RHEONICS SR User manual

PROFINET Field Device Specification:
Rheonics, SME
Covers sensor Types: SR, SRV, SRD, DVP, DVM

2
GLOBAL SUPPORT
For Support, visit: https://support.rheonics.com
EUROPE HEADQUARTERS
Rheonics GmbH
Klosterstrasse. 19
8406 Winterthur Switzerland
Tel: +41 52 511 32 00
US HEADQUARTERS
Rheonics, Inc.
3 Sugar Creek Center Blvd, Ste 100
Sugar Land, TX 77478
United States of America
Tel: +1 713 364 5427
Website: https://rheonics.com
Support Portal: https://support.rheonics.com
Sales E-Mail: info@rheonics.com
© COPYRIGHT RHEONICS 2021
No part of this publication may be copied or distributed, transmitted, transcribed, stored in a retrieval system,
or translated into any human or computer language, in any form or by any means, electronic, mechanical,
manual, or otherwise, or disclosed to third parties without the express written permission of Rheonics. The
information contained in this manual is subject to change without notice.
TRADEMARKS
Rheonics is a trademark of Rheonics, Inc. Other product and company names listed in this manual are trademarks
or trade names of their respective manufacturers.

Operators Manual
Contents
3
Contents
1Before you begin...................................................................................4
2Which gds file do i need?.......................................................................5
3Product overview..................................................................................6
4Profinet Installation ..............................................................................7
5Getting started......................................................................................8
6Installation process .............................................................................11
7Device configuration settings ..............................................................15
8Sensor status and parameter status ....................................................18
9Cyclic input data..................................................................................22
10 Units table ..........................................................................................30
11 Troubleshooting..................................................................................31
12 Notes/Errata .......................................................................................33

PNET Operators Manual
PNET -OP-2022
Chapter 1
Before you begin
4
1Before you begin
1.1 About the manual
This manual provides information on Profinet support on Rheonics devices. This document
specifies all the device-specific features and documents PROFINET Protocol implementation
details.
Important Instructions
This manual assumes that the following conditions apply:
•The sensor has been installed correctly and completely according to the installation
•The installation complies with all applicable safety requirements.
•The user is trained in relevant safety standards.
1.2 Purpose
This specification is designed to complement the SME Installation Manual by providing a
complete, clear description of this Field Device from a PROFINET Communication perspective.
1.3 Who should use this document?
The specification is designed to be a technical reference for PROFINET End Users. This document
assumes the reader is familiar with PROFINET Protocol requirements and terminology.
1.4 Warning
Before connecting the PROFINET Communicator in an explosive atmosphere, make sure
instruments are installed in accordance with intrinsically safe or EX classification-specific field
wiring practices. Explosions can cause serious injury or death.
1.5 Nomenclature
Abbreviation (short form)
Full-term
Meaning
SRV
Symmetric Resonator
Viscometer
Viscosity sensor
SRD
Symmetric Resonator
Densitometer
Density and Viscosity sensor
DVP
Density Viscosity Probe
HPHT inline probe
DVM
Density Viscosity Module
HPHT inline module
RCP
Rheonics Control Panel
Software for data acquisition
and configuration
SME
Smart Module Electronics
Sensor electronics
Table 1. Defined Acronyms
1.6 Related Documentation
You can find all product documentation on the USB stick shipped with the SME and on our
website at https://rheonics.com/resources

PNET Operators Manual
PNET -OP-2022
Chapter 2
Which GDS file do I need?
5
2Which GDS file do I need?
Rheonics GDS File provides the configuration information, parameters, modules, diagnostic and
vendor and device identification; to be used by the controller.
For up-to-date information, please check the page:
https://support.rheonics.com/support/solutions/articles/81000401423-profinet-
gsd-file-for-rheonics-inline-viscometer-and-density-meter

PNET Operators Manual
PNET -OP-2022
Chapter 3
Product overview
6
3Product overview
The Rheonics SME provides clients PROFINET interface to get digital data on devices ordered with
Profinet connectivity. This document provides guidance for field connection by an end user.
Note: If your sensor was ordered without Profinet, it is possible to upgrade it to add profinet
remotely. Contact Rheonics Sales team to order.
Figure 1. SME sensor electronics unit.
3.1 Process Interface
The SME is compatible with various Rheonics instruments. This includes Type: SR (SRV & SRD),
Type: DV (DVP, DVM) and other instruments using the SME electronics from Rheonics.
Figure 2. Rheonics Sensor for Viscosity and density measurements.
3.2 Reference to other instruments.
Manuals and guides for digital instruments are modular. General instructions give information
about the functioning and installation of instruments. Operational instructions explain the use of
the digital instrument features and parameters. Fieldbus specific information explains the
installation and use of the instrument on that Fieldbus network.
•SRV USER MANUAL
•SRD USER MANUAL
•DVP USER MANUAL
•DVM USER MANUAL
•SENSOR INSTALLATION MANUAL
•RHEONICS CONTROL PANEL USER MANUAL

PNET Operators Manual
PNET -OP-2022
Chapter 4
Profinet Installation
7
4Profinet Installation
4.1 Instrument overview:
Figure 3. SME-DRM Diagram.
4.2 Ethernet PIN assignment PROFINET
RJ45 Connector
Receptacle
Pin Number
Wire Color
Description
1
Yellow
Transmit+
2
Orange
Transmit-
3
White
Receive+
4
Not Used
5
Not Used
6
Blue
Receive-
7
Not Used
8
Not Used

PNET Operators Manual
PNET -OP-2022
Chapter 5
Getting started
8
5Getting started
5.1 Components Used
•Rheonics SRV, SRD, DVP or DVM w/ Firmware V03.30/0 or higher
•Siemens PLC S7-1212
•Configuration software: TIA Portal
•Software sensor: Rheonics Control Panel (RCP)
•Windows 10 64 bit
•GSDML file
•Ethernet Switch
5.2 System Connections
Connect Rheonics sensor, PLC, and PC (with RCP software installed) with an Ethernet Cable. We
recommend using an Ethernet Switch.
Connect SME to the PC running RCP to configure the SME.
Figure 4. Communication diagram for rheonics sensor-PLC and PC.

PNET Operators Manual
PNET -OP-2022
Chapter 5
Getting started
9
5.3 Configure Rheonics SME
Open RCP software on the connected PC, connect to the SME using USB and configure the SME
to use DHCP. Make sure it has a valid IP address. Figure 5 shows a standard configuration that can
be used for the correct performance of the system.
Figure 5. Configuration in RCP to use Profinet with DHCP.
5.3.1 Go to the “Comm Configure tab” in the RCP; In the Ethernet section input
all the parameters.
5.3.2 Click on the “Update SMET” button to upload the new settings into the SME
5.3.3 For Static IP address go to the “Comm Configure” tab in the RCP; in the
Ethernet section click the dropdown menu in DHCP and select false (This
will disable DHCP function) –input the static IP address, subnet and
gateway to use. Check RCP manual for detailed instructions.

PNET Operators Manual
PNET -OP-2022
Chapter 6
Installation process
11
6Installation process
This section describes how to install the GSD file in TIA portal software.
6.1 Open a project.
6.2 Load GSD file
6.2.1 Select [Manage general station description files (GSD)] in the [Options]
menu.
Figure 8. Screenshot of GSD file upload in TIA portal.
6.2.2 Select the file: GSDML-V2.4-Rheonics-SMET-20220321.xml, load and install
this file.
Figure 9. Adding GSDML file in TIA portal.

PNET Operators Manual
PNET -OP-2022
Chapter 6
Installation process
12
6.3 Rheonics sensor is now available in the hardware catalog.
6.3.1 Select device configuration.
Figure 10. Select device configuration from device tree.
6.4 From the [Hardware Catalog]
6.4.1 Choose the appropriate Rheonics sensor.
Figure 11. Selecting appropriate device from Hardware Catalog.
6.4.2 Select “Rheonics SMET” and add the device to your project.
Figure 12.Rheonics SMET device in the I/O device tree.

PNET Operators Manual
PNET -OP-2022
Chapter 6
Installation process
13
6.5 Rheonics sensor will appear in topology view.
Figure 13. Rheonics sensor as it appears in Topology View.
6.6 Connect the Rheonics sensor SMET to the PLC
6.6.1 Drag & drop the connection.
Figure 14. Screenshot showing Module Definition-Module Info.

PNET Operators Manual
PNET -OP-2022
Chapter 6
Installation process
14
6.7 Once PLC and SMET are connected you will find green wire that
connects both PLC controller and rheonics sensor.
Figure 15. Establishing Profinet network by connecting Rheonics SMET to PLC in TIA portal software.

PNET Operators Manual
PNET -OP-2022
Chapter 7
Device configuration settings
15
7Device configuration settings
The Rheonics PROFINET instruments offer many different modules and parameters. To select
these modules/parameters, the master configuration tooling software is used.
7.1 Rheonics device provides 2 modules “Diagnostics_1” and “Device
Parameters_1”.
Figure 16. Device overview Controller Address.
7.2 Diagnostics_1
7.2.1 This module covers data that is useful for Rheonics support team to help
customers diagnose any issues.

PNET Operators Manual
PNET -OP-2022
Chapter 7
Device configuration settings
16
Figure 17. Diagnostic module.
7.3 Device Parameters_1
This module covers the 22 parameters available for the SMET, as well the sensor status
parameter.
7.3.1 Define tags in the PLC table based in the information from the GSD file.
Figure 18. Define tag in the plc table from gsd file.
7.3.2 Go to online mode and start monitoring the parameters from the SMET

PNET Operators Manual
PNET -OP-2022
Chapter 7
Device configuration settings
17
Figure 19. Data monitor from SMET showing the measured data in both the TIA portal and RCP.

PNET Operators Manual
PNET -OP-2022
Chapter 8
Sensor status and parameter status
18
8Sensor status and parameter status
All rheonics sensors (SRV, SRD, DVP, DVM) for inline viscosity and density monitoring have inbuilt status.
These status bits can be used over digital communication channels to understand when the sensor is
operating correctly and when there is an issue.
8.1 Sensor Error Status
The sensor status can take any of the following values:
Bit
Hex
Name
Comment
Bit 0
0x0001
PLL frequency
mismatch
The PLL frequency does not match the sensor frequency.
Derived from the ASB string (E10)
Bit 1
0x0002
PLL not locked
The PLL is not locked. Derived from the ASB string (E01)
Bit 2
0x0004
PLL lock incorrect
The PLL has locked on a wrong frequency. Derived from
the ASB string (E02)
Bit 3
0x0008
ASB communication
error
Issues with sensor electronics
Bit 4
0x0010
Temperature sensor
failed
The temperature sensor has failed. Derived from the ASB
string if temperature is -273.0
Bit 5
0x0020
Sensor too hot
If temperature is above the hardcoded physical
temperature limit.
Bit 6
0x0040
ASB communication
error
Communication issue between two electronics board in
the SME
Bit 7
0x0080
Serial Changed
Bit 8
0x0100
Status not clean
Sensor is not clean (only SRV)
Bit 9
0x0200
Status in Air
Determines if sensor is in air
Bit 10
-15
Unused
Table 2. Sensor error status bit code and description.

PNET Operators Manual
PNET -OP-2022
Chapter 8
Sensor status and parameter status
19
8.2 Parameter Status
The Parameter Status can take any of the following values, OR a combination of these states.
For example: If there is a config error, the status value will be 0x0003
If there is a config error and an internal error, the status will take a value of 0x0023
Bit
Hex
Name
Comment
Bit 0
0x0001
General error
This bit is always set in case there is an issue with the parameter. It
can be used by the general user or application programmer to alert
an issue with that parameter output. For details check the other bits
Bit 1
0x0002
Config error
The parameter is not configured or there exists a configuration
error.
Bit 2
0x0004
Hardware
error
The parameter cannot be calculated as the hardware failed.
Example: Temperature sensor has failed.
Bit 3
0x0008
Dependent
error
A parameter source for a dependent parameter is not available.
Example: In case of a free formula a referenced parameter is NAN.
Bit 4
0x0010
Not ready
No result is yet available.
Example: No measurement has been taken yet. The algorithm
requires a run-in time
Bit 5
0x0020
Internal error
Internal error - Report to Rheonics
Bit 6
0x0040
Calibration
Error
Diagnostics
Bit 7
0x0080
Further use
Bit 8
0x0100
Parameter
Calibrated
Triggered when parameter has a calibration/scale factor/coefficient
applied to it.
Bit 9
0x0200
Model
Loaded
Active when a model has been loaded in script parameters. Only
valid for parameters 19,20,21
Bit
10
0x0400
Filtering
Active
Active when there is a filter loaded for that parameter
Bit
11
0x0800
Not stable
Parameter result not yet stable
Example: Set for example on viscosity if sensor status is not okay.
Bit
12
0x1000
Warning
lower
Below lower warning limit (if configured for parameter)
Bit
13
0x2000
Warning
upper
Above upper warning limit (if configured for parameter)
Bit
14
0x4000
Alarm lower
Below alarm limit (Hardcoded depending on parameter type)
Bit
15
0x8000
Alarm upper
Above alarm limit (Hardcoded depending on parameter type)
Table 3. Parameter Status bit code and description.

PNET Operators Manual
PNET -OP-2022
Chapter 8
Sensor status and parameter status
20
8.3 How to read sensor status?
Sensor status is a WORD data type, these status bits can be used over digital communication
channels to understand when the sensor is operating correctly and when there is an issue.
Figure 20. Sensor Status parameter table.
In the scenario described in Figure 20, Sensor Status has a value 16#1701, bytes must be
swapped for the correct reading of the sensor as they should be read as 16#0117 for a little-
endian format. Sensor error status is the combination from any bit from Table 2. Sensor error
status bit code and description.in this scenario Error0117 is the combination (OR) of the error
bits.:
Bit
H
Comments
0
0x01
The PLL frequency does
not match the sensor
frequency. Derived from
the ASB string (E10)
1
0x02
The PLL is not locked.
Derived from the ASB
string (E01)
2
0x04
The PLL has locked on a
wrong frequency. Derived
from the ASB string (E02)
4
0x10
The temperature sensor
has failed. Derived from
the ASB string if
temperature is -273.0
8
0x100
Sensor is not clean (SRV
only)
Result
0x117
Table 4. Sensor status bits for status 0117.
8.4 Which parameters should I read?
This manual suits for next models
4
Table of contents
Other RHEONICS Accessories manuals