30°F or less.
Do not insulate vent pipe exposed to outdoor weather
conditions (i.e. above roof lines).
Installation of the vent pipe should be as direct as possible,
with a minimum number of turns or elbows.
Rigidly support the vent pipe every 5 feet or less with
hangers or straps to ensure that there will be no movement
or sagging after installation. The humidifier vent box should
not be supporting the weight of the vent piping.