manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Rielta
  6. •
  7. Gas Detector
  8. •
  9. Rielta SH-VTG User manual

Rielta SH-VTG User manual

Push
1 General Information
AТМ security vibration, tilt and gas detector «SH-VTG»
(hereinafter, the
Detector) is designed to detect intrusion, burglary and/or
theft attempts
to units such as ATMs, Deposit Safes, Vault Doors, Free Standing Safes
and other valuables protection equipment.
Tree independent detection channels control construction break-in, tilt
of monitored structure, as well as explosive gases (propane, methane,
hydrogen, etc.) detection.
The Detector is resistant to EMI, to single blows delivered on
monitored structure and to acoustic noises.
The Detector provides choosing of operation mode in accordance
with secured structure material type as well as a possibility of sensitivity
step adjustment.
The Detector generates an alarm message by opening («C» «NC»)
contacts for a time not less than 2 sec and LED indication switching
on (see Table 1).
Table 1
Message Description
Contacts Indicators
VIBR
TILT
GAS
FAULT
TAMP
red
green
yellow
MESSAGES
Norm Standby mode С С С С С - - -
Destruction,
break-in
Destructive impact on the
protected object
ОХ Х Х Х Х Х
Tilt alarm Tilt of the protected object Х ОХ Х Х Х Х
Gas alarm Explosive gases detection Х Х ОХ Х Х Х
Failure Supply voltage drop lower
than 8V or gas sensor failure ХХХОХ
Case or wall
tampering Case or wall tampering Х Х Х Х ОХ Х Х
INDICATION
Energizing Self-testing after energizing О О О О Х
Vibration Protected object vibration Х Х Х Х Х ХХ
Memory-
destruction
Fixed “Destruction” indication
Х Х Х Х Х ХХ
Memory-tilt
Fixed “Tilt” indication
Х Х Х Х Х Х Х
Memory-
failure
Fixed “Failure” indication
Х Х Х Х Х Х
Memory-gas
Fixed “Gas” indication
Х Х Х Х Х Х Х
- – is OFF;
Х – is unchanged;
О – contact is open;
С – contact is closed;
– LED is ON;
– infrequent LED blinking (once per second);
– frequent LED blinking (5 blinks per second).
2 Specifications
Table 2
Parameter Value
Detection area, not less than:
- metal cabinet, door, ATM upper safe
- safe, ATM lower cabinet
6 m2
3 m2
Detected concentration of flammable gases 10/20% of LEL*
(for propane)
Tilt changing detection 5° and more
Voltage supply range 9 – 17 V
Maximum consumption current 80 mА
Detector contacts valid current 100 mА
Detector contacts valid voltage 72 V
Warm-up time, not more than 60 sec
Operating temperature 0 … +50 °С
Permissible relative humidity at a temperature +25 °С 90 %
IP-rating IP30
Dimensions 105 х 45 х 34 mm
Weight, maximum 150 g
Average service life 8 years
* LEL – lower explosive limit
3 The Detector Design
The Detector layout is shown in Figure 1.
Figure 1
Figure 2
4 Scope of Delivery
Each Detector unit package contains the items listed in Table 3.
Тable 3
Name QNT
ATM security vibration, tilt and gas detector «SH-VTG»
ATM security vibration, tilt and gas detector «SH-VTG».
Installation Guide
Serial interface module «US-PI»
1 pc.
1 copy
*
* – supplied optionally
5 Gas Сhannel Testing
Energize the Detector and wait for 1 minute.
For testing the explosive gases detection channel, it is necessary to
provide gas on the gas sensor (Figure 2, position 3). For this purpose
household gas lighter can be used. The Detector should generate
«GAS» message during 10 seconds (See Table 1).
Attention! The Detector must be checked at least twice a year in
order to test it performance.
6 The Detector Adjustment and Mounting
The Detector mounting and sensitivity adjustment is fulfilled with the
removed cover. To remove cover, loosen the latch by pressing it through
the rectangular opening in the cover (See Figure 1).
Depending on type and material of secured construction, the
Detector is mounted either by screws through the base openings (the
distance between the openings is 35 mm) or by means of superglue. It
is very important to ensure firm contact with the surface of protected
construction.
For the Detector mounting on metal construction, it is recommended
to use screw connection (screw M4) with washers via openings or
connection (screw M4) through closed holes with preliminary cut thread.
In these conditions it is recommended to ground metal construction
with mounted Detector.
The Detector installation inside safes or lower ATM cabinet should
be fulfilled by means of M4 screws or superglue in accordance with
supporting documentation or application notes listed on it’s package.
The glue joint is also recommended for others metal constructions
without possibility to fulfill a screw connection.
ATM SECURITY
VIBRATION, TILT AND
GAS DETECTOR
«SH – VTG»
Installation Guide
The base with the PCB is shown in Figure 2.
b) bottom viewa) top view (without cover)
1 – Hook on the cover;
2 – DIP-Switch;
3 – Gas sensor
4 – Switch MEM;
5 – PCB Latch;
6 – Terminal Blocks;
7 – Cover latch;
8 – Openable holes for wiring;
9 – Indicators;
10 – Tamper;
11 – Wall tamper pin;
12 – Sensing element.
11
12
1
2
3
4
5
9
6
7
8
1 2 3 4 5 6
IND
ATM
S1
S2
S3
MEM
10
TILT GAS VIBR
TAMP FAULT +12V-
-10% LEL
-20% LEL
. .
BQ1
+
_
-20% LEL
-10% LEL
Attention!
The operating conditions of the Detector in a controlled
environment must exclude the presence of substances
that reduce the catalytic activity of sensitive elements and
corrosive substances: acid and alkali vapors, halogens,
fumes of silicon, phosphorus, silicone lubricants, varnishes,
sealants, etc.
7 Connection
The Detector connection to data transmission system (DTS) or control
panel (CP) terminal device (TD) should be fulfilled in accordance with
connection pattern contained in relevant TD, DTS or CP exploitation
documents as per the Detector terminal blocks marking (see Figure 2,
position 6). Two openable holes (see Figure 2, position 8) are available
for wiring.
8 The Detector Controls
The IND DIP-switch is used for the Detector LED indication switching
ON.
The ATM DIP-switch is intended for choosing the signal processing
algorithm depending on type of secured construction (See Table 4).
Table 4
Secured construction ATM switch position
Safe or metal construction (cabinet, door, lattice) OFF
Automated Teller Machine (ATM) ON
DIP-switches S1, S2, S3 are intended for adjustment of destruction
channel sensitivity (see Table 5).
Table 5
DIP-switches Sensitivity
S1 S2 S3
ON ON ON Maximum
Minimum
ON ON OFF
ON OFF ON
ON OFF OFF
OFF ON ON
OFF ON OFF
OFF OFF ON
OFF OFF OFF User-operating mode (see Cl. 10)
9 Adjustment Procedure
Remove the housing cover and set the IND DIP-switch to ON position.
Set switch ATM to the position corresponding to the material of the
protected structure (see Table 4).
Switches S1, S2, S3 – in position ON, ON, ON (maximum sensitivity
level).
Switch on the power supply and check the formation of the LED
indication «Power on» and the «Normal» message. The presence of
the indication «Vibration» in the standby mode and the absence of
the effects listed in Table 4 display too high level of interference on
the protected object. If possible, eliminate the source of interference.
Set the MEM switch to ON position, switches S1, S2, S3 to OFF, OFF,
ON (minimum sensitivity level).
At the boundary of the protected area, apply a simulating
impact corresponding to the type of the protected structure (see
Table 6). If the «Destruction» message is generated and after it the
«Memory-destruction» LED indication (see Table 1) is ON, the sensitivity
adjustment can be considered completed.
In the absence of the notice «Destruction» – perform a step-by-
step sensitivity increase (see Table 5) until «Destruction» message is
generated after imitating impact.
When the sensitivity level is set, the Detector should not generate a
«Vibration» indication in the absence of any effects on the protected
structure.
After adjustment fulfillment, it is necessary to set the IND and MEM
switches in accordance with the security tactics chosen for the object.
Table 6
Methodic of a simulating impact
applying during sensitivity
adjustment
Supplementary technical data
Apply a steel plate to the surface
of the protected structure at the
outermost point of the controlled
area. Drill several holes in the
plate with a depth of 2 – 3 mm.
For each drilling, observe the LED
indication «Vibration», and after
the third one – «Destruction»
LED indication.
Cordless drill, drill ∅ (4 ± 0,5) mm, the
time of one drilling is not less than 10 sec.
Pause between drilling not more than
10 sec.
Electric drill, drill ∅ (4 ± 0,5) mm, the time
of one drilling is not less than 10 sec.
Pause between drilling not more than
10 sec.
10 User-operating mode
The user-operating mode, activated by DIP-switches (see Table 5),
is designed to adapt the Detector to a severe interference conditions
on a secured object by means of individual sensitivity adjustment to
different types of attacks.
In this mode, sensitivity adjustment is carried out by means of a
personal computer connected to the Detector via the serial interface
module «US-PI» (supplied by «RIELTA» JSC on a special order).
The procedure of the Detector adjustment in User mode is given in
the accompanying documentation for «US-PI».
11 Storage and Transportation
11.1 During the transportation the Detector in the package withstands:
- transport jolting with acceleration up to 30 m/sec2at impacts
frequency range from 10 to 120 per minute or 15.000 impacts with
the same acceleration;
- ambient temperature from minus 50 to plus 50 оС;
- relative air humidity up to 100 % at temperature plus 25 оС.
11.2 The Detector in original package may be transported by any
means of transportation in closed vehicles over any distances in
compliance with the existing shipping rules concerning the respective
means of transportation.
11.3 After transportation under the conditions different to exploitation
conditions the Detector shall be ready for operation after a maximum
of six hours.
11.4 The storage package shall be free from silica gel.
12 Manufacturer’s Guarantees
12.1 The Manufacturer guarantees conformity of the Detector to the
requirements of Specifications provided the transportation, storage,
installation and operation conditions are observed.
12.2 The guaranteed storage term of the Detector is 15 months since
the date of manufacture.
12.3 The guaranteed useful life is 12 months since the day of putting
into operation within the storage term guaranteed.
12.4 If non-conformity of the Detector to technical requirements
is detected during the guaranteed period if rules of operation are
observed, it shall be repaired by the Manufacturer.
13 Packing Certificate
Atm security vibration, tilt and gas detector «SH-VTG» has been
manufactured in compliance with the active technical documentation
and classified as fit for operation and packed by «RIELTA» JSC.
Packing date _______________________________
month, year
Rev. 4 of 17.03.20
v.2.3/v.2.3R
«RIELTA» JSC, www.rielta.com
Chapaeva Str. 17, Saint Petersburg 197046, [email protected]
Tel./fax: +7 (812) 233-03-02, +7 (812) 703-13-60,
Technical support: [email protected]
Made in Russia

Popular Gas Detector manuals by other brands

Bacharach GDA-1600 instructions

Bacharach

Bacharach GDA-1600 instructions

Riken Keiki GD-F88Di operating manual

Riken Keiki

Riken Keiki GD-F88Di operating manual

EsiWelma Sensigas URD20SS quick start guide

EsiWelma

EsiWelma Sensigas URD20SS quick start guide

Riken Keiki 70D Series Construction manual

Riken Keiki

Riken Keiki 70D Series Construction manual

mPower Electronics POLI MP400 user guide

mPower Electronics

mPower Electronics POLI MP400 user guide

GasDog GD-600 user manual

GasDog

GasDog GD-600 user manual

Riken Keiki GX-2001 Operator's manual

Riken Keiki

Riken Keiki GX-2001 Operator's manual

Dräger REGARD 39 0 Series Instructions for use

Dräger

Dräger REGARD 39 0 Series Instructions for use

MSA ALTAIR4 Quick start card

MSA

MSA ALTAIR4 Quick start card

Duran Electronica SONDELTOX quick start guide

Duran Electronica

Duran Electronica SONDELTOX quick start guide

GDS 404 Series Operating handbook

GDS

GDS 404 Series Operating handbook

Samon GD instructions

Samon

Samon GD instructions

System Sensor CO1224A Frequently asked questions

System Sensor

System Sensor CO1224A Frequently asked questions

LINNEPE TriGasAlarm instruction manual

LINNEPE

LINNEPE TriGasAlarm instruction manual

Kimo CO 100 user manual

Kimo

Kimo CO 100 user manual

SENKO SGT-P user manual

SENKO

SENKO SGT-P user manual

Vighnaharta TS21I-CLR-EX instruction manual

Vighnaharta

Vighnaharta TS21I-CLR-EX instruction manual

Brasch GSE Generation 2 Installation & operation manual

Brasch

Brasch GSE Generation 2 Installation & operation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.