
PAGE 9
Reimers Electra Steam, Inc. 05/23/2022 RB‐30 Manual REV 7
working pressure is reached. The working pressure should
have been factory set to your specification. However, if you
wish to change the working pressure setting, proceed as
follows.
All pressure controls are factory preset and require no
adjustment. However, if a change of the operating steam
pressure is required, then proceed as
follows:
• Disconnect all power supplies from the boiler.
• Close the steam outlet valve
• Remove the cover from the pressure control enclosure.
• Turn the black knob of the operating pressure switch
clockwise to increase the pressure and counterclockwise
to decrease the pressure.
• Connect all power supplies to the boiler, open the
steam outlet valve, and install the pressure control
enclosure cover.
h.)
To shut off the boiler, turn the POWER switch on the boiler
control OFF
See Boiler Control Manual for detailed instructions.
The control provides four basic functions and two optional
functions. The following overview describes the functions.
Low water cutoff
Boiler high pressure cutoff
High water level feed shutoff
Automatic boiler refill
Automatic boiler blowoff (Optional)
Remote controlled boiler ON/OFF and boiler status
(Optional)
The low water cutoff function of the boiler control de
energizes the heating elements when the water level in the
boiler pressure vessel falls below the minimum acceptable
operating level. The control senses the water level in the
boiler pressure vessel through a probe, E3. When the tip of
the probe is in contact with water in the boiler, the boiler
operates normally. When the water level in the boiler falls
below the tip of the probe the control senses that water
level is low. The control will not deenergize the heating
elements when the probe loses contact with the boiler
water for short periods of time. But, when the probe loses
contact with the probe for a set time, the control de
energizes the heating elements and turns on the “LOW
WATER” boiler alarm light. Boiler operation can only be
resumed after determining why water level is low, restoring
normal water level in the boiler and pressing the “LOW
WATER” reset button [R]. After presseing the “LOW
WATER” reset button the alarm light “LOW WATER” turns
off, the lockout is reset and the heating elements are
energized.
The Low Water CutOff function short cycling timer can be
adjusted. See the Boiler Control Manual (Doc. #9101)
If the operating pressure control fails, the steam pressure in
the boiler can reach the value set on the high limit pressure
control. In that case, the high limit pressure control de
energizes the heating elements and locks them out. The
boiler alarm light “HIGH PRESSURE” comes on. After the
pressure control is replaced the HIGH PRESSURE alarm
light turns off.
When the high water level cutoff probe (E2) comes in
contact with boiler water, the boiler control turns off the
automatic refilling device, feed pump and/or solonoid valve.
At the same time the boiler controller deenergizes the
heating elements, closes the steam outletline through the
solenoid valve (SOL2) and displays a flashing “2” on the
LED display. As soon as the probe E2 looses contact with
the boiler water the boiler controller resumes normal boiler
operation automatically. (The boiler controller can be set to
require that the “EKey be pressed to resume boiler
operation. See the Boiler Control Manual for instructions.)
When the POWER switch is turned on and the water level
probe (E1) is in contact with the boiler water, the boiler
control keeps the boiler water feed pump and/or solenoid
valve deenergized. When the water level probe (E1) loses
contact with the boiler water, the boiler control energizes
the boiler feed pump and/or the solenoid valve after a set
ON delay time. When the water level probe makes contact
with the boiler water, the boiler controller deenergizes the
boiler water feed pump and/or solenoid valve after a set re
fill OFF delay time.
The ON and OFF delay time can be adjusted. See the
boiler control manual for instructions.
If the feedwater pump and/or solenoid valve remains on for
longer than the ON delay time the boiler control de
energizes the feed water pump and/or solenoid valve and
displays a flashing “0” on the control LED display. The “E”
key must be pressed to start a new refilling attempt.
See Boiler Control Manual for instructions.
See Boiler Control Manual for instrucitons.
The following are definitions for all boiler monitor
indications. See the control manual for details including
adjusting all parameters.
Flashing “0”: Boiler feed pump and/or solenoid remained
energized longer than the set time. Boiler feed pump and/
or solenoid are deenergized. Press “E” key to reset alarm
and start a new refilling cycle.
Flashing “1”: Following a blowdown cycle, the automatic
refill device did not stay on for the set time. Press”E” key to
reset the alarm.
Flashing “2”: The high water level probe (E2) has come in
to contact with boiler water. The feed pump and or solenoid
is deenergized and the heating elements are de
energized. As soon as the probe (E2) loses contact with
WARNING
Stand clear of scalding water or steam. Disconnect the
boiler from all power supplies.
High Pressure Safety
Limit Pressure Switch:
DO NOT ADJUST!
Operating Pressure
Switch
Pressure Triggered Boiler
Blowoff Pressure Switch
when OPT1016 is
installed
2.2 Control Functions
2.2.1 Low Water Cutoff Function
2.2.2 High Pressure Cutoff Function
2.2.3 High Water Level Feed Shutoff
2.2.4 Automatic Boiler Refill
2.2.5 Automatic Boiler Blowoff (Optional)
2.2.6 Remote Controlled Boiler ON/OFF and Boiler
Status (Optional)
2.3 Boiler Monitor Definitions
Figure 09