manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Raypak
  6. •
  7. Boiler
  8. •
  9. Raypak DELTA LIMITED 989B-2339B User manual

Raypak DELTA LIMITED 989B-2339B User manual

Project Name / Date Division 23 52 33.13 - 1
DIVISION 23 52 33.13
FINNED WATER-TUBE BOILERS
PART 1 - GENERAL
1.1 SUMMARY
A. Section includes gas-fired, copper finned-tube hydronic heating boilers
B. Related Sections
Specifier Note: Use as needed
1. Building Services Piping – Division 23 21 00
2. Breeching, Chimneys, and Stacks (Venting) – Division 23 51 00
3. HVAC Instrumentation and Controls – Division 23 09 00
4. Electrical – Division 23 09 33
1.2 REFERENCES
A. ANSI Z21.13/CSA 4.9
B. ASME, Section IV
C. 2006 UMC, Section 1107.6
D. ANSI/ASHRAE 15-1994, Section 8.13.6
E. National Fuel Gas Code ANSI Z223.1/NFPA 54
F. I=B=R
G. NEC
H. ASME CSD-1, 2006
1.3 SUBMITTALS
A. Product data sheet (including dimensions, rated capacities, shipping weights, accessories)
B. Wiring diagram
C. Warranty information
D. Installation and operating instructions
1.4 QUALITY ASSURANCE
A. Regulatory Requirements
1. ANSI Z21.13/CSA 4.9
2. Local and national air quality regulations for low NOx (0-30 PPM NOx emissions) boilers
B. Certifications
1. CSA
2. ASME H Stamp and National Board Listed
3. ISO 9001
1.5 WARRANTY
A. Limited one-year warranty from date of installation
B. Limited twenty-year thermal shock warranty
C. Limited ten-year closed-system heat exchanger warranty
PART 2 - PRODUCTS
2.1 MANUFACTURER
A. Raypak, Inc.
1. Contact: 2151 Eastman Ave., Oxnard, CA 93030; Telephone: (805) 278-5300;
DELTA
LIMITED
™, TYPE H
-
MODELS
98
9
B
-
233
9
B
SUGGESTED SPECIFICATIONS
Catalog No.: 2000.98A
Effective: 11-15-08
Replaces: 9-15-02
Project Name / Date Division 23 52 33.13 - 2
Fax: (800) 872-9725; Web site: www.raypak.com
2. Product: Delta Limited™ copper finned-tube hydronic boiler(s)
2.2 BOILERS
A. General
1. The boiler(s) shall be fired with gas at a rated input of BTU/hr.
2. The boiler(s) shall be CSA tested and certified with a minimum thermal efficiency of 84 percent
at full fire.
3. The boiler(s) shall be ASME inspected and stamped and National Board registered for 160
PSIG working pressure, complete with a Manufacturer's Data Report.
4. The boiler(s) shall have a floor loading of 65 lbs. /square foot or less.
B. Heat Exchanger
1. The heat exchanger shall be of a single-bank, horizontal-grid design with twelve integral
copper finned tubes, each end of which is rolled into an ASME boiler-quality steel tube sheet.
2. The heat exchanger shall be sealed to 160 PSIG rated Cast Iron headers with silicone "O"
rings, having a temperature rating over 500°F.
3. The low water volume heat exchanger shall be explosion-proof on the water side and shall
carry a twenty-year warranty against thermal shock.
4. The headers shall be secured to the tube sheet by stud bolts with flange nuts to permit
inspection and maintenance without removal of external piping connections.
5. The boiler(s) shall be capable of operating at inlet water temperatures as low as 105°F without
condensation.
6. The boiler(s) shall be designed to accommodate field changes of either left or right hand
plumbing and electrical while leaving the tube bundle in place.
C. Burners
1. The tubular burners shall have multiport radial gas orifices, punched ports and slots, be
capable of quiet ignition and extinction without flashback at the orifice, and be manufactured
from corrosion resistant titanium-stabilized stainless steel with low expansion coefficient.
2. The burners will be supplied with a fan-assisted, clean burning, and highly efficient fuel-air
mixture.
D. Pilot Control System
1. The boiler(s) shall be equipped with a 100 percent safety shutdown system.
2. The ignition shall be Hot Surface Ignition type with full flame rectification by remote sensing
separate from the ignition source, with a three-try-for-ignition sequence, to ensure consistent
operation.
3. The igniter will be located away from the water inlet to protect the device from condensation
during startup.
4. The ignition control module shall include an LED that indicates six (6) individual diagnostic
flash codes.
5. Two external viewing ports shall be provided, permitting visual observation of burner
operation.
E. Gas Train
1. The boiler(s) shall have a firing/leak test valve and pressure test valve as required by CSD-1.
2. The boiler(s) shall have dual-seated main gas valve(s).
3. Gas control trains shall have a redundant safety shut-off feature, main gas regulator, shut-off
cock and plugged pressure tapping to meet the requirements of ANSI Z21.13/CSA 4.9.
F. Boiler Control
1. The following safety controls shall be provided:
a. High limit control
b. Flow switch, mounted and wired
c. ____PSIG ASME pressure relief valve, piped by the installer to an approved drain
d. Temperature and pressure gauge
2. The boiler(s) shall be equipped with a fixed five-minute energy-saving pump control relay,
Project Name / Date Division 23 52 33.13 - 3
mounted and wired, which automatically shuts off the boiler pump at a set period after boiler
shut-down to avoid standby losses associated with constant pump operation.
G. Firing Mode
1. For model 989B, provide two-stage firing control of the gas input to the boiler.
2. For model 1259B, provide three-stage firing control of the gas input to the boiler.
3. For models 1529B – 2339B, provide four-stage control of the gas input to the boiler.
H. Boiler Diagnostics
1. Provide external LED panel displaying the following boiler status/faults:
a. Power on - Green
b. Call for heat – Amber
c. Burner on – Blue
d. Safety fault - Red
2. A Central Point Wiring board with diagnostic LED’s indicating the status of each relay.
3. Provide ignition module indicating the following flash codes by LED signal:
a. 1 flash – low air pressure
b. 2 flashes – flame in the combustion chamber w/o CFH
c. 3 flashes – ignition lock-out (flame failure)
d. 4 flashes – low hot surface igniter current
e. 5 flashes – low 24VAC
f. 6 flashes – internal fault
I. Combustion Chamber: The lightweight, high temperature, multi-piece, interlocking ceramic fiber
combustion chamber liner shall be sealed to reduce standby radiation losses, reducing jacket
losses and increasing unit efficiency.
J. Venting
1. When routed vertically, the boiler’s flue material and size shall be in accordance with the
National Fuel Gas Code, ANSI Z223.1/NFPA54 latest edition (Category I).
2. When routed horizontally, the boiler(s) flue material and size shall meet or exceed the
requirements as specified for Category III in the National Fuel Gas Code, ANSI Z223.1/NFPA
54 latest edition.
3. The boiler(s) shall be ducted combustion air ready.
K. Cabinet
1. The corrosion-resistant galvanized steel jackets shall be finished with a baked-on epoxy
powder coat which is suitable for outdoor installation, applied prior to assembly for complete
coverage, and shall incorporate louvers in the outer panels to divert air past heated surfaces.
2. The boiler(s), if located on a combustible floor, shall not require a separate combustible floor
base.
3. The boiler(s) shall have the option of venting the flue products either through the top or the
back of the unit.
4. Combustion air intake shall be on the left side of the cabinet, right side optional.
L. Operating Controls
1. The boiler(s) shall feature an optional multi-stage digital controller with adjustable outdoor
reset, mounted and wired.
2. Water and air temperature sensors shall be shipped loose for field installation by installing
contractor.
Specifier Note: The remaining items in this section are options. Delete those that are not being
specified. IMPORTANT: The Cold Water Start and Cold Water Run Systems cannot be
used on the same boiler.
M. Boiler Pump - Refer to Equipment Schedule
N. SureRack™ Boiler Stacking Kit
1. The boilers shall be stacked directly one on top of the other, without offset, to minimize
footprint.
O. Cold Water Start System
1. The boiler(s) shall be configured with a cold water start automatic proportional by-pass system
Project Name / Date Division 23 52 33.13 - 4
that ensures the boiler will experience inlet temperatures in excess of 105ºF in less than 7-
minutes to avoid damaging condensation. The unit will automatically shut down if the inlet
temperature is not achieved within the 7-minute time frame.
2. The cold water start system shall be configured with a modulating three-way valve that is
controlled by a system-matched PID controller. The PID controller temperature sensor shall be
located in the inlet header of the boiler.
3. The control shall have a temperature setting dial located on the face of the board. The
temperature range of the dial shall be 105ºF to 120ºF. The PID Logic shall be capable of
limiting system overshoot to a maximum of 10ºF on initial start-up or call-for-heat.
4. The cold water start system shall be completely wired and mounted at the factory.
5. The control shall have the following diagnostic LED’s:
a. Call for heat
b. Start-up mode
c. Inlet temperature error
d. Sensor out of range
6. The controller shall have the capability to add optional alarm contacts.
P. Cold Water Run System
1. The boiler(s) shall be configured with a cold water run automatic proportional by-pass system
that ensures the boiler will experience inlet temperatures in excess of 105ºF in less than 7
minutes to avoid damaging condensation. The unit will automatically shut down if the inlet
temperature is not achieved within the 7-minute time frame.
2. The cold water run system shall be configured with a variable-speed pump that is controlled by
a system-matched PID control that injects the correct amount of cold water directly into the
boiler loop to maintain a minimum inlet temperature. The PID controller temperature sensor
shall be located in the inlet header of the boiler.
3. The control shall have a temperature setting dial located on the face of the board. The
temperature range of the dial shall be 105ºF to 120ºF. The PID Logic shall be capable of
limiting system overshoot to a maximum of 10ºF on initial start-up or call-for-heat.
4. The cold water start system shall be completely wired and mounted at the factory.
5. The control shall have the following diagnostic LED’s:
a. Call for heat
b. Start-up mode
c. Inlet temperature error
d. Sensor out of range
6. The controller shall have the capability to add optional alarm contacts.
2.3 SOURCE QUALITY CONTROL
A. The boiler(s) shall be completely assembled, wired, and fire-tested prior to shipment from the
factory.
B. The boiler(s) shall be furnished with the sales order, ASME Manufacturer’s Data Report,
inspection sheet, wiring diagram, rating plate and Installation and Operating Manual.
PART 3 - EXECUTION
3.1 INSTALLATION
A. Must comply with
1. Local, state, provincial, and national codes, laws, regulations and ordinances
2. National Fuel Gas Code, ASNI Z223.1/NFPA 54 – latest edition
3. National Electrical Code, ANSI/NFPA 70 – latest edition
4. Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1,
when required
5. Canada only: CAN/CSA B149 Installation Code and CSA C22.1 CEC Part I
6. Manufacturer’s installation instructions, including required service clearances and venting
guidelines
B. Manufacturer’s representative to verify proper and complete installation.
Project Name / Date Division 23 52 33.13 - 5
3.2 START-UP
A. Shall be performed by Raypak factory-trained personnel.
B. Test during operation and adjust if necessary:
1. Safeties (2.2 - F)
2. Operating Controls (2.3)
3. Static and full load gas supply pressure
4. Gas manifold and blower air pressure
C. Submit copy of start-up report to Architect and Engineer.
3.3 TRAINING
A. Provide factory-authorized service representative to train maintenance personnel on procedures
and schedules related to start-up, shut-down, trouble shooting, servicing, and preventive
maintenance.
B. Schedule training at least seven days in advance.
END OF SECTION
Catalog No.: 2000.471C Effective: 03-15-14 Replaces: 01-01-14
Job:
Engineer:
Contractor:
Prepared By: Date:
Model: Indoor/Outdoor: MBTUH Input:
100% Factory Fire Tested
Efficiency: 84%
Maximum Outlet Temperature: 230°F
Minimum Non-Condensing Inlet Temperature: 105°F
Thermal Shock Proof Heat Exchanger
Limited Twenty-Year Thermal Shock Warranty
Limited Ten-Year Closed-System Heat Exchanger
Warranty
PolyTuf Powder Coated Cabinet
No Combustible Floor Shield Required
Fan-Assisted
Patented Burner Security Blanket
Heat Exchanger
 H Stamp
 Headers
Glass-Lined Cast Iron – Standard
Bronze – Option A-1
 ASME Inspected and Stamped
160 PSIG Working Pressure
 National Board Approved
 Fin Tubing
Copper – Standard
Cupro Nickel – Option A-3
 ASME Steel Tube Sheet
 Silicone High Temp O-Rings
 ASME Pressure Relief Valve
60 PSIG – Standard
30 PSIG – Optional
 Temperature and Pressure Gauge
 Water Connections
Left – Standard
Right – Option A-6
Controls
 120V, 60Hz, 1 Phase Power
Supply
 120/24V 60Hz Transformer
 100% Shut-Off/Lockout
 Hot Surface Ignition
 Remote Flame Sensor
 High Limit Control, Manual Reset
 On/Off Power Switch
 Manual Shut-Off, Front-Mounted Switch
 Flow Switch
 Blocked Vent Pressure Switch
 Combustion Air Proving Switch
 Pump Time Delay Relay
 Status Display Lights
Gas Train
 Manual Gas Shut-Off Valve(s)
 Combination Valves
 Low Gas Pressure Switch, Manual
 Firing Stages
2-Stage: Model 989B
3-Stage: Model 1259B
4-Stage: Models 1529B-2339B
 Fuel
Natural Gas
Propane Gas
 Design Certified - ANSI
Z21.13/CSA 4.9
Burner
 Ultra-Low NOx: Less than
20 PPM
Construction
 Indoor/Outdoor Construction
 Enclosed Front Controls
 CSA Low Lead Certified ≤ .25 Pb
Venting
 Vent Location
Top, Outdoor – Standard
Top, Indoor – Option D-20
Rear – Option D-14
 Vent Termination Cap
Outdoor D-11
Indoor, Horizontal D-15
Indoor, Vertical (by others)
 Extractor – Optional
By others
Not required
Temperature Controls
B-6 Aquastat, 2-Stage (100-200ºF)
B-__ TempTracker Digital Controller,
2-Stage (Loose)
B-__ TempTracker Digital Controller,
4-Stage (Loose)
B-__ TempTracker Mod+ Hybrid (2-
16 Boilers)
B-60 Stage Interface
Options
C-6 Ignition Module, Manual Reset
F-10 Low Water Cut-Off, Remote
Probe
I-1 High Limit Control, Auto Reset
P- Pump: HP, 120V,
1, 60Hz
Cast Iron Bronze
Mounted Loose
Front Rear
P- Cold Water Start
(See 2000.48)
S-2 High Gas Pressure Switch,
Manual
X-1 SureRack™ Kit
X-2 SureRack Add-on
Regulatory Agency Requirements
Delta Limited™ - Type H
Space Heating/Hot Water Boiler
Models 989B-2339B
Shown with outdoor
air inlet and pump covers
Proudly Made in the U.S.A.
Delta Limited models not approved for use in California
H9-1529B
Catalog No.: 2000.471C Effective: 03-15-14 Replaces: 01-01-14
Raypak, Inc.

2151 Eastman Avenue, Oxnard, CA 93030

(805) 278-5300

Fax (800) 872-9725

www.raypak.com
Delta Limited – Type H
Models 989B-2339B Model
SPECIFICATIONS
Approx.
MBTUH
Firing
A
H
K
W
Amp.
Shipping
Model Input Output Stages Width NPT Draw* Wt. (Lbs.)
989B 990 832 2 57-1/8 2-1/2 10 16-13/16 < 12 900
1259B 1260 1058 3 68-1/2 2-1/2 12 20-9/16 < 12 1010
1529B 1530 1285 4 79-7/8 2-1/2 12 24-3/8 < 12 1225
1799B 1800 1512 4 91-1/8 2-1/2 14 28-1/8 < 12 1350
1999B** 1999 1679 4 102-1/2 2-1/2 14 31-15/16 < 12 1450
2069B 2070 1739 4 102-1/2 2-1/2 14 31-15/16 < 12 1450
2339B 2340 1966 4 113-7/8 2-1/2 16 35-11/16 < 12 1520
* Pump not included
** Natural Gas Only
Dimensions are in inches.
Rates shown are for natural or propane gas, and elevations up to 4,500 feet. For installation above 4,500
feet, please contact manufacturer.
Recommended natural gas supply pressure is 7 – 10.5” WC. Recommended propane gas supply pressure is
11 - 13” WC.
NOTE:
Pump location varies
based on model selected
RATES OF FLOW AND PRESSURE DROPS
20°F ∆T
30°F ∆T
Min. Flow
Max. Flow
Model
GPM
∆P (ft)
GPM
∆P (ft)
GPM
∆P (ft)
∆T GPM
∆P (ft)
∆T
989B 84 5.6 56 2.5 42 1.5 40 132 14.0 13
1259B
107 10.0 71 4.5 53 2.6 40 132 15.5 16
1529B
130 16.0 86 7.1 65 4.1 40 132 16.5 20
1799B
N/A N/A 102 10.8 76 6.0 40 132 18.0 23
1999B
N/A N/A 113 14.0 85 8.1 40 132 19.5 26
2069B
N/A N/A 117 15.0 88 8.7 40 132 19.5 27
2339B
N/A N/A 132 21.0 99 12.0 40 132 21.0 30
Basis is 40°F ∆T for minimum flow, 132 GPM for maximum flow.

Other Raypak Boiler manuals

Raypak 0133-4001 User manual

Raypak

Raypak 0133-4001 User manual

Raypak FlexGas 302BD-2342BD User manual

Raypak

Raypak FlexGas 302BD-2342BD User manual

Raypak HI DELTA 302B User manual

Raypak

Raypak HI DELTA 302B User manual

Raypak RAYTHERM 133-4001 Manual

Raypak

Raypak RAYTHERM 133-4001 Manual

Raypak 2503 Manual

Raypak

Raypak 2503 Manual

Raypak 751 User manual

Raypak

Raypak 751 User manual

Raypak 399B-2339B Manual

Raypak

Raypak 399B-2339B Manual

Raypak Hydronic Space Heating 42-180 User manual

Raypak

Raypak Hydronic Space Heating 42-180 User manual

Raypak 503-2003 Manual

Raypak

Raypak 503-2003 Manual

Raypak MVB TYPE B 504-2004 Manual

Raypak

Raypak MVB TYPE B 504-2004 Manual

Raypak 0133-4001 User manual

Raypak

Raypak 0133-4001 User manual

Raypak 504-2004 Guide

Raypak

Raypak 504-2004 Guide

Raypak 0090B 0135B User manual

Raypak

Raypak 0090B 0135B User manual

Raypak XFYRE 500 User manual

Raypak

Raypak XFYRE 500 User manual

Raypak 0180B  Type H User manual

Raypak

Raypak 0180B Type H User manual

Raypak 302BE-902BE User manual

Raypak

Raypak 302BE-902BE User manual

Raypak XPAK 85 Guide

Raypak

Raypak XPAK 85 Guide

Raypak Commercial Space Heating and Domestic Water User manual

Raypak

Raypak Commercial Space Heating and Domestic Water User manual

Raypak RAYTHERM 0042B Manual

Raypak

Raypak RAYTHERM 0042B Manual

Raypak Hi Delta FlexGas 992BD User manual

Raypak

Raypak Hi Delta FlexGas 992BD User manual

Raypak DEL TA LIMITED 399B User manual

Raypak

Raypak DEL TA LIMITED 399B User manual

Raypak 88AR-398A Manual

Raypak

Raypak 88AR-398A Manual

Raypak XFYRE 500 Guide

Raypak

Raypak XFYRE 500 Guide

Raypak Raytherm H-181 User manual

Raypak

Raypak Raytherm H-181 User manual

Popular Boiler manuals by other brands

Ideal Boilers Mexico Super RS 3/40 Installation & servicing manual

Ideal Boilers

Ideal Boilers Mexico Super RS 3/40 Installation & servicing manual

DeDietrich GT 334 Assembly instructions

DeDietrich

DeDietrich GT 334 Assembly instructions

Vaillant ecoTEC exclusive SERIES Installation and maintenance instructions

Vaillant

Vaillant ecoTEC exclusive SERIES Installation and maintenance instructions

Atlantic Boilers Multi-Elec Compacte Series Technical manual

Atlantic Boilers

Atlantic Boilers Multi-Elec Compacte Series Technical manual

Market Forge Industries M24G Parts and service manual

Market Forge Industries

Market Forge Industries M24G Parts and service manual

DOM Tronic Slim Assembly

DOM

DOM Tronic Slim Assembly

Harsco Industrial MACH C-750GG Installation & owner's manual

Harsco Industrial

Harsco Industrial MACH C-750GG Installation & owner's manual

THERMOSTAHL ENP 20 Installation and service manual

THERMOSTAHL

THERMOSTAHL ENP 20 Installation and service manual

Ferroli Combi 77 FF Installation

Ferroli

Ferroli Combi 77 FF Installation

Bryan Boilers Concert Instruction and operation manual

Bryan Boilers

Bryan Boilers Concert Instruction and operation manual

Grant Combi 90 V3 User, installation & servicing instructions

Grant

Grant Combi 90 V3 User, installation & servicing instructions

Potterton Assure Heat 13 Installation and service manual

Potterton

Potterton Assure Heat 13 Installation and service manual

PEERLESS Gas Boiler Installation & maintenance manual

PEERLESS

PEERLESS Gas Boiler Installation & maintenance manual

Centrometal EKO-CKS P 140 Technical instructions

Centrometal

Centrometal EKO-CKS P 140 Technical instructions

Calomax Clipper 2 5L Installation, operation and servicing instructions

Calomax

Calomax Clipper 2 5L Installation, operation and servicing instructions

THERMOSTAHL ENERDENSE Installation and service manual

THERMOSTAHL

THERMOSTAHL ENERDENSE Installation and service manual

Potterton Sirius two FS 50 Installation and service manual

Potterton

Potterton Sirius two FS 50 Installation and service manual

Biasi B3 Manual and installation instructions

Biasi

Biasi B3 Manual and installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.