Relpol MT-TUA-17S-11-9240 User manual

Time Relay MT-TUA-17S-11-9240
Instruction Manual
Time Functions
E - On Delay: After supply voltage U has been switched on, the set time T is being measured. After the T time has
lapsed, the R operating relay shall start operating and remains in operating position until the supply voltage U is
switched off.
Wu - Single shot leading edge voltage controlled. After the supply voltage U has been switched on, the operating
relay R starts immediately and the set time T is being measured. After the set time T has lapsed, the operating relay
R returns to the initial position.
Bp - Flasher pause first: After the supply voltage U has been switched on, the set time T is being measured. After
the time has lapsed, the operating relay R starts operating and the T time is being measured again. After the time
has lapsed, the operating relay R returns to the initial state, and another cycle of the relay operation commences.
The relay operates until the supply voltage is switched off.
Bi - Flasher pulse first: After the supply voltage U has been switched on, the set time T is measured and the
operation relay R is switched on. After the time has lapsed, the operating relay R starts operating and the time T
is being measured again. After the time has lapsed, the operating relay R returns to the initial state, and another
cycle of the relay operation commences. The relay operates until the supply voltage is switched off.
T - generating the 0.5s pulse after the T time.
R- OFF Delay: The supply voltage U must be constantly applied to the time relay. After the control contact S has
been closed, the operating relay R starts operation immediately. After the control contact S has been opened, the set
time T is being measured. After the T time has lapsed, the operating relay R returns to the initial position. When the
control contact S is closed again, even before the T time has lapsed, the time measured thus far is reset, and when
S is opened, the set time T is being measured again.
Ws - Single shot leading edge with control contact: The supply voltage U must be constantly applied to the
time relay . After the control contact S has been closed, the operating relay R starts immediately and the set time
T is being measured. After the set time T has lapsed, the operating relay R returns to the initial position. In course
of measuring the T time, the control contact S may be closed and opened repeatedly with no impact upon the
operating relay R. Only after the T time has lapsed, closing S will make the operating relay R operate and the T
time will be measured.
Wa - Single shot trailing edge with control contact: The supply voltage U must be constantly applied to the time
relay. Closing of the control contact S does not trigger the measurement of the time delay or operation of the
operating relay R. Only opening of the control contact S causes the immediate operation of the operating relay R,
and the set time T is being measured. After the T time has lapsed, the operating relay R returns to the initial position.
In course of measuring the T time, the control contact S may be closed and opened repeatedly with no impact upon
the output relay. Only after the T time has lapsed, closing and opening of S will make the operating relay R operate
and the T time will be measured.
Esa - ON and OFF delay with control contact: The supply voltage U must be constantly applied to the time relay.
After the control contact S has been closed, the set time T is being measured and when it lapses the operating relay
R is switched on. On opening of the control contact S the set time T is measured again, and after the time has
lapsed, the operating relay R is switched off. In case the time of closing the control contact S is shorter than the set
time delay T, the operating relay R shall start operation after the set delay has lapsed, and it will continue to operate
for the T time. In course of the operation of the R relay, closing of the control contact S does not affect the function.
B - Bistable relay leading edge with control contact.
Each closing of the control contact S changes the operating relay status to the opposite one (a feature of a bi-stable
relay).
Permanent switching ON and OFF. The functions ON and OFF are selected with the TI E potentiometer. In the
ON function the normally open contacts are closed all the time whereas in the OFF function they are open. The
position of the FUNC potentiometer is of no significance when the ON / OFF function is selected.
E
Wu
Bp
Bi
T
R
Ws
Wa
Esa
B
Programme
settings should be
set efore
switching the unit
on!
Relpol_Multi_Time _Inst uctions_Final:Layout 1 7/1/11 09:43 Page 1
Time Relay MT-TUA-17S-11-9240
Instruction Manual
Caution, Hazards
Time relays must be installed by qualified electricians. All and
any electrical connections of the time relay shall comply with
the appropriate safety standards.
Disposal of Electrical Waste
All electrical waste should be
disposed of in compliance with
current WEEE regulations.
Description of Relay: ultifunction time relay MT-TUA-17S-11-9240
10 time functions
8 time ranges
Cadnium - free contacts
AC/DC input voltages
odule width: 17.5mm
Direct mounting on 35mm din rail in accordance with PN-EN 60715 (wiring: 1 x 2.5mm2, 2 x 1.5mm2)
Application: in low voltage systems
Compliance with standard PN-EN 61812-1
Recognition, certification, directives:
Connection Diagram:
A2 N (-)
S
L (+)
Supply voltage:
12.....240V AC/DC
AC: 50/60Hz
A1
Relay Features: Supply terminals (A1, A2)
and control contact
terminal (S)
Green LED U ON
Indication of supply voltage U
Yellow LED R
ON/OFF
Output relay status
Time adjusting dial
Range and function
ON/OFF adjusting dial
Function adjusting dial
Output terminals
(15, 16, 18)
Output Circuit - Contact Data
Number and type of contacts 1P / 1CO (Changeover)
Contact material AgNi
ax. switching voltage 400V AC / 300V DC
Rated Load AC1: 16A / 250V AC
in. breaking capacity 0.3W 5V, 5mA
Input Control Circuit
Rated Voltage 12...240V AC/DC AC 50/60 Hz terminals (+) A1 - (-) A2
Overvoltage category II
Insulation pollution degree 1
Dielectric strength Input - output: 2 500V AC 
Contact clearance: 1 000 V AC 
General Data
Dimensions (L x W x H) 90 x 17.5 x 63.5mm (weight: 64g)
Storage / operating temperature - 40 to + 70oC / - 20 to + 45oC
Cover protection category IP20 PN-EN 60529
Time Module Data
Functions E, Wu, Bp, Bi, T, R, Ws, Wa, Esa, B, (ON/OFF )
Time ranges 1s ; 10s; 1 min.; 1 h; 10h; 1 d; 10 d
Setting accuracy + 5% 
Repeatability + 5% 
Technical Data:
Type of insulation: Basic
Type of clearance: micro-disconnection
Length with 35mm rail taps: 98.8mm
Permanent switching ON and OFF
For first range set point (1s) setting accuracy and repeatability are smaller than
the given ones in technical parameters (significant influence of the operational
relay operating time, processor start time, and at the moment of supply switching
as referred to the AC supply course).
For the minimum to maximum direction of the time adjust dial.
Relpol_Multi_Time _Inst uctions_Final:Layout 1 7/1/11 09:43 Page 2

Popular Other manuals by other brands

SoftBank 104SH user guide

SoftBank

SoftBank 104SH user guide

Eaton IZM40 Operation and Maintenance Instructional Manual

Eaton

Eaton IZM40 Operation and Maintenance Instructional Manual

tronical TronicalTune PLUS manual

tronical

tronical TronicalTune PLUS manual

Globisens Labdisc Gensci quick start guide

Globisens

Globisens Labdisc Gensci quick start guide

UNITED OFFICE UAV 220 A2 operating instructions

UNITED OFFICE

UNITED OFFICE UAV 220 A2 operating instructions

GEONAUTE MP3 PLAYER 1GB manual

GEONAUTE

GEONAUTE MP3 PLAYER 1GB manual

Osprey Ozone 28/80L owner's manual

Osprey

Osprey Ozone 28/80L owner's manual

DAVIS Terminal Box install guide

DAVIS

DAVIS Terminal Box install guide

Samsung SGH-X530 Service manual

Samsung

Samsung SGH-X530 Service manual

Perfect Aire Damp2Dry 2PACD200 user manual

Perfect Aire

Perfect Aire Damp2Dry 2PACD200 user manual

SealMaster SK300 owner's manual

SealMaster

SealMaster SK300 owner's manual

T&D RTR-52Pt user manual

T&D

T&D RTR-52Pt user manual

Kuryakyn 8955 installation instructions

Kuryakyn

Kuryakyn 8955 installation instructions

ATS Allison Transmission Pan kit installation manual

ATS

ATS Allison Transmission Pan kit installation manual

T&D RTR-53A user manual

T&D

T&D RTR-53A user manual

Bulldog Security 200Q Fitting instructions

Bulldog Security

Bulldog Security 200Q Fitting instructions

Martin Audio AS118 - SCHEMATICS manual

Martin Audio

Martin Audio AS118 - SCHEMATICS manual

Skyrc e4 instruction manual

Skyrc

Skyrc e4 instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.