QTech SMS Lite –Quick Start Guide V1.5 8
www.qtech.co.nz Ph: +64 3 366 3713 Page 8 of 21
Configuration can be sent individually with one text message per configuration
instruction or in a combined text message:
Example:
To programme the Site name to Shed1, name Input 1 as Pump and set notification
escalations to phones 1, 2 and 3.
You can either send the SMS Lite 3 individual configuration text messages:
e.g. #12345 Site:Name=Shed1.
#12345 INP1:Name=Pump.
#12345 INP1:Phones=Ph1,Ph3.
Or you can send 1 combined message:
e.g. #12345 Site:Name=Shed1. INP1:Name=Pump. INP1:Phones=Ph1,Ph2, Ph3.
When programming the alarm escalations to phone numbers it is important to note that
the numbers step in numerical order.
E.g. Ph1→Ph2→Ph4 and Ph1→Ph2→Ph3 will work however if you were to attempt to
programme Ph4→Ph2→Ph3, the configuration text would be accepted however the
escalation order would be Ph2→Ph3→Ph4.
After any configuration change you will receive either a confirmation message or an
error message. If you receive an error message, double check the configuration format
and check that there is a full stop at the end. Correct the error and resend.
Text commands can be in upper or lower case; however any capitalisation when
naming the Site, Input or Outputs will be retained.
e.g. #12345 Site:Name=Shed1. is valid as is #12345 site:name=shed1.
Note: Each Input and Output must have a unique name.
Important. The security for these messages is based on the PIN number being
correct. Any phone can be used for these commands as long as the PIN in
the message matches that printed on the SMS-Lite. If the PIN is not correct
messages will not be processed.
Examples:
#pin defaults
#pin inp1:name = alarm.
#pin inp1:phones = ph1, p2.
#pin ph1:number = 0221234567.
#pin ph2:number = 0227654321.