WTV5050 | External Inline Mixing Valve
Copyright © Puretec Pty Ltd 2021
Installation
Fig 1.
Installation
1. Isolate the water supply & release the pressure.
2. Remove the existing bypass and/or inlet/outlet adaptors by turning the union anticlock-
wise.
3. Install the WTV5050 External Blending Valve. Ensure that the arrows are pointing in the
direction of the ow. If unsure, contact Puretec for assistance.
Note: Hand tighten only, do NOT overtighten.
4. Connect bypass and/or inlet/outlet adaptors to the External Blending Valve.
5. Turn on the water supply and adjust the External Blending Valve as required by:
Clockwise: Increases bypass (less treated water).
Anticlockwise: Reduces bypass (more treated water).
When setting up for max bypass (least amount of treated water) turn the dial anti-clock-
wise until it stops. Then adjust the dial turning it clockwise to the thickest part of the line
on the dial indicator.
Note: If the dial is turned clockwise past the max bypass line (maximum blending) posi-
tion it will need to be reset. To reset, turn the dial anticlockwise until it stops and turn the
dial to the desired position.
6. Once the External Blending Valve has been set, the unit is ready for use.