71.800.627.4499 INSTALLATION, OPERATION AND MAINTENANCE MANUAL RENEWAIRE.COM
RENEWAIRE.COM 1.800.627.4499
112
SPECIFICATIONS & DIMENSIONS
Specifications may be subject to change without notice.
ROOFTOP UNIT SPECIFICATIONS
ELECTRICAL DATA
Standard Electrical Specifications Optional Factory Installed
VFD Electrical Specifications
HP Volts HZ Phase FLA
per motor
Min. Cir.
Amps
Max.
Overcurrent
Protection
Device
FLA
per motor
Min. Cir.
Amps
Max.
Overcurrent
Protection
Device
3.0 208-230 60 Single 14.7-14 33.1 40 9.38-8.48 40.2 45
3.0
208-230
460
575
60
60
60
Three
Three
Three
9.38-8.48
4.24
3.3
21.1
9.5
7.4
25
15
15
9.38-8.48
4.24
3.3
23.2
10.5
8.2
25
15
15
5.0
208-230
460
575
60
60
60
Three
Three
Three
14.5-13.4
6.7
5.3
32.6
15.1
11.9
45
20
15
14.5-13.4
6.7
5.3
35.9
16.6
13.1
45
20
15
7.5
208-230
460
575
60
60
60
Three
Three
Three
21.0-19.0
9.5
7.6
47.3
21.4
17.1
60
25
20
21.0-19.0
9.5
7.6
52.0
23.5
18.8
60
25
20
CORE PERFORMANCE
ThermalPerformanceRatingsG52015.2.xlsx 8Cores(IOM)
30%
50%
70%
90%
2000 4000 6000 8000
Effectiveness (%)
Airflow (CFM)
At AHRI 1060 standard conditions.
See all AHRI certified ratings at www.ahrinet.org.
AIRFLOW PERFORMANCE
Airflow
CFM
External Static Pressure (in.w.g.)
0.00 0.25 0.50 0.75 1.00 1.25 1.50 1.75 2.00
BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM
3 HP LOW SPEED 3 HP MED
SPEED 3 HP HIGH SPEED
2000 1.3 640 1.3 730 1.4 810 1.6 8 90 1.9 960 2.4 1030 2.9 1100
3000 1.5 700 1.6 780 1.9 860 2.2 930 2.7 1000 3.1 1060 3.7 1130 5 HP HIGH
SPEED
4000 1.6 680 1.9 760 2.2 840 2.6 910 3.0 980 3.5 1040 4.0 1100 4.6 1160
4500 1.8 710 2.1 800 2.5 870 3.0 940 3.5 1010 4.0 1060 4.5 1120 5.1 1170
7.5 HP
HIGH
SPEED
5000
3 HP
LOW
SPEED
1.7 660 2.1 750 2.5 830 3.0 910 3.5 970 4.0 1030 4.5 1090 5.1 1140 5.6 1190
5500 2.0 710 2.4 790 2.9 870 3.4 940 4.0 1000 4.5 1060 5.1 1110 5.6 1160 6.2 1210
6000 2.4 750 2.9 840 3.4 910 4.0 970 4.5 1030 5.1 1090 5.7 1140 6.2 1190 6.8 1230
6250 2.6 780 3.1 860 3.7 930 4.2 990 4.8 1050 5.4 1100 6.0 1150 6.5 1200 7.1 1240
6500 2.8 800 3.4 880 4.0 950 4.5 1010 5.1 1060 5.7 1110 6.3 1160 6.8 1210 7.4 1250
6750 5 HP
LOW
SPEED
3.1 820 3.7 900 4.3 960 4.8 1020 5.4 1080 6.0 1130 6.6 1180 7.2 1220
7000 3.3 850 4.0 920 4.6 980 5.2 1040 5.8 1090 6.3 1140 6.9 1190 7.5 1230
7250 3.6 870 4.3 940 4.9 1000 5.5 1060 6.1 1110 6.7 1160 7.2 1200
7500 3.9 900 4.6 960 5.2 1020 5.8 1080 6.4 1120 7.0 1170
7750 5 HP
MED
SPEED
4.3 920 4.9 980 5.6 1040 6.2 1090 6.8 1140 7.4 1180
8000 4.6 940 5.3 1000 5.9 1060 6.5 1110 7.1 1160
8250 5.0 970 5.7 1020 6.3 1080 6.9 1130 7.5 1170
8500 5.4 990 6.0 1050 6.7 1100 7.3 1140
8800 5.9 1020 6.5 1070 7.1 1120
7.5 HP LOW SPEED 7.5 HP MED SPEED
Note: Airflow performance includes effect of clean, standard filter supplied with unit.
LE10XRT shown
Ventilation Type:
Static plate, heat and humidity transfer
Typical Airflow Range: 2,000-8,800 CFM
AHRI 1060 Certified Core: Eight L125-G5
Standard Features:
TEFC Premium efficiency motors
Motor starters
Non-fused disconnect
24 VAC transformer/relay package
Filters: Total qty. 16, MERV 8: 20" x 25" x 2"
Unit Dimensions & Weight:
111 1/4" L x 165 1/2" W x 71 1/4" H
Modular (per module) 1,311-1,806 lbs., varies by option(s)
Assembled (1-piece) 2,631-3,453 lbs., varies by option(s)
Max. Shipping Dimensions & Weight (on pallet):
Modular (2-modules) 100" L x 90" W x 78" H
Module 1 - 1,986 lbs., Module 2 - 1,917 lbs.
Assembled (1-piece) 200" L x 90" W x 78" H
3,812 lbs.
Motor(s):
Qty. 2, Belt drive blower/standard motor packages
with choice of adjustable sheaves for low,
medium or high blower speed (see table below)
Options:
Integrated programmable controls
Fused disconnect
Double wall construction
Factory supplied and mounted variable frequency
drives (VFDs) - one or both airstreams
Shaft grounding ring on motors with VFDs
Class 1 low leakage motorized isolation dampers -
OA, RA or both airstreams
Qty. 2, Factory mounted filter alarms
Exterior paint - white, custom colors
Spring vibration isolators
Accessories:
Filters - MERV 13, 2" or 4"; MERV 8, 4" (shipped loose)
Roof Curb - Standard 14"
Curb wind clip
Engineered combo curb for Carrier RTU
Engineered combo curb for Trane RTU
Digital time clock - wall mount (TC7D-W),
in exterior enclosure (TC7D-E)
Motion occupancy control - ceiling mount (MC-C),
wall mount (MC-W)
Carbon dioxide control - wall mount (CO2-W),
duct mount (CO2-D)
Electric duct heater - EK series (1–60 kW),
EH series (61–175 kW); designed for indoor
ductwork installation only
Indirect gas-fired duct furnace - GH series
(50-400 MBH), installed downstream of any fans
8XRTHE Energy Recovery Ventilator
Standard
LE
Download specification at:
renewaire.com/specifications
LE8XRT SUBMITTAL SPECIFICATIONS LE8XRT SUBMITTAL SPECIFICATIONS