Qonnex DCE.230 User manual

DCE.230 DC Energy Meter
DCE.230 User Manual 1.7
1. Introducon
DCE.230 series DC energy meters are
designed for measuring and monitoring
in DC systems. The din rail DC energy
meters can measure of important DC
parameters: Voltage, current, power
and energy etc. It also support bi-
direconal measurement with pulse
output. All data in the meter are
accessible via RS485 using Modbus RTU.
The meter has DC power supply. Input
voltage range up to 1000V DC, and
current inputs are exible with DC shunt
and current sensors.
•Measures kWh, W, V, A etc.
•Bi-direconal measurement
IMP & EXP
•Pulse output
•RS485 Modbus
•Din rail mounng 35mm
•DC shunt connecon
•Class 1
1.1 General Specicaons
Voltage DC Input: 5~1000V DC
Auxiliary Supply: 9-40V DC
DC Shunt Input: 75mV
Current Range: 0~2000A
Power consumpon: ≤ 2W / 5VA
AC voltage withstand: 4400V/ 1min
Impulse voltage withstand: 6.4kV -
1.2/50μS waveform
1.2 Unit Characteriscs
The Unit can measure and display:
•voltage
•Currents
•Power
•Acve energy imported and
exported
Pulse output indicates real-me energy
measurement. An RS485 output allows
remote monitoring from another
display or a computer.
1.3 Shunt Primary Current
The unit can be congured to operate
with primary current and secondary
input.
Primary current range: 0~2000A.
Second input: 75mV
1.4 RS485 Output for Modbus RTU
For Modbus RTU, the following RS485
communicaon parameters can be
congured from the Set-up menu:
Baud rate 1200,2400, 4800, 9600,19200
Parity none (default)/odd/even
Stop bits 1 or 2
RS485 address 3-digit, 001 to 247
Modbus™ Word order Hi/Lo byte order
is set automacally to normal or
reverse. It cannot be congured
from the set-up menu.
Set-up screens are provided for seng
up the RS485 port.
1.5 Pulse output
The unit provides a pulse output. The
constant can be congured to below:
Pulse output: 1, 10, 100, 1000 imp/kWh
(default)
Pulse duraon: 60, 100 (default), 200mS
Pulse output indicate: Total kWh/
import kWh/ export kWh
Display: LCD with backlit
Max. Reading: 999999.9kWh
Weight: 220g
Standard: GB/T 33708-2017
10000 imp/kWh
1000 imp/kwh
100 imp/kWh
10 imp/kWh
1 imp/kWh
Pulse width: 200/100(default)/60 ms.
Note: the relaonship between pulse
constant and CT1
CT1
Default pulse
imp/kWh
Seable pulse
imp/kWh
1–20
1000
1000,100,10,1
21–200
100
100,10,1
201–2000
10
10,1
*when the CT seng on meter is 2000A,
the default pulse constant is 10
imp/kWh and it can be set to
10imp/kWh or 1 imp/kWh.
*Over-current alarm: Alarm will
happened when the current is over the
CT1 value set on the meter. The Alarm
LED will stay solid and the corres-
ponding register value will be changed.
The user can read this register through
communicaon to determine whether
an overcurrent alarm has occurred.
The pulse outputs can be set to generate
pulses to represent Import kWh/ Export
kWh/ total kWh.
The pulse output is passive type,
complies with IEC62053-31 Class A.
1.7 Environment
Operang temperature -25 to + 55℃
Reference temperature 23℃±2℃
Relave humidity 0 to 90%, non-
condensing
Altude up to 2000m
Installaon category CATIII
Mechanical Environment M1
Electromagnec environment E2
Degree of polluon 2
1.8 Mechanics
Din rail dimensions 36x100x63 (WxHxD)
DIN 43880
Mounng DIN rail 35mm
Ingress Protecon IP51 (indoor)
Material Self-exnguishing UL94V-0
2. Operaon
2.1 Inializaon Display
When it is powered on, the meter will
inialize and do self-checking.
Full Screen (stay
2s)
Soware Version
(stay 2s)
(This informaon
is for reference
only.)
Current Modbus
address
(stay 2s)
Current baud
rate (stay 2s)
Total acve
energy(kWh)
Total=Import+
Export
Max read:
999999.9 kWh
2.1 Buons funcon
There are two buons on the front
panel.
>Scroll the display for
data checking.
>Changing opon at
Set-up mode
>Exit the Set-up mode
>Set-up mode entry
>Conrmaon
2.1.1 Scroll display
Aer inializaon and self-checking
program, the meter displays the
measured values. The default page is
total kWh. If the user wants to check
other informaon, please press the
scroll buon on the front panel.
Total acve
energy(kWh)
Total=Import+
Export
Display format:
5+2 -> 6+1 -> 5+2
99999.99 ->
100000.0 ->
999999.9 ->
00000.00
Paral reseable
acve
energy
Display format:
5+2 -> 6+1 -> 5+2
99999.99 ->
100000.0 ->
999999.9 ->
00000.00
Voltage
Current
Power
Display format:
<1000 W: XXX W
<1000kW: XXX.XXX
kW
For other value:
XXXX.XX kW
Pulse constant
CT1 Primary
current
Meter address
Baud rate
Parity
Soware Version
Set-up Mode
To get into Set-up Mode, the user need
press the “Enter” buon for 3 second.
1 Password
To get into Set-up mode,
it asks a password
conrm. Default
password: 1000
Use Scroll and Set to
enter correct password.
2 Keep pressing Set for 3
second, the current
selecon
will ash, use Scroll and
Set to change the
Modbus address.
Opons: 1~247
Keep press Set for 3s to
conrm the selecon.
3 Keep pressing Set for 3
second, the current
selecon will ash, use
Scroll and Set to change
the Baud rate. Opons:
1.2k, 2.4k,4.8k,9.6k (
default ),19.2k
Keep press Set for 3s to
conrm the selecon.

4 Keep pressing Set for 3
second, the current
selecon will ash, use
Scroll and Set to change
the Parity.
Opons: EVEN, ODD,
NONE ( default )
5 Keep pressing Set for 3
second, the current
selecon
will ash, use Scroll and
Set to change the type
of Pulse Output.
Opons: total kWh, IMP
kWh, EXP kWh
6 Keep pressing Set for 3
second, the current
selecon will ash, use
Scroll and Set to change
the pulse constant.
Opons: 1000, 100, 10, 1
imp/kWh
*Default pulse constant
is related to the CT1
seng
7 Keep pressing Set for 3
second, the current
selecon will ash, use
Scroll and Set to change
the pulse width. Opons:
60, 100, 200, unit: ms
8 Use Scroll to select the
CT1 opon. Keep
pressing for Set 3
second, the current
selecon will ash, use
Scroll and Set to enter
the Primary current. The
range is from 0001 to
2000. For example, if
using a 100A/75mV
current transformer, the
CT1 shall be 0100.
Keep press Set for 3s to
conrm the selecon.
Default : 1A
9 Keep pressing Set for 3
second, the current
selecon will ash, use
Scroll and Set to change
the DIT(Demand
Integraon Time).
Opons: 0,5,8, 10,15,
20,30,60( default)
10 Use Scroll to select
the scroll display me
opon. Keep pressing Set
for 3 second, the current
selecon will ash, use
Scroll and Set to enter
the
opons: 0~60s.
Default: 0 s, represent do
not scroll display
11 Use Scroll to select
the backlit me opon.
Keep pressing Set for 3
second, the current
selecon will ash, use
Scroll and Set to enter
the opons:0,5,10,
20,30,60 minutes. 0
means the light is always
on. Default: 60 min.
12 Use Scroll to select
the Password opon.
Keep pressing Set for 3
second, the current
selecon will ash, use
Scroll and Set to enter
the new password. The
range is from 0001 to
9999.
Default: 1000
13 Shunt wiring
Use Scroll to select the
shunt connecon opon.
Keep
pressing Set for 3
second, the current
selecon will ash, use
Scroll to choose the
connecon way.
Opon: N, P
N: Negave type
(default)
P: Posive type
Keep pressing buon to
exit the set-up mold.
Keep pressing SCROLL buon to exit
the set-up mold.
3. Wiring diagram
3.1 Terminal Connecon
DC Power Supply:
3.2 Shunt Connecon
4. Shunt
Below a lisng of common shunt resistors
5. Dimensions
Qonnex bv
B-9310 Aalst
Belgium
Email: inf[email protected]
www.2-wire.be
Other Qonnex Measuring Instrument manuals
Popular Measuring Instrument manuals by other brands

AFL
AFL NOYES OPM Series user guide

Buhler
Buhler 222.10 Series Installation and operation instruction

Startec S.R.L.
Startec S.R.L. RAIN 260 Plus user manual

Minolta
Minolta AUTOMETER VF - PART 3 manual

Spirax Sarco
Spirax Sarco VLM30 Installation and maintenance instructions

Hach
Hach DR2400 instruction sheet

Powerfix Profi
Powerfix Profi 288019 Operation and safety notes

Hamamatsu
Hamamatsu ENERGETIQ LDLS EQ-99X Operation and maintenance manual

Hioki
Hioki 8835-01 instruction manual

Rohde & Schwarz
Rohde & Schwarz FSH4 operating manual

Deviser
Deviser TC500 Operation manual

Deltamess
Deltamess TKS-WM operating manual