Pyxis ST-565T User manual

Table of Contents
1 Introducon 2
1.1 Main Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2 Specicaons 3
3 Unpacking Instrument 3
3.1 Standard Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3.2 Oponal Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
4 Installaon 5
4.1 Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4.2 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4.3 Connecng via Bluetooth . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4.4 Connecng via USB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5 Setup and Calibraon with uPyxis® Mobile App 7
5.1 Download uPyxis® Mobile App . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5.2 Connecng to uPyxis® Mobile App . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5.3 Calibraon Screen and Reading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5.4 Diagnosis Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5.5 Device Info Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
6 Setup and Calibraon with uPyxis® Desktop App 11
6.1 Install uPyxis® Desktop App . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
6.2 Connecng to uPyxis® Desktop App . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
6.3 Informaon Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
6.4 Calibraon Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
6.5 Diagnosis Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
7 Outputs 14
7.1 4–20mA Output Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
7.2 Adjusng 4–20mA Span . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
7.3 Communicaon using Modbus RTU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
8 Sensor Maintenance and Precauon 16
8.1 Methods to Cleaning the ST-565 Series Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . 16
8.2 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
9 Troubleshoong 17
10 Contact Us 17

Warranty Informaon
Condenality
The informaon contained in this manual may be condenal and proprietary and is the property of Pyxis
Lab, Inc. Informaon disclosed herein shall not be used to manufacture, construct, or otherwise reproduce
the goods described. Informaon disclosed herein shall not be disclosed to others or made public in any
manner without the express wrien consent of Pyxis Lab, Inc.
Standard Limited Warranty
Pyxis Lab warrants its products for defects in materials and workmanship. Pyxis Lab will, at its opon, repair
or replace instrument components that prove to be defecve with new or remanufactured components
(i.e., equivalent to new). The warranty set forth is exclusive and no other warranty, whether wrien or oral,
is expressed or implied.
Warranty Term
The Pyxis warranty term is thirteen (13) months ex-works. In no event shall the standard limited warranty
coverage extend beyond thirteen (13) months from original shipment date.
Warranty Service
Damaged or dysfunconal instruments may be returned to Pyxis for repair or replacement. In some in-
stances, replacement instruments may be available for short duraon loan or lease.
Pyxis warrants that any labor services provided shall conform to the reasonable standards of technical com-
petency and performance eecve at the me of delivery. All service intervenons are to be reviewed and
authorized as correct and complete at the compleon of the service by a customer representave, or des-
ignate. Pyxis warrants these services for 30 days aer the authorizaon and will correct any qualifying
deciency in labor provided that the labor service deciency is exactly related to the originang event. No
other remedy, other than the provision of labor services, may be applicable.
Repair components (parts and materials), but not consumables, provided during a repair, or purchased
individually, are warranted for 90 days ex-works for materials and workmanship. In no event will the in-
corporaon of a warranted repair component into an instrument extend the whole instrument’s warranty
beyond its original term.
Warranty Shipping
A Repair Authorizaon (RA) Number must be obtained from Pyxis Technical Support before any product can
be returned to the factory. Pyxis will pay freight charges to ship replacement or repaired products to the
customer. The customer shall pay freight charges for returning products to Pyxis. Any product returned to
the factory without an RA number will be returned to the customer. To receive an RMA you can generate a
request on our website at hps://pyxis-lab.com/request-tech-support/.
Pyxis Technical Support
Contact Pyxis Technical Support at +1 (866) 203-8397, [email protected], or by lling out a request for
support at hps://pyxis-lab.com/request-tech-support/.

1 Introducon
The ST-565 Series inline uorometers are patented to Pyxis Lab Inc. These devices ulized UV light uores-
cence to detect Halogenated Tolytriazole (HST with ST-565) and Tolytriazole (TTA with ST-565T) content in
water. The results are instantaneous and, with proper applicaon understanding, results are highly reliable.
It is important to note that this technology is not wet chemistry tesng for azole content and variaons may
be observed depending on the quality of the water sample. In certain waters the background of other or-
ganic maer may cause a false posive reading of azole due to UV uorescence or absorbance. Inconsistent
makeup water quality with lile organic loading (ie. city water makeup) and systems with no known organic
contaminaon (ie. hydrocarbon) this technology is very accurate in comparison to wet chemistry methods.
The ST-565 Series sensor does not dierenate between azole species or reacted versus unreacted azole.
The device measures the total UV uorescence signature of the azole and oers the nal value as ppm
Halogenated Tolytriazole (HST with ST-565) and Tolytriazole (TTA with ST-565T). It is incumbent for the user
to idenfy the correlaon to exact wet chemistry values and potenal background interference should be
accounted for by idenfying untreated makeup for UV uorescent signal and removing that from the nal
value measured.
The ST-565 Series sensor will not work in waters containing Nitrite treatment as Nitrite absorbs UV light
and will result in a false high value. With these applicaon limitaons clearly understood, the ST-565 Se-
ries sensor is commonly used for rapid azole validaon, dramacally reducing service me enabling water
treaters to adjust their programs accordingly. It is important to note however, that there are some applica-
ons (surface makeup water systems or high organic loading/contaminated systems) where this technology
is not ideal due to a high degree of interference. The user needs to understand the dynamics of their system
and evaluate its use accordingly.
1.1 Main Features
The ST-565 Series measures Halogenated Tolytriazole (HST with ST-565)/Tolytriazole (TTA with ST-565T) in
a water sample and includes the following features:
• Easy calibraon with using uPyxis® Mobile or Desktop App.
• Automac compensaon for turbidity and color.
• Water sample does not need to be acidied. Sample pH between 6.4 to 10.0 and the sample PTSA
concentraon (<300 ppb) do not aect the azole measurement.
• Diagnosc informaon (sensor fouling, color or turbidity over range, failure modes) are available in
uPyxis® App or via Modbus RTU.
• Easy to remove from the system for cleaning and calibraon without the need for any tools.

2 Specicaons
Table 1. ST-565 Series Specicaons
Specicaon*ST-565 ST-565T
Part Number (P/N) 50664 50671
Azole Species Halogenated Tolytriazole (HST) Tolytriazole (TTA)
Azole Range (4-20mA) 0–7.5 ppm 0–10.0 ppm
Azole Accuracy ±0.2 ppm
Calibraon Two-point calibraon against standard soluon
Outputs 4–20mA Analog Output,
RS-485 Digital Output with Modbus protocol
Installaon Custom tee assembly (P/N: ST-001) with 3/4” FNPT socket & threaded ports
Cable Length 1.5 meter with IP67 connectors & 1.5 meter flying lead with IP67 adapter
Power Supply 22–26 VDC, 1 W
Dimension (L ×Dia) 6.8 ×1.44 inch (172.7 ×36.6 mm)
Weight 0.37 lbs (170 g)
Material UPVC
Operaonal
Temperature 32–120 °F (0–49 °C)
Storage Temperature -4–140 °F (-20–60 °C)
Pressure Up to 100 psi (0.7 MPa)
Flowrate 0–8 gpm (505 cm3/s)
Enclosure Rang IP67
Regulaon CE / RoHS
*With Pyxis’s connuous improvement policy, these specicaons are subject to change without noce.
3 Unpacking Instrument
Remove the instrument and accessories from the shipping container and inspect each item for any damage
that may have occurred during shipping. Verify that all accessory items are included. If any item is missing
3.1 Standard Accessories
P/N: ST-001
•Tee Assembly 3/4” NPT (1x Tee, O-ring, and Nut)
• 7-Pin Female Adapter/Flying Leads Cable (1.5 meter)P/N: MA-1100
• User Manual available online at hps://pyxis-lab.com/support/

3.2 Oponal Accessories
The following oponal accessories can be ordered from Pyxis Customer Service (or[email protected]) or
Pyxis E-Store at hps://pyxis-lab.com/shop/.
Figure 1.
Optional Accessories Information P/N
ST-001 Inline Tee Assembly Spare (3/4 –inch FNPT Inline Tee For ST Probes) 50704
HST-01 (HST Calibration Standard 1ppm for ST-565T / 500mL) 20131
HST-02 (HST Calibration Standard 2ppm for ST-565T / 500mL) 20132
TTA-01 (TTA Calibration Standard 1ppm for ST-565T / 500mL) 57015
TTA-02 (TTA Calibration Standard 2ppm for ST-565T / 500mL) 57016
Probe Cleaning Kit (Contains Probe Cleaner Solution 100mL + Qtips + Pipe Cleaners) SER-01
MA-WB Bluetooth Adapter (Pyxis Bluetooth Adapter for 7Pin Pyxis Sensors) MA-WB
PowerPACK-1 (Single Chanel Auxiliary Power Supply w/Bluetooth For Pyxis Sensors) MA-BLE-1
PowerPACK-4 (Four Chanel Auxiliary Power Supply w/Bluetooth For Pyxis Sensors) MA-BLE-4
MA-NEB Bluetooth/USB Adapter (Enables Bluetooth for Desktop and uPyxis APP) MA-NEB
SP-395 Handheld HST Fluorometer (HST 0-7.5ppm) 50209
SP-395T Handheld HST Fluorometer (TTA - 10.0ppm) 50221
MA-C10 (10’ Extension Cable for 7Pin Pyxis Sensors) 50738
MA-C50 (50’ Extension Cable for 7Pin Pyxis Sensors) 50705

4 Installaon
4.1 Piping
The ST-565 Series sensor can be installed in an inline ow applicaon using the included Pyxis ST-001 Inline
Tee Assembly. The ST-001 oers 3/4” FNPT thread or socket weld adapters with unions for easy installaon
and sensor maintenance. To properly install the ST-565 Series sensor into the ST-001 Tee Assembly, follow
the steps below:
1. Insert the provided O-ring into the O-ring groove on the tee.
2. Insert the ST-565 Series sensor into the tee.
3. Tighten the tee nut onto the tee to form a water-ght, compression seal.
Figure 2. Dimension of the ST-565 Series sensor and the ST-001 Tee Assembly (mm)

4.2 Wiring
The power ground wire (black) and the negative 4–20mA are internally connected. There is connection of
a 4-20mA- wire for ST565 series. If a separate DC power supply other than that from the controller is
used, make sure that the output from the power supply is rated for 22–26 VDC @ 65 mA.
*NOTE* The negative 24V power terminal (power ground) and the negative 4–20mA terminal on the ST-
565 Series sensor are internally connected.
Follow the wiring table below to connect the ST-565 Series sensor to a controller:
Table 2.
4.3 Connecng via Bluetooth
A Bluetooth adapter (P/N: MA-WB) can be used to connect a ST-565 Series sensor to a smart phone with
the uPyxis® Mobile App or a computer with the uPyxis® Desktop App.
Figure 3. Bluetooth connection to ST-565 Series sensor with MA-WB and uPyxis Mobile App.
ST-565 Wiring Table (HST) ST-565T Wiring Table (TTA)
Color Designation Color Designation
Red 24V+ Red 24V+
Black 24V- Black 24V-
White 4-20mA +
HST (0-7.5ppm) White 4-20mA +
TTA (0-10.0ppm)
Green No Connect Green No Connect
Blue RS-485 A Blue RS-485 A
Yellow RS-485 B Yellow RS-485 B
Clear Earth Ground Clear Earth Ground

4.4 Connecng via USB
A USB-RS485 adapter (P/N: MA-485) can be used to connect a ST-565 Series sensor to a computer with the
uPyxis® Desktop App.
*NOTE*Using non-Pyxis USB-RS485 adapters may result in permanent damage of the ST-
565 Series sensor communicaon hardware.
Figure 4. USB connection to ST-565 Series sensor with MA-485 and uPyxis Destop App.
5 Setup and Calibraon with uPyxis® Mobile App
5.1 Download uPyxis® Mobile App
Download uPyxis® Mobile App from Apple App Store or Google Play.
Figure 5. uPyxis® Mobile App installaon

5.2 Connecng to uPyxis® Mobile App
Connect the ST-565 Series sensor to a mobile smart phone according to the following steps:
1. Open uPyxis® Mobile App.
2. On uPyxis® Mobile App, pull down to refresh the list of available Pyxis devices.
3. If the connection is successful, the ST-565 Series and its Serial Number (SN) will be displayed (Figure 6).
4. Press on the ST-565 Series sensor image.
Figure 6.
5.3 Calibration Screen and Reading
When connected, the uPyxis® Mobile App will default to the Calibration screen. From the Calibration
screen, you can perform calibrations by pressing on Zero Calibration, Slope Calibration, and 4–20mA
Span. Follow the screen instructions for each calibration step.
Figure 7.

5.4 Diagnosis Screen
From the Diagnosis screen, you can check the diagnosis condion as well as Send to Pyxis. This feature
To preform a sensor Cleanliness Check, rst select the Diagnosis Condion which denes the uid type
that the ST-565 Series sensor in currently measuring, then press Cleanliness Check. If the sensor is clean, a
green Clean message will be shown. If the sensor is parally fouled, a yellow Becoming Dirty message
will be shown. If the sensor is severely fouled, a red Dirty message will be shown. In this case, follow the
procedure in the Methods to Cleaning the ST-565 Series Sensor secon of this manual.
Figure 8.

5.4 Diagnosis Screen
From the Diagnosis screen, you can check the diagnosis condion as well as Send to Pyxis. This feature
To preform a sensor Cleanliness Check, rst select the Diagnosis Condion which denes the uid type
that the ST-565 Series sensor in currently measuring, then press Cleanliness Check. If the sensor is clean, a
green Clean message will be shown. If the sensor is parally fouled, a yellow Becoming Dirty message
will be shown. If the sensor is severely fouled, a red Dirty message will be shown. In this case, follow the
procedure in the Methods to Cleaning the ST-565 Series Sensor secon of this manual.
Figure 8.
5.5 Device Info Screen
From the Device Info screen. You can name the Device or Product as well as set the Modbus address.
Figure 9.

6 Setup and Calibration with uPyxis® Desktop App
6.1 Install uPyxis® Desktop App
Download the latest version of uPyxis® Desktop software package from: https://pyxis-lab.com/upyxis/ this
setup package will download and install the Microsoft.Net Framework 4.5 (if not previously installed on the
PC), the USB driver for the USB-Bluetooth adapter (MA-NEB), the USB-RS485 adapter (MA-485), and the
main uPyxis® Desktop application. Double click the uPyxis.Setup.exe file to install.
Figure 11. uPyxis® Desktop App installation
Click Install to start the installaon process. Follow the screen instrucons to complete the USB driver and
uPyxis® installaon.
Figure 10. USB Connection to ST-565 sensor with MA-WB and MA-NEB and uPyxis Desktop App.

6.2 Connecng to uPyxis® Desktop App
Connect the ST-565 Series sensor to a Windows computer using either a Bluetooth/USB adapter (P/N: MA-
NEB) or a USB-RS485 adapter (P/N: MA-485) according to the following steps:
1. Plug the Bluetooth/USB adapter or USB-RS485 adapter into a USB port in the computer.
2. Launch uPyxis® Desktop App.
3. On uPyxis® Desktop App, click Device→Connect via USB-Bluetooth or Connect via USB-RS485 (Fig-
ure 12).
4. If the connection is successful, the ST-565 Series and its Serial Number (SN) will be displayed in the
le pane of the uPyxis® window.
*NOTE* After the sensor and Bluetooth is powered up, it may take up to 10 seconds for the
adapter to establish the wireless signal for communication.
Figure 12.

6.3 Informaon Screen
Once connected to the device, a picture of the device will appear on the top le corner of the window and
the uPyxis® Desktop App will default to the Informaon screen. On the Informaon screen you can set the
informaon descripon for Device Name,Product Name, and Modbus Address, then click Apply Sengs
to save.
Figure 13.
6.4 Calibraon Screen
To calibrate the device, click on Calibraon. On the Calibraon screen there are three calibraon tabs, Zero
Calibraon, Slope Calibraon, and 4-20mA Sp an. The screen also displays the reading of the de vice. The
reading refresh rate is every 4 seconds.
Figure 14.

6.5 Diagnosis Screen
Aer the device has been calibrated and installaon has been completed, to check diagnosis, click on Diag-
nosis. When in the Diagnosis screen you can view the Diagnosis Condion of the device. This feature may
Figure 15.
7 Outputs
7.1 4–20mA Output Setup
The 4–20mA output of the ST-565 sensor is scaled as:
• Halogenated Tolytriazole (HST):
–4 mA = 0 ppm
–20 mA = 7.5 ppm
The 4–20mA output of the ST-565T sensor is scaled as:
• Tolytriazole (TTA):
–4 mA = 0 ppm
–20 mA = 10.0 ppm

7.2 Adjusng 4–20mA Span
Users may adjust the output scale using 4–20mA Span to change the HST or TTA ppm value corresponding
to the 20 mA output via uPyxis®. For the uPyxis® Mobile App, press 4-20mA Span found on the Calibration
and Reading Screen, shown in Figure 16. For the uPyxis® Desktop App, click 4-20mA Span found on the
Calibration Screen, shown in Figure 17.
Figure 16.
Figure 17.
7.3 Communicaon using Modbus RTU
The ST-565 Series sensor is congured as a Modbus slave d evice. In addion to the HST or TTA ppm val-
ues, many operaonal parameters, including warning and error messages, are available via a Modbus RTU
connecon. Contact Pyxis Lab Customer Service ([email protected]) for more informaon.

8 Sensor Maintenance and Precauon
The ST-565 Series sensor is designed to provide reliable and connuous HST or TTA readings even when
installed in moderately contaminated industrial cooling waters. Although the opcs are compensated for
the eects of moderate fouling, heavy fouling will prevent the light from reaching the sensor, resulng in
low readings and the potenal for product overfeed if the ST-565 Series sensor is used as part of an auto-
mated control system. When used to control product dosing, it is suggested that the automaon system
be congured to provide backup to limit potenal product overfeed, for example by liming pump size or
duraon, or by alarming if the pumping rate exceeds a desired maximum limit.
The ST-565 Series sensor is designed to be easily removed, inspected, and cleaned if required. It is sug-
gested that the ST-565 Series sensor be checked for fouling and cleaned/calibrated on a monthly basis.
Heavily contaminated waters may require more frequent cleanings. Cleaner water sources with less con-
taminaon may not require cleaning for several months. The need to clean the ST-565 Series sensor can
be determined by the Cleanliness Check using the uPyxis® Mobile App (see the Mobile Diagnosis Screen
secon).
8.1 Methods to Cleaning the ST-565 Series Sensor
Any equipment in contact with industrial cooling systems is subject to many potenal foulants and contam-
inants. Our inline sensor cleaning soluons below have been shown to remove most common foulants and
contaminants. A small, so bristle brush, Q-Tips coon swab, or so cloth may be used to safely clean the
sensor housing and the quartz opcal sensor channel. These components and more come with a Pyxis Lab
Inline Probe Cleaning Soluon Kit (P/N: SER-01) which can be purchased at our online E-Store hps://pyxis-
lab.com/product/probe-cleaning-kit/
Figure 18. Inline Probe Cleaning Solution Kit

To clean the ST-565 Series sensor, soak the lower half of the sensor in 100 mL inline sensor cleaning soluon
for 10 minutes. Rinse the ST-565 Series sensor with dislled water and then check for the ashing blue light
inside the ST-565 Series sensor quartz tube. If the surface is not enrely clean, connue to soak the ST-565
Series sensor for an addional 10 minutes. Use the small, so bristle brush and Q-Tips coon swabs as
necessary to remove any remaining contaminants in the ST-565 Series sensor quartz tube.
8.2 Storage
Avoid long term storage at temperature over 100 °F. In an outdoor installaon, properly shield the ST-565
Series sensor from direct sunlight and precipitaon.
9 Troubleshoong
If the ST-565 Series sensor output signal is not stable and uctuates signicantly, make an addional ground
connecon –– connect the clear (shield, earth ground) wire to a conductor that contacts the sample water
electrically such as a metal pipe adjacent to the ST-565 Series tee.
Carry out roune calibraon vericaon against a qualied Halogenated Tolytriazole (HST with ST-565) or
Tolytriazole (TTA with ST-565T) standard. Aer properly cleaning the ST-565 Series sensor, carry out the zero
point calibraon with dislled water and slope calibraon using the qualied standard. Pyxis Lab HST Cal-
ibraon Standard can be purchased at our online Estore/Catalog hps://pyxis-lab.com/product/halogen-
stable-triazole-calibraon-standards/. Pyxis Lab TTA Calibraon Standard can be purchased at our online
Estore/Catalog hps://pyxis-lab.com/product/a-standards/.
10 Contact Us
Pyxis Lab, Inc
1729 Majesc Dr. Suite 5
Lafayee, CO 80026 USA
www.pyxis-lab.com
Phone: +1 (866) 203-8397
Email: [email protected]
Table of contents
Other Pyxis Security Sensor manuals
Popular Security Sensor manuals by other brands

MSA
MSA Ultra Elite-PF operating manual

B.E.G.
B.E.G. LUXOMAT PD4-M-1C-C-SM Installation and operating instruction

IMMOOS
IMMOOS SS1 mGB operating instructions

Prime Controls
Prime Controls LH200 operating instructions

PCB
PCB 4115K-08A Installation and operating manual

Rielta
Rielta STEKLO-3RK installation guide