TECHNICAL DOCUMENTATION
DTR
Desctratification fan


Table of contents
1. INTRUDCTION
1.1 PRECAUTIONS
1.2 TRANSPORT
1.3 PACKAGE CONTENT
1.4 USE AND PRINCIPLE OF OPERATION
2. SCHEMATIC DIAGRAM
2.1 CONSTRUCTION
2.2 DIMENSIONS
2.3 TECHNICAL DATA
3. ASSEMBLY
4. INSTALLATION INSTRUCTIONS
5. PRECAUTIONS & WARNINGS
6. CONTROLS
7. CONNECTION SCHEMES
8. TERMS OF WARRANTY
8.1 WARRANTY CARD
8.2 WARRANTY FORM
8.3 SERVICE FORM
ENG
TECHNICAL DOCUMENTATION
1. INTRODUCTION
Thank you very much for purchasing Reventon Group's destratification fan. We
woud like to congratulate you on good choice.
1.1 PRECAUTIONS
The buyer and the user of the device should read carefully the following
instructions and proceed to the content recommendations. Proceeding due to
the following instruction guarantees the correct usage and safety. In case of any
doubts please contact the producer. The producer reserves the rights to make
changes to the technical documentation without previous notice. The producer
is not responsible for the damages which occur due to improper installation, not
keeping the device in repair or using the device out of line. The installation should
be carried out by the professional installers, who possess the qualications to
install these types of devices. The installers are responsible for making the
installation as instructed in the technical data. Regulations and safety rules must
be followed. During the installation, use, service and periodical inspections all
regulations and safety rules must be followed. In case of unserviceable please
plug out the device and contact with the authorized person or the producer.
1.2 TRANSPORT
During the acceptance of goods it is needed to check the device in order to
exclude any damages. During the transport it is needed to use the proper
equipment, it is necessary to carry the device by two people. In case of any
damages please ll in the damage report in presence of the supplier.
1.3 PACKAGE CONTENT
- Destratification fan
- Instruction and warranty card
1.4 USE AND PRINCIPLE OF OPERATION
In the heated high large-spaces the air mass is located in the upper part of room,
which causes the heat loss. Destratification fans also called the drop fans or air
mixers are used to save on heating. They steer the air back to work zone at the
same time they level out the air temperature in the high room, they also limit the
heat loss through the roof. They are used in production halls, warehouses and
logistic centres.
2. SCHEMATIC DIAGRAM
2.1 CONSTRUCTION
- Casing
- Four-sided diffuser- cover plate
- Axial fan
- Rotational holder
Casing: made of expanded polypropylene EPP, resistant, light and reliable. The
material is capable of carrying considerable loads without deforming. It does not
degrade under the influence of a lubricant, oil, crude oil and the majority of
chemicals. It has an excellent sound insulation properties, that is why it is used as
casings, material is environmentally friendly and "green", i.e. 100% recyclable.
Aesthetic design gives new nature to the device.
Four-sided diffuser: cover plate made of galvanized steel. It enables the air flow
in four different directions in the room.
Axial blowaing fan: protective grid made of steel wire galvanized, metal blades.
The motor has got the safety degree IP 54. Rated current 1,2 A . 1-phase device,
fan's diameter 450 mm.
Rotating mounting bracket: made of steel, element for mounting the device on
wall or ceiling. Soild and durable construction, possible to assemble device in
parallel on the angle 60º and 45 º. Possible rotation horizontally.
2.2 DIMENSIONS
CASING HC
height: 698 mm
width: 739 mm
depth: 340 mm
a)
b)
c)
2.3 TECHNICAL DATA
a
c
b
Unit of measure Destartification fan HC
Technical data
Maximum airflow
Maximum range of air stram
Rated current
Power supply voltage
Motor power
Noise *
Motor speed
Motor IP
m³/h
m
A
V/Hz
W
Obr./min
-
dB
5100
25
1,2
230/50
250
1350
54
50
* The measurement at a distance of 5 m from the unit.
3. ASSEMBLY
Destratification fans can be assembled on the wall or ceiling via rotating
mounting bracket. The drawings below show the ways of assembly. In the bigger
accommodation it is recommended to assemble more than one device. Follow the
parameters which are provided on the drawings.
4. INSTALLATION INSTRUCTIONS
The installation should be made by the qualified staff, who possess the needed
rights to install electrical devices, as instructed in the following documentation.
To install the Reventon Group destratification fans use the duct size 2 x 2,5mm².
5. PRECAUTIONS & WARNINGS
All works concerning electrical installation should be made by the qualified staff,
who possess the qualifications due to the domestic and local norms. These
recommendations include service and disassembly as well. Not following to the
recommendations may cause electrocution, device damages or its incorrect
work.
- Before service or exchange of the device it is obligatory to cut off the current
suply.
- Do not cover the inlet and outlet of the device.
- Do not use the device in room with high moisture or close to the water basin.
- Do not install, service the device with wet hands or barefoot.
- Do not use the device in room with flammable fumes, gas and high concentration
of dust.
– The device should be kept out of reach of children and animals.
– It is recommended to check the electric installation before the first start.
- It is recommended to use the external current dierential protection.
- After operating time of the device, please utilize it concerning the local norms
and regulations.
Drawing 1. Assembly on the ceiling.
max. 25m

It is recommended to clean the device periodically:
- Fan casing and blades clean form the dirt.
- If the device is not used for a longer time disconnect the voltage supply.
- The device is transported with the closed air stators. It is essential to open them
in 30 % before first start. Not keeping to the following recommendation may
cause the damages of the fan.
Opening the air stators must be made by two hands in parallel. Not keeping to
the following recommendation may cause the damages of the air stators.
6. CONTROLS
To make easier the usage of the Reventon Group devices we also offer
the additional controls:
Fan speed controller - designed to change the single-phase fan's speed voltage
controlled in industrial supply and heating systems
8. TERMS OF WARRANTY
I. Reventon Group Sp. z o.o. [Ltd. ] 3B Montazowa Street , 43-300 Bielsko-Biała,
Poland, is the producer of the Reventon Group brand. The warranty concerns the
following devices and it is valid for 3 years:
- destratification fan HC 5100 m3/h
* lifetime warranty for EPP caisng
II. Warranty is valid in the European Union.
III. The terms of warranty are valid from purchasing the device (the date issuing a
document confirming the purchase of the device) but not further than 42 months
from leaving the producer’s warehouse.
IV. The defects revealed during the warranty period will be removed free of
charge in 14 working days. The service will be done by the installation company
due to the terms of included in warranty card. The
elements will be supplied by the Reventon Group producer during the warranty
period.
V. Warranty does not cover the parts of the device subject to normal
maintenance and the cases as below:
a) Mechanical defects, damages from the impact of the improper transportation
or damages through improper storage.
b) Defects through:
- improper usage and service;
- using the device in the improper conditions (too high humidity, too high or too
low temperature, impact of the surrounding, sun etc.) ;
- modified equipment that has been modified or repaired without written
agreement of the producer;
- connecting additional equipment, which is not recommended by the producer
or inconsistent with the technical documentation;
- improper power supply.
c) Elements which wear and tear such as discolor or using.
VI. All changes in record in the warranty terms or any constructive modifications,
independent service outside the Reventon Group service or use, uncaring, makes
the warranty not valid.
VII. To obtain the service it is needed to send to the producer warranty card with
the signature, document confirming the purchase, (copy of the invoice) and
correctly filled the warranty form.
VIII. Not following to any of warranty regulations makes the warranty not valid.
IX. All correspondence, returns, complains should be send to the following
address: Reventon Group Sp. z o.o. 3B Montazowa Street, 43-300 Bielsko-Biała,
Poland or e-mail: [email protected]
The producer reserves the rights to make changes to the technical
documentation without previous notice.
5 control levels: 0-70-85-105- 145-230V
Power supply voltage: 230V AC/50-60Hz
Allowable current output: 3 A
Protection:
Dimensions: 126mm x 176mm x 56mm
Weight: 1,3kg
Degree of protection: IP 54
thermal cut-out
5 control levels: 0-70-85-105- 145-230V
Power supply voltage: 230V AC/50-60Hz
Allowable current output: 1,2 A
Protection:
Dimensions: 126mm x 176mm x 56mm
Weight: 1,3kg
Degree of protection: IP 54
thermal cut-out
Fan speed controller HC 1,2A Fan speed controller HC 3A
Fan speed controller HC 5A
0-80-120-140-170-230V
Power supply voltage: 230V AC/50-60Hz
Allowable current output: 5 A
Maximum ambient temperature: 40°C
Maximum temperature controller: 70°C,
limited motor protection.
Dimensions: 125 mm x 175 mm x 100 mm
Weight: 3,8 kg
Degree of protection: IP 54
5 control levels:
Fan speed controller HC 7A
0-80-120-140-170-230V
Power supply voltage: 230V AC/50-60Hz
Allowable current output: 7 A
Maximum ambient temperature: 40°C
Maximum temperature controller: 70°C,
limited motor protection.
Dimensions: 240 mm x 190 mm x 125 mm
Weight: 6,4 kg
Degree of protection: IP 54
5 control levels:
Fan speed controller HC 11A
0-80-120-140-170-230V
Power supply voltage: 230V AC/50-60Hz
Allowable current output: 11 A
40°C
70°C,
limited motor protection.
Dimensions: 240 mm x 190 mm x 125 mm
Weight: 8,1 kg
Degree of protection: IP 54
5 control levels:
Maximum ambient temperature:
Maximum temperature controller:
Fan speed controller HC 14A
0-80-120-140-170-230V
Power supply voltage: 230V AC/50-60Hz
Allowable current output: 14 A
40°C
70°C,
limited motor protection.
Dimensions: 240mm x 190 mm x 125 mm
Weight: 10,2kg
Degree of protection: IP 54
5 control levels:
Maximum ambient temperature:
Maximum temperature controller:
7. CONNECTION SCHEMES
PE- protective earthing, duct yellow-green colour;
N- neutral, duct black-black colour;
L- phase duct, duct brown colour;
Empty clamp, duct blue-black colour.

Reventon Group [Ltd.] 3B Montazowa Street, 43-300 Bielsko-Biała, Poland
:

Reventon Group [Ltd.] 3B Montazowa Street, 43-300 Bielsko-Biała, Poland

Reventon Group [Ltd.] 3B Montazowa Street, 43-300 Bielsko-Biała, Poland

Reventon Group Sp. z o.o. [Ltd.] , 3B Montażowa Street, 43-300 Bielsko-Biała, Poland, www.reventongroup.eu
Table of contents
Other REVENTON Fan manuals
Popular Fan manuals by other brands

Swegon
Swegon WISE Lockzone Ceiling a Instructions for use

Leader
Leader ESP280 user manual

Panasonic
Panasonic WhisperGreen FV-13VKML3 installation instructions

Pelonis
Pelonis FB50-16H owner's manual

Craftmade
Craftmade ELLINGTON Anvil ANV52ABZ5 installation guide

Zehnder Rittling
Zehnder Rittling Adaptive ZLE100TA installation instructions