RECO EasyLine RM-216 C User manual

Operating and Installation Instructions
Filter control system
RM-216 C
EasyLine

RM-216 C.10 Easy Line Documentation
RDN 10000029 2 13.05.2014
Table of Contents
1 Safety instructions...................................................................................................................................3
2 Equipment specification ..........................................................................................................................3
3 Assembly................................................................................................................................................. 4
4 “Step by step” installation ........................................................................................................................4
5 “Step by step” settings.............................................................................................................................7
5.1 Function when shipped................................................................................................................. 7
5.2 Setting parameters .......................................................................................................................7
5.3 Parameter list ...............................................................................................................................9
6 Operating modes...................................................................................................................................10
6.1 Test mode................................................................................................................................... 10
6.2 ∆p-Mode (differential pressure controlled cleaning)....................................................................10
6.3 Down time cleaning modes.........................................................................................................10
6.4 Cleaning via start/stop input (external ∆p switch) .......................................................................12
7 Troubleshooting ....................................................................................................................................13
8 Text messages on the display............................................................................................................... 14
9 Details on the equipment function......................................................................................................... 15
10 Glossary ..............................................................................................................................................16
11 Technical specifications ......................................................................................................................18
Regulations
VDE 0160 EN 60.439 Part 500
EN 50178 2004/108 EC
Legend
Important note
Important warning

RM-216 C.10 Easy Line Documentation
RDN 10000029 3 13.05.2014
1 Safety instructions
The filter control system RM-216 C when connected to the mains poses an electrical hazard. Device
failure, serious or even fatal injuries may occur as a result of improper installation of the connected
equipment. Consequently, follow in particular the points set out below in addition to the general safety
regulations for equipment in industrial electrical installations:
- Installation of the device may be carried out only by qualified experts, in accordance with the
provisions of IEC 364, DIN VDE 0105 for electrical equipment.
- All applicable laws, conditions, orders and regulations governing the setting up of electrical equipment
must be observed with respect to the installation site.
- Setting of equipment with degree of protection IP00 without covers, may only be performed by
authorized expert staff, when disconnected, and whilst observing the local safety and accident
prevention regulations.
The RM-216 C may only be operated in the permitted operating area.
Switch off the mains supply before replacing the filter control or any components connected to
it. Otherwise the equipment may be damaged.
2 Equipment specification
The RM-216 C is used to control 24 V DC solenoid valves on filtering separators with compressed air
pulse cleaning. After connecting the supply voltage, the filter control system functions fully automatically
without further activation. With ∆p mode switched on, the current differential pressure of the filter system
is displayed on the text display. The cleaning is carried out depending on the differential pressure. The
filter can be monitored via a ∆p alarm switch point (∆p alarm).
The full scale output for the measured differential pressure can be set by the parameter 15 "dP range".
The anlog output signal is automatically adjusted to the set full scale output.

RM-216 C.10 Easy Line Documentation
RDN 10000029 4 13.05.2014
3 Assembly
4 “Step by step” installation
Supply voltage connection
A separate
power supply unit is recommended for the operation of the filter controller with
extra low voltage.
The unit can be operated with a supply voltage of 24 V DC, if no expansion modules are
connected and if the electric cables (minimum cross-section: 0.75 mm²) to the solenoid valves
are shorter than 10 meters long.

RM-216 C.10 Easy Line Documentation
RDN 10000029 5 13.05.2014
Solenoid valve connection
Connection of expansion modules RM-LV8 / RM-LV16
Use shielded cable for all bus lines! The shielding must be connected unilaterally to the
protective earthing (PE).
Signal cables must not be laid parallel to power cables.
Tighten all cable glands in use so the cables are properly enclosed and water cannot
penetrate.
Cable glands that are not in use must be closed or replaced by blind plugs.

RM-216 C.10 Easy Line Documentation
RDN 10000029 6 13.05.2014
Other connections
Connecting differential pressure measurement cables
Use hoses with 4 mm inner and
6 mm outer diameters.
Connect the connection marked
with 3 lines (black screw cap) to
the crude gas side and the other
connection
(blue screw cap) to
the pure gas side of the filter.

RM-216 C.10 Easy Line Documentation
RDN 10000029 7 13.05.2014
5 “Step by step” settings
5.1 Function when shipped
The down time cleaning input E1, E2 (terminals 10, 11) is bridged at the factory. The cleaning starts
when the differential pressure ∆p for the filter has reached the value ∆p-MAX (factory setting: 1300 Pa).
The solenoid valves are triggered in sequence. The RM-216 C automatically detects how many valves
are connected. The cleaning process means that the differential pressure drops after a time. Cleaning
stops when the differential pressure reaches the value ∆p-MIN (factory setting: 700 Pa).
If another function is required or if additional functions are to be activated, the parameter setting of the
RM-216 C must be changed. See also section 5.2.
5.2 Setting parameters
To set or check the parameters, proceed as follows:
Use the parameter list in section 5.3 to search for the parameters you want to change or
check. On the RM-216 C, press buttons and
simultaneously, for at least 3 seconds. The
program then changes from operation mode to parameter selection mode. The parameter P00
“Δp-MIN” is displayed on the text display at its set value.
Press the
button to call up all following parameters P01 ... P20 in sequence. The parameters
already displayed can be accessed by repeatedly pressing the button.
To change the value of a displayed parameter, press the ENTER button for at least one
second. The program then changes from parameter selection mode to parameter setting
mode.
Press the
button to increase the parameter value displayed in increments. Press the
button to decrease the parameter value displayed.
Press the ENTER button for at least 3 seconds. The new parameter value is stored. The text
display will briefly display the message “Store
”. The program automatically returns to the
parameter selection mode. You can now call up other parameters and check or change their
values.
So that the program changes from parameter selection mode to operation mode, press buttons
and simultaneously for at least 3 seconds.
If the program is still in parameter setting mode, follow the instructions given under point .
The symbols shown on the right will be shown in the
lower left-
hand corner of the text display. They
indicate to the operator which mode the equipment is
currently in.
+ - Operation mode
+^- Parameter selection mode
+>- Parameter setting mode
If no buttons are pressed for 4 minutes, the RM-216 C automatically returns from parameter
selection mode or parameter setting mode to operation mode with the last values stored.

RM-216 C.10 Easy Line Documentation
RDN 10000029 8 13.05.2014

RM-216 C.10 Easy Line Documentation
RDN 10000029 9 13.05.2014
5.3 Parameter list
Parameter
.
no.
Text on the display Explanation Factory settings Setting range
P00
Delta-P Min
∆p-MIN
700 Pa
260 ... 4000 Pa
P01
Delta-P Max
∆p-MAX
1300 Pa
280 ... 4400 Pa
P02
Delta-P Alarm
∆p-Alarm
2300 Pa
300 ... 5000 Pa
P03
Pulse Time
Pulse time
60 ms
30 ... 300 ms
P04
Interval Time
Interval time
10 s
4 ... 500 s
P05
DTC.Interv.Time
Down time interval time
6 s
2 ...100 s
P06
Total Valve no.
Total no. of valves 1
0
0 ... 128
P07
DTC Down Time Cy
Down time cleaning cycles
6
0 ... 32
P08
Delta-P DTC Max
Parameter to activate down time
(DTC modes 2 and 3)
1000 Pa
280 ... 4000 Pa
P09
Delta P DTC Min
Parameter to activate down time
(DTC mode 3)
260 Pa
260 ... 2000 Pa
P10
Hours in operati
Operating hours
–
0 ... 250000 h
P11
Text Language
Language for the display text
D
D, GB, F, I, NL,
DK, FIN, PL
P12
DP-Display Range
Unit of displayed ∆p values
Pa
Pa, mbar,
Inch WC, mm
WG
P13
DTC Cleaning Mod
Down time cleaning mode (DTC-
mode)
2
1 ... 3
P14
Test Mode
0 = Test mode off
1 = Valve test
2 = Input test
3-7 = For manufacturer
purposes only
Off (0)
0 ... 7
P15
dP range
∆p range
0 ... 5000 Pa
0 ... 1000 Pa
to
0 … 5000 Pa
2
P16
Servic.Run Hours
Service operating hours
–
–
P17
Ser.Run Hours AL
Service operating hours alarm
0 h 3
0 ... 25000 h 3
P18
Ser.Run Hou.Code
Service operating hours code
0
–
P19
DP-Mode
Differential pressure mode
On
On / Off
P20
Setting Lock
Parameter setting lock
On
On / Off
1Number of all valves connected to the RM-216 C and to the expansion modules. The parameter is used by the equipment for
internal monitoring purposes and need only be set, if expansion modules are fitted. If the equipment detects that the total number
of valves set is different from the actual number of valves controlled, an alarm message is issued.
2The ∆p measuring range of the 4-20 mA signal output 52, 53 is configurable from 0 … 1000 Pa to 0 … 5000 Pa in 500 Pa
increments.
3If the parameter is set to the value 0 h, the alarm is switched off.
The parameters P03, P06, P07, P08, P09, P13 and P18 are protected by a setting lock at the
factory. If the values need to be changed, the parameter P20 “Setting lock" Must be set to the
value “Off”.
The parameters P10, P16 and P17 are only displayed, if the service operating hours code
(parameter P18) has been entered.

RM-216 C.10 Easy Line Documentation
RDN 10000029 10 13.05.2014
6 Operating modes
6.1 Test mode
In test mode, the most important functions in the control sequence are checked and shown on the text
display. To start test mode, call up parameter no. P14 “Test mode” (see section 5.2 for more information)
and select one of the following test modes:
Test mode 1 (Valve test)
Each connected valve is activated in sequence and shown in the text display.
Test mode 2 (Input test)
The signal statuses of the inputs are displayed on the text display.
Test modes 3-7
For manufacturer purposes only.
Test mode 0 (test mode off)
Test mode is switched off.
6.2 ∆p-Mode (differential pressure controlled cleaning)
There are two options for switching the differential pressure controlled cleaning on the RM-216 C on and
off:
By setting the parameter P19 “DP-Mode” to the value “On” or “Off”
By pressing the ENTER button for around 3 seconds
If differential pressure-controlled cleaning is switched off, the text “DP-Mode Off” is shown on
the display.
6.3 Down time cleaning modes
Down time cleaning is activated differently depending on the mode selected. Down time cleaning modes
1, 2 and 3 (abbreviated below as DTC modes 1, 2 and 3; Down-Time-Cleaning mode) are available:

RM-216 C.10 Easy Line Documentation
RDN 10000029 11 13.05.2014
DTC mode 1
The down time cleaning is started via the contact connected on input E1 and E2. If the fan is switched
off, the contact on E1, E2 must open.
DTC mode 2
The down time cleaning is only started via the contact connected to input E1 and E2 if the differential
pressure has exceeded the value ∆p DTC max during operation. If the fan is switched off, the contact on
E1, E2 must open.

RM-216 C.10 Easy Line Documentation
RDN 10000029 12 13.05.2014
DTC mode 3
The down time cleaning is started when the differential pressure falls below the value ∆p DTC min, after
the value ∆p DTC max has first been exceeded. The signal on input E1, E2 is ignored.
6.4 Cleaning via start/stop input (external ∆p switch)
If the cleaning is controlled via an external ∆p switch, the isolated contact on the ∆p switch must be
connected to the start/stop input D1, D2 (terminals 12, 13). The function of the RM-216 C is given in the
following table.
If the setting is “
∆
p mode OFF”
Contact (input D1, D2) Cleaning
open ON
closed OFF
If the setting is “
∆
p mode ON”
Contact (input D1, D2) Differential pressure
∆
pCleaning
open ∆p > ∆p MAX ON
closed ∆p > ∆p MAX OFF
open ∆p < ∆p MIN OFF
closed ∆p < ∆p MIN ON
During down-time cleaning, the start/stop input D1, D2 is inactive.

RM-216 C.10 Easy Line Documentation
RDN 10000029 13 13.05.2014
7 Troubleshooting
Error Possible causes Recommended action
The “ON” LED is not lit and input
E1, E2 is bridged.
-
No mains voltage
-
Check power feed
-
Device fuse is defective
-
Replace fuse
- EMERGENCY STOP
activated
- Check EMERGENCY STOP
No valve activity
- No control system release
- Bridge input E1, E2
- Wiring to valves interrupted - Check cables and electrical
connections
-
Magnet coil faulty
-
Replace coil
- Cycle interrupted - Check hose connections. Set
different values for ∆p control
No down time cleaning - Parameter P07 = 0
(down time cleaning cycles)
- Set parameter P07 “Down
time cleaning cycles” to a
different value
- There is no signal from the
valve controller (DTC modes
1-2)
- Activate signal to input I1, I2
Cleaning ineffective - Interval time too long - Set parameter P04 “Interval
time” to a lower value
- Pressure too low - Set pressure to 6 ... 8 bar
(min. 5 bar)
- Set parameter P04 “Interval
time” to a higher value
-
Valve faulty
-
Check / replace valves
- Pulse time too short - Set parameter P03 “Pulse
time” to a higher value
- Cycle often interrupted - Check differential pressure
monitor and hose
connections
Differential pressure display
error - Hose connection error - Drain hoses. Clean joints
between hose connections
and the filter casing with
compressed air (only towards
the filter, never towards the
sensor)
- Fit the hoses so there are no
kinks
- Check the hose connections
for water, kinks, etc.
“Alarm” LED on - The number of valves is set
incorrectly
- Set parameter P06 “Total no.
of valves” correctly
- ∆p-Alarm - Observe the service
instructions for the filter

RM-216 C.10 Easy Line Documentation
RDN 10000029 14 13.05.2014
8 Text messages on the display
Display Explanation
Reset status, text version and differential pressure.
The text message is displayed for approx. 1 second after the voltage is
switched on.
Reset RM200VXX
+ - XXXX Pa
Controller is not enabled through inputs I1 and I2.
Stand By
+ - XXXX Pa
Controller is enabled through inputs I1 and I2.
The Max ∆p switching point has not yet been reached.
Cleaning Off
+ - XXXX Pa
Controller is enabled through inputs I1 and I2 and the Max ∆p switching
point has been exceeded.
Cleaning On
+ - XXXX Pa
Controller is enabled through inputs I1 and I2 and the ∆p alarm switching
point has been exceeded.
Cleaning On
+ - XXXX Pa
alternating with
DP-Max Alarm
+ - XXXX Pa
Controller is enabled through inputs I1 and I2 and the Max ∆p switching
point has not yet been reached with inputs D1 and D2 bridged.
Extern Clean ON
+ - XXXX Pa
Controller is enabled through inputs I1 and I2 and the Max ∆p switching
point has been exceeded with inputs D1 and D2 bridged.
Extern Clean OFF
+ - XXXX Pa
∆p mode switched off
DP-Mode Off
+ - XXXX Pa
Down time cleaning active
DTC Cleaning ON
+ - 000 Pcs
The alarm switching point for the service hours counter has been
exceeded.
Call Service
+ - XXXX Pa
A connected I/O module RM-LV8 or RM-LV16 is out of order
or
the total number of valves (parameter P06) is set incorrectly.
RM-LVX Alarm
+ - XXXX Pa
Locked parameter in parameter selection mode
Lock
XXXX The differential pressure value displayed depends on the parameter setting.

RM-216 C.10 Easy Line Documentation
RDN 10000029 15 13.05.2014
9 Details on the equipment function
Differential pressure controlled cleaning
The cleaning is controlled by means of two ∆p switch points which can be set independently of one
another. It starts when the value ∆p-MAX is reached. All connected solenoid valves are controlled using
the preset values for the pulse time and the interval time, starting with the interval time. If the differential
pressure reaches the value ∆p-MIN, cleaning stops. To monitor the filter, a ∆p alarm switch point (∆p
alarm) can be set.
Cleaning starts at the first valve. If cleaning is interrupted using the ∆p controller or the start/stop input
D1, D2, the controller sequence is continued with the next cleaning process. The cleaning then starts at
the valve following the last valve activated.
If the control is reactivated following a mains voltage failure, a restart is carried out.
Input E1, E2 “Down time cleaning” (terminals 10, 11)
If the control is working in DTC mode 1 or DTC mode 2 (Down-Time-Cleaning mode. See also section
6.3), the control must be switched on and off via input E1, E2. The input should be operated in isolation.
Ideally, the auxiliary contact of the fan contactor should be connected here.
Closing the contact on input E1, E2 switches on the control unit.
In DTC mode 1, opening the contact on input E1, E2 executes the down time cleaning cycles and then
switches the device off. In DTC mode 2, the same function is only carried out if differential pressure
exceeded the value ∆p DTC max during the last operating period.
In DTC mode 3, the down-time cleaning cycles are activated if differential pressure exceeded the value
∆p DTC max during the last operating period and then fell below the value ∆p DTC min.
Relay output S1, S2 to control extractor elements (terminals 8, 9)
If automatic components for dust removal (extractor elements) are fitted, these need to be in operation
during cleaning and during down time cleaning. Connect the cut-out for controlling these drive units to the
isolated output S1, S2.
“Alarm” relay output A1, A2, A3 (terminals 5, 6, 7)
As soon as the supply voltage is present on the RM-216 C, relay contact A1, A2 closes (terminals 5, 6)
and contact A2, A3 opens (terminals 6, 7). In the following situations, relay contact A1, A2 opens and
contact A2, A3 closes:
Supply voltage failure
Failure of a voltage internal to the equipment
Fault in a connected I/O module
Total number of valves is set incorrectly (parameter P06)
The ∆p alarm switching point has been exceeded.

RM-216 C.10 Easy Line Documentation
RDN 10000029 16 13.05.2014
10 Glossary
Term Explanation
Bulkhead connector Connections for fitting the differential pressure measurement hoses.
Cleaning Cleaning the filter elements using compressed air pulses.
Compressed air pulse
cleaning
Cleaning of the filter elements using compressed air pulses.
Differential pressure Difference between the air pressures ∆pon the pure gas side (behind
the filter element) and the crude gas side (in front of the filter element) of
the filter.
Down time cleaning Cleaning the filter elements after the system is shut down for a set
duration or number of cycles.
Down time cleaning cycles The number of cleaning cycles performed in the down time cleaning.
Down time cleaning input Input on the RM-216 C for starting the down time cleaning.
Down time interval time Pause time during the down time cleaning.
DTC mode Down Time Cleaning mode
The way in which the down time cleaning is started.
Expansion module If the filter has more than 16 valves, expansion modules of type RM-LV8
(for 8 valves) or RM-LV16 (for 16 valves) are required. A maximum of 7
type RM-LV16 expansion modules can be connected to the main
RM-216 C equipment. With the outputs on the main equipment, this
makes a maximum of 128 valve outputs available.
Extractor element Device for extracting the filter casing from the dust deposited. E.g.
cellular wheel sluice, through conveyor worm.
Extractor element contactor Contactor which switches an extractor element drive unit on and off.
I/O module Input/output module (module for the input and output of control signals)
Operation mode Status of the RM-216 C in which the equipment is ready for operation.
Parameter selection mode Status of the RM-216 C in which the equipment operator can select a
parameter.
Parameter setting lock The parameters P03, P06, P07, P08, P09, P13 and P18 are protected
by a setting lock at the factory. If the values need to be changed, the
parameter P20 “Setting lock" Must be set to the value “Off”.
Parameter setting mode Status of the RM-216 C in which the equipment operator can set a
parameter.
Pause time
(also Interval time)
Time period between two consecutive control pulses from the valve
outputs when the cleaning is running.
Pulse time Duration of a control pulse on the valve outputs.
Service operating hours
alarm
Alarm issued when the operating hours set for the maintenance interval
has elapsed.
Service operating hours
code
Code which needs to be entered to change the set value for the service
operating hours.
Setting lock See Parameter setting lock

RM-216 C.10 Easy Line Documentation
RDN 10000029 17 13.05.2014
Term Explanation
Solenoid valve (also relay valve) electromagnetically operated valve for the pneumatic
triggering of the filter membrane valves. The membrane valves in turn
release the compressed air strokes for filter cleaning.
Start/stop input Input on the RM-216 C for starting and stopping the cleaning via an
external ∆p switch.
Total no. of valves Number of all valves connected to the RM-216 C and to the expansion
modules.
∆p alarm Differential pressure value at which an alarm is issued.
∆p-MAX Differential pressure value at which the cleaning is started.
∆p-MIN Differential pressure value at which the cleaning is stopped.
∆p mode Operating mode of the filter control in which the cleaning of the filter
elements depends on the differential pressure ∆p.
∆p remote display Display showing the differential pressure of the filter in a control room.
∆p switch Switch which is triggered by a differential pressure value set and which
activates the filter cleaning.

RM-216 C.10 Easy Line Documentation
RDN 10000029 18 13.05.2014
11 Technical specifications
Application Data
Supply voltages
230 V AC ±10%
110 V ... 120 V AC ±10%
26 V … 28 V DC*
Signal inputs
24 V DC, operate ensuring isolation
Signal output
Relay outputs, max. 2 A, 250 V
or 1 A, 30 V DC
Control outputs for valves
For valves with a rated voltage of 24 V DC,
can be expanded to 128 outputs,
Output power in pulse mode 42 Watt
Outputs for expansion mo-
dules
Supply voltage and pulse wires to the expansion modules
Signal output F1, F2
4-20 mA 0 ... x Pa**; resistance 500 Ω
∆p measuring range
configurable from 0 … 1000 Pa to 0 … 5000 Pa
in 500 Pa increments
Measurement sensor
piezoresistant, excessive pressure-safe up to 120 kPa
Fuses
230 V: T 0.4 A, 250 V, 5 x 20 mm
110 V: T 0.8 A, 250 V, 5 x 20 mm
Extra low voltage: Fusing via PTC resistor
Temperature range
-20°C to +60°C
Degree of protection
Casing IP-66 / NEMA 4
Dimensions
See chapter 3 “Assembly”
Weight
approx. 0.8 kg
Installation height
max. 3000 m above M.S.L.
*The unit can be operated with a supply voltage of 24 V DC, if no expansion modules are connected and if the electric cables
(minimum cross-section: 0.75 mm²) to the solenoid valves are shorter than 10 meters long.
** configurated ∆p measuring range
Disclaimer
The contents of this documentation has been verified for correctness and completeness. Nevertheless, errors can not be excluded
so that we cannot guarantee the correctness of this information. Subject to alterations at any time.
Table of contents
Popular Control Unit manuals by other brands

swissflex
swissflex uni_75RF operating instructions

VAT
VAT 192 Series Installation, operating, & maintenance instructions

BNC
BNC 106C instruction manual

Keba
Keba Kemro NX 252/A Project engineering manual

Ross
Ross CrossMirror CM26 Series operating instructions

Teletype
Teletype 33 General description and operation

IVAR
IVAR MULTIMIX-C instruction manual

Exodraft
Exodraft EBC10v2 Fitting, Installation and Operating Instructions

HWH
HWH 625 Series Operator's manual

Flowserve
Flowserve atomac AtoPro Series Technical manual

EOS
EOS Emotec D Operation manual and user guide

Realtek Semiconductor
Realtek Semiconductor RTL8822CE user manual