Remberg ENERGY-0-RS User manual

ENERGY-0-RS
Energy Meter
User manual
TRMS AC/DC
i RMS
800Vac
-/+ 1000Vdc
Watt
Var
Vpk
Frecuency
Energy
bidireccional
COS phi
V rms
50A ac/dc
RS485

User Manual - 3
Index
1 Safety guide lines ..........................................................................................................................................4
2 Model identication.....................................................................................................................................4
3 Technical data................................................................................................................................................4
3.1 Main features........................................................................................................................................4
3.2 Hardware and software features ....................................................................................................4
4 Dimensions and Installation......................................................................................................................6
5 Electrical wirings ...........................................................................................................................................6
6 Mounting.........................................................................................................................................................7
7 Conguration.................................................................................................................................................7
7.1 Remarks .................................................................................................................................................7
8 EnergyMeter-Programmer .........................................................................................................................8
9 Modbus Register Map .................................................................................................................................8

4 - User manual
Introduction
Thank you for choosing is Energy Meter.
The ENERGY-0- is a
Single-phase Power Meter
able to measure the TRMS AC/DC
Current and Voltage. On the RS485 Modbus following measuring units are available:
Irms, Vrms, Watt, Var, Va, Vpk, Ipk, Frequency, Cosφ, Energy bidirectional and THD.
The device is fully congurable by RS485, DIN rail mounting, 4kV galvanic isolation for
Voltage input.
1 Safety guide lines
Read carefully the safety guidelines and programming instructions contained in
this manual before using/connecting the device. Disconnect power supply before
proceeding to hardware settings or electrical wirings. Only qualied personnel should
be allowed to use the device and/or service it and in accordance to technical data and
environmental conditions listed in this manual. Do not dispose electric tools together
with household waste material. In observance European Directive 2002/96/EC on
waste electrical and electronic equipment and its implementation in accordance with
national law, electric tools that have reached the end of their life must be collected
separately and returned to an environmentally compatible recycling facility.
2 Model identication
Power supply 9..30 V DC
ENERGY-0-RS P
ower / Energy Meter Single Phase AC/DC TRMS - RS485
Modbus
3 Technical data
3.1 Main features
• TRMSMeasure,THDavailable
• 0,5%Accuracy
• RS485Modbusintegrated
• BidirectionalEnergymetering
• DINrailmountinginbothside
• OEM’sdesign,lowcost
• FullycongurablebyfreeinterfacesoftwareEnergyMeter-Programmer
• Bootloaderforupdatingrmware
3.2 Hardware and software features
Power supply
9..30 V DC, Protection against polarity reversal and
overtemperature
Absorption
1,3 W
Protection index
IP20
Accuracy
Voltage, Current, Active Power, Reactive Power, Apparent

User Manual - 5
power:<0,5%F. S.
Frequency: +/- 0,1 Hz
Energy:+/-1%ofreading
Vpeak,Ipeak:+/-5%f.s.
Measurement
Irms, Vrms, Watt, Var, Va, Vpk, Ipk, Frequency, Cosφ,
Energy bidirectional, THD
Temperature coecient
< 200 ppm/°C
Working temperature
-15..+65°C
Storage temperature
-40°C.. +85°C
Type of measure
TRMS or DC
Range
Current: Up to 50 A AC/DC
Voltage: up to 800 V AC or 1000V DC
RS485 customize setting with free interface software
EnergyMeter-Programmer
Crest factor
1,8 (on current measurement)
Output
RS485 Modbus RTU
Working frequency
DC or 1..400 Hz
Sampling rate
11k Samples per Second
Input impedence
1Mohm+/-1%
Isolation
3 kV on bare wire for Current measure,
4 kV for Voltage measure (reinforced insulation to power
supply and serial output)
Hysteresis
0,15%f.s.
Humidity
10..90%notcondensing
Altitude
Up to 2000 m s.l.m.
Weight
80 g.
Filling
Epoxy Resins
Box material
PBT,grey
Mounting
Screw predisposition for vertical/horizontal mounting,
DIN rail clips (included) for vertical/horizontal mounting.
Terminals
Removable terminals 3,5mm, n°1 4 poles, n°2 2 poles
Dip-switch
2 poles
Led
N°1 yellow, Power on xed, data communication blinking
Standards CE
EN61000-6-4/2006 + A1 2011; EN64000-6-2/2005;
EN61010-1/2010
Overvoltage category
Cat III up to 600V; Cat II up to 1000V
Dimensions
46,1x 63x 26,4 mm (terminal excluded)

6 - User manual
4 Dimensions and Installation
ON
Addr
Cat III: 600 V
Cat II: 1000 V 9..30 V DC
P1
TRMS AC/DC
1000 V
dc
ENERGY-0-RS
15,0 mm
46,2 mm
63,0 mm
800 V
ac
50 V
ac/dc
1-ph energy meter
Baud
V-
V-
V+
V+
B-
A+
GND
Pow
12
5 Electrical wirings
Although this controller was designed to resist electromagnetic interferences
in industrial environments, please observe following safety guidelines:
• Separatethecontrollinefromthepowerwires.
• Avoidproximityofremotecontrolswitches,electromagneticcontactors,powerful
engines and in all instances use specic lters.
• Avoidproximityofpowergroups,especiallythosewithphasecontrol.
POW
+ 9..30
V DC
± 1000 V DC
800 V AC
Cat. II: 1000V
Cat. III: 600V LOAD
(COATING SIDE ) (P1 SIDE )
+
Vg
GND
-
A+
B-
V+
V-
485
USB

User Manual - 7
6 Mounting
The Power Meter ENERGY-RS can be mounted in any position (see photo below),
horizontal or vertical mounting, horizontal or vertical through the two hooks for DIN
rail included in the box.
7 Conguration
Using a seriallinkRS485-USByou canconnecttheenergy-rs withtheinterface
program EnergyMeter-Programmer. This software allows to set the Modbus address,
baudrate, delay, the TV and TA ratio, to modify a lter in order to have fastest responce
time instead of a more stable measurement (lter range from 1-speed to 5-accuracy).
You can download the EnergyMeter-Programmer free of charge from Download Area
on our website .
A second way to program the device is by using the Modbus Register Map directly.
7.1 Remarks
• Modbusconnections:A+andB-asperModbusRTUstandards;
• ModbusRegisterreference:withreferencetothelogicaladdress,forex.40010,
corresponds to physical address n°9 as per Modbus RTU standard;
• Modbusfunctionssupported:3(Readmultipleregisters,max100),6(Writesingle),
16 (Write multiple).
• Anychangemadebydip-switchrequirestoswitchothepowersupply
Energy storage data on ash memory: 4,5 years minimum, 45 years typical
Minimum Current measurement oset: 100mA
Minimum Power measurement oset: 1 W
Measurement refresh: every 50 cycles or 1 second (the faster), programmable by
EnergyMeter-Programmer
If you want to set the device by EnergyMeter-Programmer set the dips to 0. If you want
to set by RS485 directly, set the rst dip to 1 (up) then use the second dip for baudrate
setting ( 0 for 9600 or 1 for 38400). After the settings, please save the conguration
bytheCOMMANDregister,thenswitchothepowersupply:Beforeswitchingonthe
power supply set the dips to 0.

8 - User manual
Dip-switch settings 12
All setting from EEPROM 00
SetAddress1-Baud9600 10
SetAddress1-Baud38400 11
8 EnergyMeter-Programmer
The free interface program EnergyMeter-Programmer is the fastest way to congure
the device. The changes made to the program act on the register of the device.
To restore the default conguration, just press the button FACTORY DEFAULT.
Type of measure
Allows the selection of the measure RMS or DC only to
dene the sign (positive or negative) of reading
Save on energy ash
It is possible to activate the saving of the counters
directly on the device’s ash memory
Report of transformation
In case you would use the TA and / or TV, you can dene
the transformation ratio for the current input and
voltage input, the default ratio is 1:1
Filter
Allows to insert a lter on reading in order to get more
speed in responding (value 1) or a more stable and
accuratemeasurement ( value5).Bydefaultthevalue
is set to 2. You can choose between intermediate values
already set or manually enter the desired lter by
choosing the CUSTOM option from the menu.
In this case, you can set the following parameters:
ltering in DC, ltering in AC (default value 5 ), Frequency
measurement on Current channel
CAUTION
: Magnetic elds of high intensity can vary the values measured by the
transformer. Avoid installation near permanent magnets, electromagnets or iron
masses that induce strong changes in the magnetic eld. If any irregularity, to reorient
or move the transformer in the area most appropriate.
9 Modbus Register Map
See paragraph 9, page 15.

9 Modbus Register Map
Register
Name Comment Register Type R/W Default
Value Range Modbus
Address
Machine ID Machine ID Unsigned short R7 40001
FW version Firmware version Unsigned short R0 40002
Address Modbus address Unsigned short R/W 140003
Delay Machine answer delay (in characters) Unsigned short R/W 10..1000 40004
Baudrate
0= 1200, 1= 2400, 2= 4800, 3=
9600, 4= 19200, 5= 38400, 6=
57600, 7= 115200
Unsigned short R/W 10..7 40005
Parity 0= NO, 1= ODD, 2= EVEN Unsigned short R/W 00..2 40006
DC Filter Number of tenths of second (1/10) for
all RMS calculation in DC Unsigned short R/W 10 1..65535 40007
Flag
Measurement
bit 0 :[ 0= TRMS value (without sign);
1 = DC_measurement (with sign)];
bit 1:[ 0= Energy stori ng disable;
1= Energy storing enable];
bit 2 :[ 0= Frequency detect on
Voltage channel; 1= Frequency
detect on Current channel].
Unsigned short R/W 0x10 40008
TV_Ratio Voltage transformer ratio Float
(LSW rst) R/W 1.0 40009
40010
TA_Ratio Current transformer ratio Float
(LSW rst) R/W 1.0 40011
40012
# of ZX for VI
measurement
Number of ZX for_AC Meas Number
of line cycle Zero Crossings for AC
measurement RMS.
Unsigned short R/W 50 1..65535 40014
STATUS
bit 0: ash settings error;
bit1: ash calibration error;
bit 2: Voltage Over Range;
bit 3: Voltage Under Range;
bit [4:5] Reserved;
bit 6: Zero crossing detecting;
bit [7:9] Reserved;
bit 10: Energy storing error;
bit 11: Energy initialization error;
bit 12: Reserved;
bit 13: Current Over Range;
bit 14: Current Under Range;
bit 15: Reserved.
Unsigned short R0 40072
V RMS Voltage RMS Measurement (V) Float
(LSW rst) R40073
40074
I RMS Current RMS Measurement (mA) Float
(LSW rst) R40075
40076

16 - Manuale d’uso
Register
Name Comment Register Type R/W Default
Value Range Modbus
Address
PActive Power Measurement (W) Float
(LSW rst) R40077
40078
QReactive Power Measurement (VAR) Float
(LSW rst) R40079
40080
SApparent Power Measurement (VA) Float
(LSW rst) R40081
40082
Cosφ Cosφ Measurement Float
(LSW rst) R40083
40084
Frequency Frequency Measurement (Hz) Float
(LSW rst) R40085
40086
THD THD Measurement Float
(LSW rst) R40087
40088
Energy Totale Energy Measurement (KWh) Float
(LSW rst) R40089
40090
Energy positive Only positive Energy Measurement
(KWh)
Float
(LSW rst) R40091
40092
Energy
negative
Only negative Energy Measurement
(KWh)
Float
(LSW rst) R40093
40094
V peak Instantaneous Voltage Peak (V) Float
(LSW rst) R/W 40095
40096
I peak Instantaneous Current Peak (mA) Float
(LSW rst) R/W 40097
40098
V MAX Max RMS Voltage (V) Float
(LSW rst) R/W 40099
40100
V min Min RMS Voltage (V) Float
(LSW rst) R/W 40101
40102
I MAX Max RMS Current (mA) Float
(LSW rst) R/W 40103
40104
I min Min RMS Current (mA) Float
(LSW rst) R/W 40105
40106
P MAX Max RMS Power (W) Float
(LSW rst) R/W 40107
40108
P min Min RMS Power (W) Float
(LSW rst) R/W 40109
40110
Q MAX Max Reactive Power (VAR) Float
(LSW rst) R/W 40111
40112
Q min Min Reactive Power (VAR) Float
(LSW rst) R/W 40113
40114
S MAX Max Apparent Power (VA) Float
(LSW rst) R/W 40115
40116
S min Min Apparent Power (VA) Float
(LSW rst) R/W 40117
40118

Manuale d’uso - 17
Register
Name Comment Register Type R/W Default
Value Range Modbus
Address
Cosφ MAX Max Cosφ Float
(LSW rst) R/W 40119
40120
Cosφ min Min Cosφ Float
(LSW rst) R/W 40121
40122
Frequency MAX Max Frequency (Hz) Float
(LSW rst) R/W 40123
40124
Frequency min Min Frequency (Hz) Float
(LSW rst) R/W 40125
40126
THD MAX Max THD Float
(LSW rst) R/W 40127
40128
THD min Min THD Float
(LSW rst) R/W 40129
40130
STATUS SW
bit 0: ash settings error;
bit1: ash calibration error;
bit 2: Voltage Over Range;
bit 3: Voltage Under Range;
bit [4:5] Reserved;
bit 6: Zero crossing detecting;
bit [7:9] Reserved;
bit 10: Energy storing error;
bit 11: Energy initialization error;
bit 12: Reserved;
bit 13: Current Over Range;
bit 14: Current Under Range;
bit 15: Reserved.
Unsigned short R40132
V RMS SW Voltage RMS measurement (V)
swapped
Float
(MSW rst) R40133
40134
I RMS SW Current RMS measurement (mA)
swapped
Float
(MSW rst) R40135
40136
P SW Power measurement (W) swapped Float
(MSW rst) R40137
40138
Q SW Reactive Power measurement Q
(VAR) swapped
Float
(MSW rst) R40139
40140
S SW Apparent Power measurement S (VA)
swapped
Float
(MSW rst) R40141
40142
Cosφ SW Cosφ measurement swapped Float
(MSW rst) R40143
40144
Frequency SW Frequency measurement (Hz)
swapped
Float
(MSW rst) R40145
40146
THD SW THD swapped Float
(MSW rst) R40147
40148

18 - Manuale d’uso
Register
Name Comment Register Type R/W Default
Value Range Modbus
Address
Energy SW Total Energy measurement (KWh)
swapped
Float
(MSW rst) R40149
40150
Energy positive
SW
Only positive Energy Measurement
(KWh) swapped
Float
(MSW rst) R40151
40152
Energy
negative SW
Only negative Energy Measurement
(KWh) swapped
Float
(MSW rst) R40153
40154
V peak SW Instantaneous Voltage Peak (V)
swapped
Float
(MSW rst) R/W 40155
40156
I peak SW Instantaneous Current Peak (mA)
swapped
Float
(MSW rst) R/W 40157
40158
V MAX SW Max RMS Voltage (V) swapped Float
(MSW rst) R/W 40159
40160
V min SW Min RMS Voltage (V) swapped Float
(MSW rst) R/W 40161
40162
I MAX SW Max RMS Current (mA) swapped Float
(MSW rst) R/W 40163
40164
I min SW Min RMS Current (mA) swapped Float
(MSW rst) R/W 40165
40166
P MAX SW Max RMS Power (W) swapped Float
(MSW rst) R/W 40167
40168
P min SW Min RMS Power (W) swapped Float
(MSW rst) R/W 40169
40170
Q MAX SW Max Reactive Power (VAR) swapped Float
(MSW rst) R/W 40171
40172
Q min SW Min Reactive Power (VAR) swapped Float
(MSW rst) R/W 40173
40174
S MAX SW Max Apparent Power (VA) swapped Float
(MSW rst) R/W 40175
40176
S min SW Min Apparent Power (VA) swapped Float
(MSW rst) R/W 40177
40178
Cosφ MAX SW Max Cosφ swapped Float
(MSW rst) R/W 40179
40180
Cosφ min SW Min Cosφ swapped Float
(MSW rst) R/W 40181
40182
Frequency
MAX SW Max Frequency (Hz) swapped Float
(MSW rst) R/W 40183
40184
Frequency
min SW Min Frequency (Hz) swapped Float
(MSW rst) R/W 40185
40186
THD MAX SW Max THD swapped Float
(MSW rst) R/W 40187
40188
THD min SW min THD swapped Float
(MSW rst) R/W 40189
40190

Manuale d’uso - 19
Register
Name Comment Register Type R/W Default
Value Range Modbus
Address
STATUS 100
bit 0: ash settings error;
bit1: ash calibration error;
bit 2: Voltage Over Range;
bit 3: Voltage Under Range;
bit [4:5] Reserved;
bit 6: Zero crossing detecting;
bit[7:9] Reserved;
bit 10: Energy storing error;
bit11: Energy initialization error;
bit 12: Reserved;
bit 13: Current Over Range;
bit 14: Current Under Range;
Unsigned short R40192
V RMS 100 Voltage RMS measurement (V/100)
in hundredths
Signed long
(LSW rst) R40193
40194
I RMS 100 Current RMS measurement (mA/100)
in hundredths
Signed long
(LSW rst) R40195
40196
P 100 Power measurement (W/100) in
hundredths
Signed long
(LSW rst) R40197
40198
Q 100 Reactive Power measurement
(VAR/100) in hundredths
Signed long
(LSW rst) R40199
40200
S 100 Apparent Power measurement
(VA/100) in hundredths
Signed long
(LSW rst) R40201
40202
Cosφ 100 Cosφ measurement in hundredths Signed long
(LSW rst) R40203
40204
Frequency 100 Frequency measurement (Hz/100) in
hundredths
Signed long
(LSW rst) R40205
40206
THD 100 THD in hundredths Signed long
(LSW rst) R40207
40208
Energy 100 Total Energy measurement
(KWh/100) in hundredths
Signed long
(LSW rst) R40209
40210
Energy positive
100
Only positive Energy Measurement
(KWh/100) in hundredths
Signed long
(LSW rst) R40211
40212
Energy
negative 100
Only negative Energy Measurement
(KWh/100) in hundredths
Signed long
(LSW rst) R40213
40214
V peak 100 Instantaneous Voltage Peak (V/100)
in hundredths
Signed long
(LSW rst) R/W 40215
40216
I peak 100 Instantaneous Current Peak
(mA/100) in hundredths
Signed long
(LSW rst) R/W 40217
40218
V MAX 100 Max RMS Voltage (V/100) in
hundredths
Signed long
(LSW rst) R/W 40219
40220
V min 100 Min RMS Voltage (V/100) in
hundredths
Signed long
(LSW rst) R/W 40221
40222

20 - Manuale d’uso
Register
Name Comment Register Type R/W Default
Value Range Modbus
Address
I MAX 100 Max RMS Current (mA/100) in
hundredths
Signed long
(LSW rst) R/W 40223
40224
I min 100 Min RMS Current (mA/100) in
hundredths
Signed long
(LSW rst) R/W 40225
40226
P MAX 100 Max RMS Power (W/100) in
hundredths
Signed long
(LSW rst) R/W 40227
40228
P min 100 Min RMS Power (W/100) in
hundredths
Signed long
(LSW rst) R/W 40229
40230
Q MAX 100 Max Reactive Power (VAR/100) in
hundredths
Signed long
(LSW rst) R/W 40231
40232
Q min 100 Min Reactive Power (VAR/100) in
hundredths
Signed long
(LSW rst) R/W 40233
40234
S MAX 100 Max Apparent Power (VA/100) in
hundredths
Signed long
(LSW rst) R/W 40235
40236
S min 100 Min Apparent Power (VA/100) in
hundredths
Signed long
(LSW rst) R/W 40237
40238
Cosφ MAX 100 Max Cosφ in hundredths Signed long
(LSW rst) R/W 40239
40240
Cosφ min 100 Min Cosφ in hundredths Signed long
(LSW rst) R/W 40241
40242
Frequency MAX
100
Max Frequency (Hz/100) in
hundredths
Signed long
(LSW rst) R/W 40243
40244
Frequency min
100
Min Frequency (Hz/100) in
hundredths
Signed long
(LSW rst) R/W 40245
40246
THD MAX 100 Max THD in hundredths Signed long
(LSW rst) R/W 40247
40248
THD min 100 min THD in hundredths Signed long
(LSW rst) R/W 40249
40250
Command
Flash settings save command =
0xC1C0;
Reset command = 0xC1A0;
Load Energy command = 0xBABA
(energy to load must be written in
Command_aux);
Load Positive Energy command =
0xBABB (positive energy to load must
be written in Command_aux);
Load Negative Energy command =
0xBABC (negative energy to load
must be written in Command_aux);
Unsigned short R/W 040252
Command aux Auxiliary Register for Energy
Command (see command register)
Float
(LSW rst) R/W 040253
40254