REO REOVIB 514 User manual

Operating Instructions
REOVIB 514
ID No. 51401
REO ELEKTRONIK AG
5140110_EN_09-12.DOC
27.02.2012
Thyristor control units for use with vibratory feeder units
The REOVIB 514 range of control units are suitable for powering vibratory feeders which have a mechanical vibrating frequency
which the same as, or double that of mains frequency. The adjustment of feeder throughput is achieved by using a triac with
phase angle control. The set point for the feeder throughput can be derived from a potentiometer, a signal voltage 0…10 V or a
signal current 0/4…20 mA. The set point input is isolated from live mains. The set point range can be adjusted to suit the
feeder unit by using trimmers “Umin “ / “Umax” (see “effects of trimmers Umin / Umax”).
The units can operate with feeders which have a mechanical vibrating frequency of 50 Hz or 100 Hz, ie 3000/6000 vibs/min (for
60Hz mains supply this would be 60 Hz or 100 Hz, ie 3600/7200 vibs/min). The mechanical frequency is determined, externally,
by the use of a link between terminals 19 and 20; without link = 50 Hz or 3000 vibs/min and with link = 100 Hz or 6000 vibs/min.
An enable input is provided on terminals 8, 9 and 10 for power free switching of the output (eg from a PLC). This input can be
operated from external contacts or with a signal voltage 12...24 V. The unit is enabled when the contacts are closed or when a
signal voltage is applied. The enable input is isolated from the mains. An additional control input is provided on terminals 1 and
2 for use with other control units, such as a track controller. When these inputs are not used, then each pair of terminals 1and
2, as well as 8 and 9 must be linked.
The unit is supplied in a simple to install modular housing which is suitable for both DIN rail mounting (EN 50022-35) and back
panel mounting. The terminals have safety covers, according to VBG 4 standards.
Technical data
Type REOVIB 514 51401
Supply voltage 230 V, + 6 % / - 10 %, 50/60 Hz
Output voltage 0…210 V
Output current 0.5…6 A
Set point source Potentiometer 10 kΩ
0…10 V, DC Ri 20 kΩ
0…20 mA Ri 500 Ω
Enable input Contact / 12…24 V, DC signal voltage Ri 10 kΩ
Ambient operating temperature 0…45
O
C
Dimensions (h x w x d) 74 x 100 x 125,5 mm
Enclosure standard VBG 4
Other standards EN 61000-6-2, EN 61000-6-4, VDE 0160
Fuse FF 10 A (5 x 20 mm)
Ordering Code: REOVIB 51401 ID No.: 51401.10
100
74
C 125,5 C1 106,5
U
E
E
1
2
Umax Umin
REOVIB 514

Operating Instructions
REOVIB 514
ID No. 51401
REO ELEKTRONIK AG
Technical Safety Information for the User
This description contains the necessary information for the correct application of the product described below. It is intended for
use by technically qualified personal.
Qualified personnel are persons who, because of their training, experience and position as well as their knowledge of
appropriate standards, regulations, health and safety requirements and working conditions, are authorised to be responsible for
the safety of the equipment, at all times, whilst carrying out their normal duties and are therefore aware of, and can report,
possible hazards (Definition of qualified employees according to IEC 364)
Safety Instructions
The following instructions are provided for the personal safety of operators and also for the protection of the described product
and connected equipment.
Warning!
Hazardous Voltage
Failure to observe can kill, cause damage or serious injury
•Isolate from mains before installation or dismantling work, as well as for fuse changes or post installation modifications.
•Observe the prescribed accident prevention and safety rules for the specific application.
•Before putting into operation check if the rated voltage for the unit conforms with the local supply voltage.
•Emergency stop devices must be provided for all applications. Operation of the emergency stop must inhibit any further
uncontrolled operation.
•The electric connections must be covered!
•Earth connection must be checked for safe function after assembly!
Specified Use
The units described herein are electrical controllers for installation in industrial plant. They are not suitable for domestic use.
Units with exposed electrical contacts are only suitable for installation in control panels.
These units conform with the standard 2004/108/EC EMC Standard
!
230V, 50/60Hz
L
N
PE
Magnet
Set point +
-+ -
12...24 V, DC
010 20 30 40 50 60 70 80 90 100[%]
10
20
30
40
50
60
70
80
90
100
[%]
output voltage
Set point
Umin
Umax
.
0...20 mA
0...10 V, DC
Connection for external track control
e.g. REOVIB 513, if not useing make a link
A S E
U
E
E
1
2
Umax Umin
REOVIB 514
link
Adjustment:
Connect controller according to diagram.
Adjust setpoint to minimum and inhibit unit.
Switch on mains supply and enable unit.
Slow increase the setpoint to maximum and monitor
the load condition (if possible measure the current).
On reaching maximum, limit the output with trimmer
Umax and then set the minimum set point
value with trimmer Umin.
Operating range
Effects of Umin and Umax trimmers
Connection Drawing
Setpoint source voltage signal
0...10 V, DC or current 0...20 mA
Enable signal voltage 12...24 V, DC
Control cables should be screened
Bond screen to earth on unit
Setpoint and enable control terminals are mains
potential free
Enable using
Signal Voltage
Close contacts to
enable
Setpoint source using
10 kOhm Potentiometer
Selection for
3000 / 6000 cycles / min
Fit link for
6000 cycles / min
Fit link for
0...20mA Setpoint source
To prevent noise the earth must be
bonded if possible to a flat mounting
surface eg mounting plate.
Only use type FF 10 A fuses
(very fast acting characteristic)