manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Rayleigh Instruments
  6. •
  7. Industrial Equipment
  8. •
  9. Rayleigh Instruments RI-D340 User manual

Rayleigh Instruments RI-D340 User manual

RI-D340-IM-V02
1
RI-D340 Instrucon Manual
X 1
Safety related noficaon, symbols and instrucons that appear in this
operang manual or on the equipment must be strictly followed to
ensure the safety of personnel as well as the instrument. If the
equipment is not used in a manner specified by the manufacturer it may
impair the protecon provided by the equipment
· Do not use the equipment if there are mechanical damage
· Do not exceed the stated maximum rangs of the device
· No repairs, maintenance or adjustments are possible
· Read the complete instrucon manual prior to installaon or
operang the unit
· The equipment in its installed state must not come into close
proximity to any heang sources, oils, steam, causc vapours or
other unwanted process by-products
· Do not use in hazardous or classified locaon where explosion or
other dangers can be triggered by the device
PRODUCT SAFETY INSTALLATION PRECAUTIONS
Risk of electric shock!
Only to be installed by a competent person
· To prevent the risk of electrocuon, always isolate and lock-off the
power supply to the equipment prior to undertaking any work
· Always confirm absence of electricity prior to starng work using
appropriate voltage detecon equipment
· Wiring shall be done strictly according to the terminal layout
· Confirm that all connecons are correct before energizing the
equipment
· Roung of cables shall be way from any internal EMI source
· Copper cable should be used
· All wiring to be in accordance with applicable local standards
Once Configuraon Mode is entered, ‘Configuraon Lock’ will acvate
aer 15 minutes or if meter is switched off. No further adjustment is
possible for the lockable sengs. Unlock only by returning to supplier.
All terminal covers provided
must be fied. All cable
connecons and terminal
covers of the meter and the
CT must be secured with
sealing hasp.
Installaon must comply with MID cerfied requirements
Configuraon Lock
>> see ‘Configuraon’
for Lockable Sengs
Specificaons Accuracy
Wiring Input 3Ø 4 wire (MID Approved)
1Ø 2 wire - P1, P2, P3 (All MID Approved) Voltage V L-N and V L-L ±0.5% of full scale
Rated Input Voltage 3x 85...240V AC (L-N), 147...415V AC (L-L) Current ±0.5% of full scale
Frequency 45...65Hz (MID approved @50Hz) Frequency for L-N > 20V, L-L > 35V ±0.1% of full scale
CT Primary 1...6,000A configurable Acve, Reacve and Apparent Power 1%
CT Secondary 0.01...1(1.2)A (Meter Input: 330mV) Power Factor ±0.01 of Unity
VT Primary 100...600V configurable Acve Energy EN50470-3: Cl.B
VT Secondary 100...500V AC (L-L) configurable Reacve Energy EN62053-23: Cl.2
Voltage Rated Burden < 8VA
Display Update Rate 1 sec all parameters Wh Resoluon and Default Pulse Weight
Operang / Storage Temperature -10…55°C / -20…75°C
Example
If CT Primary = 200A (CT rao = 200/1 = 200) & VT = 350/350V (VT Rao = 1)
Wh resoluon = 1kWh (200 x 1 = <1500) | Pulse O/P default = 1kWh/pulse
Humidity 0...85% non-condensing
Protecon Degree (IEC/EN60529) IP54 (front of Housing), IP20 (terminals)
Communicaon Modbus RTU over RS485
MBus (EN13757)
Auxiliary Supplied from any phase Apparent Energy Class 1
CT Rao x VT Rao <15 <150 <1500 <15000 >15000
Wh / kArh / VAh / 0.01k 0.1k 1k 0.01M 0.1M
EO&E: Document subject to change
1x 3Ø
1x 1Ø
3x 1Ø
RI-D340-G-C
RI-D340-G-MB
RTU
Pulse SO
RI-D340-IM-V02
2
1 RJ45 cable
2 Fuse class CC UL / fast acng
3 Phase 600V/Single Phase 250V
3 Supply 31 addional meters (32 total)
4 For ’Volt-free’ PLC or digital input, voltage must
be provided by the addion of a DC PSU
5 For Single Phase Easywire CT - Set Phase
Network to 1P2W-P1, Voltage Reference V1
must be same phase as CT. Connect V2/V3 to N.
WIRING
Modbus / MBus
Wiring Topology
Daisy Chain Star Network
Modbus ü û
MBus ü ü
A | B
+ | -
1 | 2
Typical Modbus
configuraon shown
For MBus interface
follow Wiring
Topology below
500m Max, ≤ 32 meters
DIN rail mounted, this device must be installed within
a suitable IP rated enclosure. Indoor use only.
The meter is intended to be installed in Mechanical
Environment ‘M1’, with Shock and Vibraons of low
significance, as per 2014/32/EC Direcve.
The meter is intended to be installed in Electromag-
nec Environment ‘E2’, as per 2014/32/EC Direcve.
Installaon Category III (300V L-N)
Protecon Class: II Polluon degree: II
MECHANICAL INSTALLATION
DISMOUNT
No. Meters ≤ 5 ≤ 10 ≤ 20 ≤ 32
Fuse Rang 0.5A 1A 1.5A 2A
Single Core 0.5 > 4mm2
Ø 2.5mm Max Stranded 0.5 > 2.5mm2
7mm + Ø 2.5mm
0.5 Nm
Max
CT phase rotaon is
RH/LH dependant
refer to Configuraon
1 Channel
3P4W or
1P2W P1,P2 or P3
3 CH 1P2W-P1 (3x L1) 3 CH 1P2W-P2 (3x L2) 3 CH 1P2W-P3 (3x L3)
RI-D340-IM-V02
3
D340-G-C
D340-G-MB
Seng
= MID CONFIG LOCK
(refer to page.1)
Default Adjustment Range Network
& CT
Must
configure
VT
Adjust if
Using VT
Comms
Modbus /
MBus
Pulse O/P
Adjust if
ulised
System
Sengs
Oponal
1 1 Change Password 1000 NO / YES (0000 > 9998) ü
2 2 Channel Selecon 1 CH 1 CH (3P4W or 1P2W)
3 CH (3x 1P2W)
3 3 Phase Network Selecon 3P4W 3P4W, 1P2W-P1/P2/P3
4 4 CT Secondary 1 Non-adjustable
5 5 CT Primary (see CT Label) 1 1 - 6000A
6 6 Current Connecon - see RHS RHS / LHS
7 7 PT Secondary 350 100 > 500V
8 8 PT Primary 350 100 > 600V
9 9 Slave ID Modbus:
MBus (Primary ID):
1
1
1 > 255
1 > 250 ü
10 10 Baud rate Modbus:
MBus:
9600
2400
300 > 19200 bps
1200 > 9600 ü
11 11 Parity Modbus:
MBus:
None
Even
None / Odd / Even
Even ü
12 12 Stop Bit Modbus:
MBus:
1
1
1 / 2
1 ü
13 13 Back Light Off (0000 = Never) 0000 0 > 7200 Sec ü
14 14 Demand interval method Sliding Sliding / Fixed ü
15 15 Demand interval duraon 15 1 > 30 min ü
16 16 Demand interval length 1 1 > 30 min ü
17 17 Pulse Weight 0.10 0.01 > 9.99 kWh/imp
18 18 Pulse Duraon 200 50 > 300 mS ü
19 20 Factory Default No No / Yes Does not reset energy & demand values
20 21 Reset Energy & Demand No No / Yes (Password +1) Once entered, reset each value individually
X 19 MBus Secondary ID Serial # 0000 0000 > 9999 9999 ü
CONFIGURATION
CT Phase Rotaon
RHS
LHS
Step A: Enter Configuraon Menu Step B: Configure each seng, as required, referring to
Config Table below, using the buons as follow:
1 Press once to make digit or opon flash, press again to
move flashing cursor
2 Press to change digit or opon, press to move
cursor posion as required
3 Press to save and move to next seng opon, Exit
menu once all sengs are configured (see Step A)
Hold 3 Secs to
Enter Config
(same to Exit)
Password = 1000
(Refer to Step 2)
2
1
RI-D340-IM-V02
4
OPERATION
1 Display Symbols:
Avg Average of 3-phase
tOt Total of 3-phase
MD Max/Min Demand
L-N Line to Neutral
RS485 communicaon in progress
2 Measurement Units (refer to Funcons Table below)
V, kWh, kVArh, kVAh, A, Hz, kW, kVAr, kVA
3 Navigaon Buons: Change PARAMETER
Change PAGE
(hold 10 sec: Serial #)
4 HOLD 10 Secs to check Current Connecon
5 Integraon of Energy Indicator (blinks at rate of INT)
x1
Voltage x2
Current x3
V/A/F/PF x4
PF & Power
Avg Voltage (V L-N)
Acve Energy (kWh)
Phase Voltage
(V L-N)
Phase Current
(A)
Avg Voltage (V L-N)
Total Current (A)
Frequency (Hz)
Avg Power Factor
Phase Power Factor
Frequency (Hz)
x1 Avg Voltage (V L-N)
Reacve Energy (kVArh)
Phase Voltage
(V L-L)
Avg Voltage (V L-L)
Total Current (A)
Frequency (Hz)
Avg Power Factor
Phase Acve Power (kW)
x2 Phase Reacve Power (kVAr)
x3 Phase Apparent Power (kVA)
x4 tOt Acve Power (kW)
x5 tOt Reacve Power (kVAr)
x6 tOt Apparrent Power (kVA)
x7 tOt Acve Max MD (kW)
x8 tOt Reacve Max MD (kVAr)
Energy
Parameters in BOLD not
displayed for 1P2W
1 CHANNEL
Energy x1
Voltage x2
Current x3
PF & Power
Avg Voltage (V L-N)
CH1 Acve Energy (kWh)
Phase Voltage
(V L-N)
Phase Current
(A)
Phase Power Factor
Frequency (Hz)
x1 CH1 Reacve Energy (kVArh) Phase Acve Power (kW)
x2 CH2 Acve Energy (kWh) Phase Reacve Power (kVAr)
x3 CH2 Reacve Energy (kVArh) Phase Apparent Power (kVA)
x4 CH3 Acve Energy (kWh) tOt Acve Power (kW)
x5 CH3 Reacve Energy (kVArh) tOt Reacve Power (kVAr)
x6 tOt Acve Energy (kWh) tOt Apparrent Power (kVA)
x7 tOt Reacve Energy (kVArh) Phase Acve Max MD (kW)
x8 Phase Reacve Max MD (kVAr)
3 CHANNEL Voltage Phase Rotaon
Hold 3 Sec
OK CLK: L1 → L2 → L3
ANTI-CK: Incorrect Order
INVAL Id: Missing Phase û
ü
Rayleigh Instruments Limited (Head Office)
Raytel House, Cutlers Road, South Woodham Ferrers, Chelmsford, Essex. CM3 5WA
W: www.rayleigh.com E: sales@rayleigh.com
Rayleigh Instruments Limited SP. Z o.o. (European Office)
Ul. Aleje Jerozolimskie 214, Warsaw, Poland, 02-486
W: www.rayleigh.pl E: sales@rayleigh.pl

Popular Industrial Equipment manuals by other brands

WÜRGES HV Series operating instructions

WÜRGES

WÜRGES HV Series operating instructions

Universal MC-10NI Series owner's manual

Universal

Universal MC-10NI Series owner's manual

Blastrac 500HSH operating instructions

Blastrac

Blastrac 500HSH operating instructions

THORLABS IO-F-940 user guide

THORLABS

THORLABS IO-F-940 user guide

Ormandy Group Breeze operating & maintenance manual

Ormandy Group

Ormandy Group Breeze operating & maintenance manual

Graco LineLazer III 200HS Operation

Graco

Graco LineLazer III 200HS Operation

RS 32-05000 Operation manual

RS

RS 32-05000 Operation manual

MIYAWAKI RE2 Series Operation manual

MIYAWAKI

MIYAWAKI RE2 Series Operation manual

ABB A145-M55 Operation manual

ABB

ABB A145-M55 Operation manual

Convectium 710Shark Training manual

Convectium

Convectium 710Shark Training manual

Datcon DT1102 M (PS) operating instructions

Datcon

Datcon DT1102 M (PS) operating instructions

Rapid Packaging Eastey Value Series user guide

Rapid Packaging

Rapid Packaging Eastey Value Series user guide

altitude A2 Assembly instructions

altitude

altitude A2 Assembly instructions

Graham Field LUMEX LX6690-1 Assembly and installation instructions

Graham Field

Graham Field LUMEX LX6690-1 Assembly and installation instructions

CKD ESM Series manual

CKD

CKD ESM Series manual

HPSi 300 Operator, maintenance and parts manual

HPSi

HPSi 300 Operator, maintenance and parts manual

Bowers & Wilkins TS10055 Adjusting Manual

Bowers & Wilkins

Bowers & Wilkins TS10055 Adjusting Manual

Toro Workman Topdresser 1800 Operator's manual

Toro

Toro Workman Topdresser 1800 Operator's manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.