X
0
1
2
3
4
5
6
7
C
Y
PWR
0
1
2
3
C1
4
5
6
7
C2
Models:
FLD0808N
FLD0808P
FLD0808R
FlexiLogics series
INSTRUCTION SHEET
Thank you for purchasing FlexiLogics series
expansion models. Please read the instruction sheet
and thoroughly familiarize yourself with the functions
and characteristics of the products before use.
For more information, please refer user manual which
will be available in FlexiSoft software help and/or you
can download from REPL website.
Digital Inputs: 8 Normal inputs 8 points per
common. Bidirectional type.
Digital outputs:
8 Relay (Form A) outputs. 4
points per common.
Power Supply: 24VDC, 50mA
100mA for relay coil supply
Input per channel: 24VDC, 5mA
Output per channel: 0.5 A, 24VDC and
For FLD0808R: 230V, 2A /
24VDC, 2A
Input Impedance: 5.4K ohm
Min. ON voltage: 9.6 VDC
Max. OFF voltage: 3.6 VDC
Turn ON time: 10 msec
Turn OFF time: 10 msec
Isolation: Optically isolated from the
internal circuit
8 NPN type Transistor o/p. 4
points per common.
8 PNP type Transistor o/p. 4
points per common.
Output Capacity 2A per o/p. 8A per common for
Relay type o/p
500mA max for PNP and NPN
type transistor o/p
Rated load: 230V / 2A, 30VDC / 2A (for Relay),
500mA at 24VDC (for transistor)
General:
Operating Temp.: 0 to 55 C.
Storage Temp.: -20 to 85 C.
Operating Humidity: 10% to 90% (Non condensing)
Vibration: 10Hz to 150Hz ,displacement of
0.2 mm (peak)
(3 mutually perpendicular axes)
Shock: 490.5 m/s2,2 half-sine shocks per
axis, on (3 mutually perpendicular
axes)
Mechanical Dim.: 100mm X 35mm X 70mm
Power Rating (Back Plane)
Voltage Rating: 3.75 VDC derived from base
Current Rating: Up to 80mA
Power Supply:
Supply: 24 VDC +/-15% @ 80mA
Up to 100mA for relay coil supply
Input: 5mA per input
Output: 0.5A @ 24 VDC per output
230V / 2A or 24VDC / 2A per output
O
O
Specifications:
FIG-1 Pull up the sliders provided with the unit towards outward direction.
FIG-2 Rest the unit on the DIN rail plate
FIG-3 Pull down the slider again so that unit can fix up with the DIN rail plate.
Steps to lock the expansion module with base module:
Fig 1 Fig 2 Fig 3 Fig 4
FIG-1 Lock connector provided with base PLC unit
FIG-2 Two slots to grip the locking connector are
provided on the case highlighted by RED circle. Insert
a big leg of locking connector highlighted by RED
rectangle.
FIG-3 Single base PLC unit with locking connector
FIG-4 Locking connector helps the two units (FL base
&/or FL expansion) to hold each-other properly on the
DIN rail plate along with DIN rail slider.
Renu Electronics Pvt. Ltd. Pub.: 01/2011
Dimensions and Panel Mounting:
WARNINGS:
WARNING: DO NOT REMOVE OR REPLACE WHILE
CIRCUIT IS LIVE UNLESS THE AREA IS
KNOWN TO BE FREE OF IGNITIBLE
CONCENTRATIONS OF FLAMMABLE SUBSTANCES.
This equipment is suitable for use in Class I, Division 2,
Groups A, B, C and D or non-hazardous locations only.
WARNING – EXPLOSION HAZARD – Do not
disconnect equipment unless power has been removed
or the area is known to be non-hazardous.
WARNING – EXPLOSION HAZARD - Substitution of
components may impair suitability for Class I, Division 2.
WARNING - CAUTION, Battery May Explode If
Mistreated. Do Not Recharge, Disassemble Or Dispose
Of In Fire.
WARNING - exposure to some chemicals may degrade
the sealing properties of materials used in the following
devices; Relay Model G6M-1A-DC24, manufactured by
OMRON Relay Model G6DS-1A-H-DC24, manufactured
by OMRON
A recommendation for the user to periodically inspect
the sealed devices used, for any degradation of
properties and replace if degradation is found.