6| UVantage PLUS™ Installation Guide
DO’s
✓Disconnect all power supplies to the
HVAC unit and UVantage PLUS™ module
(hereafter referred to as “LED module”)
before beginning any servicing.
✓Install the LED module at one of the
preferred locations listed by the
manufacturer in this manual.
✓Use the power supply which was
provided with the LED module for safe
operation.
✓Use gloves and safety goggles while
installing the LED module.
✓Understand all the safety guidelines of
UVC radiation before handling the LED
module. Refer to the Safety Guidelines in
this manual.
✓While installing the UVC product, maintain
a minimum distance of 6 feet clearance
from filter or plastic materials which are
in direct line of sight. If not in direct line
of sight, a minimum distance of 3 feet is
recommended.
DON’Ts
✗Don’t attempt to look at the
UVC LED module while in
operation.
✗Don’t allow any UV light to
escape from ductwork in
any way. Make sure ducts
are sealed.
✗Don’t touch the UVC LEDs
directly with bare oil from
hands may damage the bulb.
✗Don’t operate the LED
module when the product
reaches the end of lifespan.
A RED LED will be displayed
on the control cover.
✗Don’t rotate the LED module
clockwise while installing.
✗Don’t connect power to the
module before completing
the entire installation.
installation