Pipe fittings
All pipe connections to the Remeha Flexistor are made via BSP female parallel threaded pipe connection directly to the unit.
Cold water supply
A 2" cold water supply is recommended, however, if a smaller supply exists which provides sufficient flow this may be used. More flow noise
may be experienced from small bore pipes due to the increased water velocity through them. A minimum flow rate of 100l/min is required for
the Remeha Flexistor range of cylinders
High flow cold water control pack (Low and high pressure)
The control pack consists of a pressure reducing valve with integral strainer, check valve, core unit and expansion relief valve. The pressure
settings are adjustable for the low or high pressure valve sets. For the "low" pressure valve set the pressure reducing valve can be set between 1.5
and 6 bar. For the "high" pressure valve set the pressure can be set between 5 and 10 bar. For optimum performance the following installation
instructions should be complied with.
Note: The expansion vessel pressure must be set in accordance with the inlet pressure set on the pressure reducing valve by the installer. Set the
Expansion Vessel pressure before pressurising the cylinder.
Installation
Flush supply pipe work before connection to remove all flux and debris prior to fitting the inlet controls. Failure to do this may result in
irreparable damage to the controls and will invalidate the warranty.
The pressure reducing valve can be fitted in any orientation to suit the installation as long as it is fitted in the correct flow direction. Check the
flow arrows on the side of the body.
The expansion relief valve should be installed with the discharge pipe work in either the horizontal position or facing downwards, if the
discharge pipe is facing upwards debris may be deposited on the seat of the valve when in operation.
The blank plastic plugs in the body of the pressure relief valve are pressure gauge connections to enable pressure monitoring to be carried
out, should the system develop a fault. It is recommended that these be accessible (the pressure reducing valve has two - only one need be
accessible).
Expansion relief discharge pipe work must be connected to a safe visible discharge point via a tundish and the pipe work must have a continuous
fall. If site conditions allow, the expansion relief discharge pipe work can be connected to the T&P valve discharge pipe work before the tundish.
Pressure reducing valve
The pressure reducing valve can be connected anywhere on the cold water mains supply prior to the Remeha Flexistor unit. There is no
requirement to site it close to the unit, it can be located at a point where the mains supply enters the premises if this is more convenient but
you must install a non-return valve just after the reducing valve for ease of maintenance. The pressure reducing valve incorporates a adjustable
pressure reducer / strainer. The valve can be fitted in any orientation to suit the installation, however, ensure that the valve is installed with the
direction of flow arrows (stamped on the side of the brass body) pointing towards the Remeha Flexistor cylinder
page 13