Regin RU-FO User manual

Regin product information Regin product information
RU-FO
Room unit with fan switch and forced
ventilation for use with RCP
• Awardeddesign
• Simpleinstallation
• Built-intemperaturesensor
• Cableforconnectionbetweentheroomunitandthe
 RCPcontrollerisavailableasaccessory
RU-FO is a room unit from the Regio series. It has a
switch for controlling a three-speed fan (fan coil). It
should be connected to one of the Regio Maxi controllers
RCP100F, RCP100FT, RCP200F or RCP200FT.
Regio
Regio is a wide series of controllers which handle heating
and cooling.
The controllers are divided into three different series,
Mini, Midi and Maxi. Mini are pre-programmed,
stand-alone controllers. The Midi controllers are pre-
programmed with communication. The Maxi group, to
which RU-FO belongs, consists of freely programmable
controllers with communication.
Applications
The Regio controllers are suitable in buildings where you
want optimal comfort and low energy consumption, for
example ofces, schools, shopping centres, airports, hotels
and hospitals etc.
Design
The room units have a modern design. The
design has been awarded the 2007 “iF product
design award”.
Sensor
The room unit has a built-in sensor.
Easy to install
The modular design with a separate bottom plate for
wiring makes the whole Regio series easy to install and
commission. The bottom plate can be put into place
before the electronics are installed. Mounting is directly
on the wall or on an electrical connection box.
Connection to RCP
The room unit is connected to the RCP-unit with an
RJ12-cable, max length 30 m. Regin has two cables as
accessories, RU-CBL3 (length 3 m) and RU-CBL10
(length 10 m).
product
design
award
2007
RU-FOisaroomunitintendedforusetogetherwith
RegioMaxicontrollers.
revision
09 2009
Regin product information
2
Regin product information
The Occupancy button
If you press the Occupancy button for less than 5 seconds
when the controller is in the preset operating mode, the
controller changes to operating mode Bypass. If you press
the button for less than 5 seconds when the controller
is in Bypass, it changes operating mode to the preset
operating mode.
When the Occupancy button is held depressed for more
than 5 seconds, the controller changes operating mode to
Unoccupied, regardless of the current operating mode. If
you press the Occupancy button for less than 5 seconds
in Unoccupied, the controller returns to Bypass.
Forced ventilation
Regio has a built-in function for forced ventilation.
A short press on the Occupancy button activates the
output that has been congured for forced ventilation, for
example for a damper.
Setpoint
In Occupied mode, the controller operates from a heating
setpoint (FS=22°C) or a cooling setpoint (FS=24°C) that
can be changed centrally or locally using the dipswitches
on RU-FO.
The setpoint can be adjusted up and down
(FS=+/-3°C) with the knob on the front of the room unit.
Switching between heating and cooling setpoints is done
automatically in the controller depending on the heating
and cooling requirement.
Indications
The room unit has an LED shaped like a thermometer on
the front. A red indication is shown when heating control
is functional and a blue indication when cooling control is
active. No LED indication shows that neither heating nor
cooling control is active.
Fan control
RU-FO has a fan switch with the following positions:
Auto Automatic control of the fan speed to maintain
desired room temperature.
0 Fan off.
I Manual position with low speed.
II Manual position with medium speed.
III Manual position with high speed.
In operating modes Off and Unoccupied, the fan is
stopped, regardless of the position of the fan switch.
Regin product information
Regin product information
3
Technical data
Supply voltage Fed from RCP
Ambient temperature 0...50°C
Storage temperature -20...+70°C
Ambient humidity Max 90% RH
Protection class IP20
Communication Same as RCP
Built-in temperature sensor NTC type, measuring range 0...50°C, accuracy +/-0.5°C at 15...30°C
Material, casing Polycarbonate, PC
Weight 110 g
Colour Cover: Polar white RAL9010
Bottom plate: Light gray
Cable for connection between RU and RCP Type RJ12, max length 30 m.
Cables that can be ordered from Regin RU-CBL3 (length 3 m)
RU-CBL10 (length 10 m)
This product conforms with the requirements of European EMC standards
CENELEC EN 61000-6-1 and EN 61000-6-3, and the requirements of
European LVD standard IEC 60 730-1. It carries the CE mark.
Inputsandoutputs
In RCP
Terminal blocks in RCP So-called lift type for cable cross-section 2.1 mm2
SetpointsettingsviaRegioTool©
Basic heating setpoint 5...40°C
Basic cooling setpoint 5...50°C
Setpoint displacement +/-0...10°C (FS = +/-3°C)
Basicheatingsetpoint,settingwithdipswitches
The ON-position is marked on the dipswitch. The cooling setpoint is 2°C higher.
Basicsetpoint,heating(°C) SW1 SW2
20 OFF OFF
22 (FI) OFF ON
24 ON OFF
26 ON ON
Otherdipswitches
ON OFF Comment
SW3 Stand-by Occupied (FI) Preset operating mode
SW4 --Not used
Regin product information
Head Office Sweden
Phone: +46 31 720 02 00
Web: www.regin.se
Mail: [email protected]
Sales Offices
France: +33 14 171 46 46
Hong Kong: +852 24 07 02 81
Singapore: +65 67 47 82 33
Germany: +49 30 77 99 40
Wiring
Terminal Designation Operation
10-33 No function
40 +5 V +5 V supply voltage from RCP
41 N (0 V) 0 V supply voltage from RCP
42 A RU-Bus A
43 B RU-Bus B
Dimensions
Product documentation
Document Type
Regio Maxi Manual Manual for the controllers from the Regio Maxi series
Installation instruction Regio RU-FO Installation instruction for RU-FO
All product documentation is available on www.regin.se.
95
31
60 68
mm

Popular Switch manuals by other brands

Eaton TRIPP LITE U360-004-IND owner's manual

Eaton

Eaton TRIPP LITE U360-004-IND owner's manual

SICK STR1 operating instructions

SICK

SICK STR1 operating instructions

Hall Technologies EMCEE200 user manual

Hall Technologies

Hall Technologies EMCEE200 user manual

Siemens SITRANS LVL200S operating instructions

Siemens

Siemens SITRANS LVL200S operating instructions

Exsys EX-1187HMVS-2 manual

Exsys

Exsys EX-1187HMVS-2 manual

NETGEAR ProSafe GSM7324 Reference manual

NETGEAR

NETGEAR ProSafe GSM7324 Reference manual

Sea Wit 21UA user guide

Sea Wit

Sea Wit 21UA user guide

ATEN CS1942DP user manual

ATEN

ATEN CS1942DP user manual

Allied Telesis AT-RG624 user manual

Allied Telesis

Allied Telesis AT-RG624 user manual

Optical Systems Design OSD2251BP Series Operator's manual

Optical Systems Design

Optical Systems Design OSD2251BP Series Operator's manual

Rose electronics UltraView DVI Installation and operation manual

Rose electronics

Rose electronics UltraView DVI Installation and operation manual

Varilight V-PLUS IR instructions

Varilight

Varilight V-PLUS IR instructions

AVCOMM 628GX4 Quick installation guide

AVCOMM

AVCOMM 628GX4 Quick installation guide

ZIV SWT user guide

ZIV

ZIV SWT user guide

Motorola WS2000 - Wireless Switch - Network Management... System reference guide

Motorola

Motorola WS2000 - Wireless Switch - Network Management... System reference guide

RTcom DS-21R user manual

RTcom

RTcom DS-21R user manual

Comprehensive CVG-21RCA user manual

Comprehensive

Comprehensive CVG-21RCA user manual

Keysight Technologies 34902A Service guide

Keysight Technologies

Keysight Technologies 34902A Service guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.