PAGE9
ReimersElectraSteam,Inc. 01/10/2022 HLR120‐180Manual‐English REV1
a.Withallpowerdisconnected,checkthecontrolpanelfor
loose wires caused by vibration in shipping. Review
installationinstructionstobesureboiler
isproperlywiredandinstalled.
b. Be sure that the boiler drain valve is
closed
c.Fillthesystemwithwater
d. Ensure that the selector switch is in
OFFposition(middleposition)
e. Turn on the control voltage power
supply
f. TurntheredPOWERswitchtotheON
position
g. Start the circulating pump, or pumps by throwing the
selector switch of the boiler controller into the PUMP
position.Withpumprunning,bleedairfromsystemand
checkentiresystemforleaks.
h. This hot water boiler is equipped in its standard
configurationwithonetemperaturesensor,placedinside
the boiler pressure vessel near the water outlet nozzle.
Itsensesthewatertemperatureasitexitstheboiler.For
space heating applicationsthat require outdoor reset, a
second sensor can be easily connected to the boiler
controllerinthefield.
NOTE: For all boilers equipped with the Honeywell
T775P2003 controller (standard configuration), please
continue reading this paragraph. For all boilers equipped
with the BACnetTM enabled controller, model OPTHLR
BMS, please refer to the separate instruction manual that
comeswiththeboiler.
TheHoneywellcontrollerT775P2003wassetatthefactory
with its parameters as shown below and to the operating
watertemperatureasordered:
1.1EnteringSetupMode:PressandholdtheMENUbutton
for5secondstodisplaytheSetupmenu
1.2.SettinguptheSensors:
1.2.1.#ofSensors=1
1.2.2.SensorA
1.2.2.1.UNITS=DEGF
1.2.2.2.CALIBRATE=0.0°F
1.2.2.3.LABEL=BOILERA
>EXIT
2.3. SENSOR B = Not set, unless outdoor reset sensor
connectedtocontroller
1.2.4.SENSORC:Notused
>EXIT
1.3.SettinguptheOutputs
1.3.1.NumberofSTAGES=4
1.3.2.SCHEDULE=NO
1.3.3.OPTIONS
1.3.3.1. RESET = NO, unless outdoor reset sensor is
connectedtocontroller
1.3.3.2.INTEGRAL=0sec.
1.3.3.3.DERIVATIVE=0sec.
1.3.3.4.ONDELAY=0sec.
1.3.3.5.OFFDELAY=0sec.
1.3.3.6.WWSD=NO
1.3.3.8.LEADLAG=FOFO
1.3.3.9.DIOPTIONS=DISABLE
1.3.3.10.SHOWRT=NO
>EXIT
1.3.4.SettinguptheStages=Notset
>EXIT
1.4.SetupAlarms=Notset
>EXIT
PROGRAMMINGOUTPUTSTAGESWITHNORESET
3.1.EnteringProgramMode:PresstheMENUbutton,then
select PROGRAM and press the > button to view the
Programmenu.
3.1.1. SETPOINT = Set value to desired heating loop
temperature
3.1.2. THROTTLING RANGE = recommended range 15 –
25°F
3.1.3.SENSOR=Notset
3.1.4.HEAT/COOL=HEAT
>EXIT
>EXIT
To set the boiler controller for reset mode, please refer to
the Honeywell T775P2003 boiler controller manual that is
attachedtothismanual.
i. TurnthethreephasepowersupplyON
j. TurntheselectorswitchintotheHEATINGposition
a.Assoonastheselectorswitchisinthe
HEATINGpositionandtheRoom/Process
thermostatcallsforheating:
BothlightsremainONaslong
as the Room/Process
thermostatcallsforheating.
b. Depending on the difference between
the programmed temperature set point
and the actual temperature in the boiler
pressure vessel, the boiler controller will
start energizing heating stages. The
energizedheatingstages areindicatedin
thecontrollerdisplayasblackdots.
c. The actual temperature of the boiler is shown in the
middle portion of the display.Tochange the
set point, follow the instructions above
(Honeywell Controller T775P2003 Setting
OperatingParameters)
d. Various status messages may be shown
in the lower portion of the boiler controller
display. As long as the thermostat calls for
heating,DI=OFF,whenthethermostatdoes
notcallforheating,DI=ON.
e. As soon as the temperature in the
pressure vessel approaches the
programmed set point temperature, the
boilercontrollerwillbegintostepoutheating
stages.
If the actual temperature in the pressure
vessel (temperature indicated on the
temperature gauge) is higher than the
programmedtemperaturesetpoint,thenthe
throttling range must be increased. If the
actual temperature in the pressure vessels
swings too high over the programmed set point, the high
temperaturesafetylimitcontrol(s)maytrip.
2.Operation
2.1BoilerStartup
HoneywellControllerT775P2003Setup:
Selector
Switch
FIGURE2
HoneywellControllerT775P2003SettingOperating
Parameters:
2.2BoilerOperation,SequenceofEvents
HEATING
lightON
FIGURE5
PUMPlight
ON
FIGURE6