Instructions
GB
5762H402 Ed.02
AKO-57624
355762402 REV.01 2020
AKO ELECTROMECÁNICA , S.A.L.
Avda. Roquetes, 30-38
08812 • Sant Pere de Ribes.
Barcelona • Spain.
Tel.: +34 902 333 145
Fax: +34 938 934 054
www.ako.com
We reserve the right to supply materials that might vary slightly to those
described in our Technical Sheets. Updated information is available on our
website.
General warnings
-Using the unit without observing the manufacturer's instructions may alter the appliance's safety requirements.
- Detectors should be installed in a place protected from vibrations, water and corrosive gases, where the ambient
temperature does not exceed the value indicated in the technical data.
- Detectors supervise a point and not an area. If the gas leak does not reach the sensor, or the level of
concentration in that point does not reach the alarm values, no alarm will be activated. If perimeter
supervision is required, several sensors should be installed around that area.
Working conditions:
-Keep the detector work environment free of chemical agents (such as solvent, paints, alcohol, acetone, silicone, etc.), and
free of engine fumes or gases from fermentations (bread, pizza) or ripening (breathing) of fruits.
-The detector should generally be installed in an area of potential concentration/accumulation of gas, in low positions (due
to the greater relative density, in relation to air, of the gases subject to detection).
-The AKO-57624 refrigerant gas detector may only be used in locations that have not been classified with risk of explosion.
-Reference regulations: EN 378
-Applicable local regulations: Compliance must be ensured
Technical specifications
Power supply ...............................................................................................................................................................12-30 Vdc
Consumption........................................................................................................................... Typical: 75 mA, Maximum:150 mA
Alarm relay .........................................................................................................................................SPDT 30 Vdc, 2A, cos j =1
Working ambient temperature....................................................................................................................................-20 to 50 ºC
Storage ambient temperature.....................................................................................................................................-20 to 60 ºC
Range of moisture permitted...................................................................................................0 - 95 % RH (Without condensation)
Protection degree.................................................................................................................................................................IP68
Dimensions..........................................................................................................................107 mm (W) x 85 mm (H) x 39 mm (D)
Complies with the EN 14624 standard.
Installation
2
1
Option A
Fixed by screws
36 mm
70 mm
3
1
2
Optional rear cable entry
3.3
3.1
3.2
Option B
Fixed by an
adhesive
x2
Ø 2,8 mm
Ø 5 mm
x2
+
Connect following the
diagrams
Carefully perforate the rear entry so as not to
damage the electronic board.
This option involves changing from IP68 to
IP40.
Red
Green
Blue
OFF
No alarms
Detector turned off
1st set of levels activated
ON
Alarm / Pre-Alarm activated
Standard operation
2nd set of levels activated
Flashing*
Alarm / Pre-Alarm saved
Standard operation, acoustic
alarm disabled
MAINTENANCE mode
activated
Flash*
Detector error
Detector in initialisation
process
SET HOLD mode activated
Pre-Alarm
Alarm
Sensor error
Intermittent
sound
Bi-tonal
sound
3 tones
every 2 minutes
Description
Refrigerant gas detector, which can be used in independent operation or connected to alarm stations AKOCam, AKOAlarm and AKOGas.
Independent detector: The detector makes a certain warning sound in the event of an Alarm, Pre-Alarm or sensor error and the red indicator lights up (See operation section).
Detector connected to the alarm station: The detector notifies the station of its status (Alarm, Pre-Alarm or sensor error) and the station notifies the alarm through sound and indicators (for
further information consult the station's manual).
Pre-alarm jumper
Configuration push-button
Connection strip
Delay and alarm
levels configuration
Pre-alarm enabled
Pre-alarm disabled
Alarm delay
C C
NC NCNO NO
Gas
Alarm
Tr-
Tr-
Tr+
Tr+
Gnd
Gnd
RS485 RS485
Alarm Alarm
15V
15V
S
S
Gnd
Gnd
Red: Alarms Green:
Operation
Mute
push-button Blue: Operating
mode
Operation
Mute push-button
In the event of an Alarm or Pre-Alarm in process, any push-button press silences the Alarm/Pre-Alarm tone.
Any push-button press deletes saved alarms.
Medium press (between 3 and 9 sec.): It activates or deactivates the SET-HOLD mode. Should there be a sensor error, reset the detector.
Long press (> 9 sec.): It activates or deactivates the MAINTENANCE mode. Should there be a sensor error, reset the detector.
Configuration
In this mode the acoustic alarm can be activated / deactivated or the detector can be returned to factory settings.
To activate it:
1.- Disconnect the power supply, reconnect it and press the “CONFIGURATION” push-button 5 times within 2 minutes; the detector will emit a confirmation beep and the blue indicator will show the
status of the acoustic alarm: ON: Acoustic alarm enabled / Flashing: Acoustic alarm disabled.
2.- Press the Mute push-button to enable / disable the acoustic alarm.
3.- Press the “CONFIGURATION” push-button for 5 seconds to save the changes and exit the configuration mode; the detector will make 5 short beeps.
Optionally, you can return the detector to its factory settings. To do so, press the “CONFIGURATION” push-button 5 times before step 3.
Pre-alarm jumper
Allows for Pre-alarm detection to be enabled / disabled. Before using this option, ensure that regulations allow for two alarm levels.
SET-HOLD mode
Prevents false alarms when charging or cleaning the chambers. While this mode is activated, pre-alarms will not signal and alarms will signal as pre-alarms when faced with all effects (sound, relay
activation and signalling). This mode will remain active for a maximum of 5 hours, then will deactivate automatically.
Maintenance mode
Disables gas pre-alarms and alarms for 1 hour for maintenance tasks. While this mode is activated, no gas pre-alarm or alarm will sound.
*Flashing: 0.5 s ON / 0.5 s ON / Flash: 0.1 s ON / 0.8 s OFF
Audible alarm
Alarm relay
Pre-Alarm
Alarm
Sensor error
CNC NO CNC NO CNC NO
Connection to alarm station
Alarm station
15V
In
Gnd
Input x
GAS
Independent operation
12 - 30 Vdc
Without
delay
ON
1 2
ON
1 2
180 s
Alarm levels
By
default
ON
1 2
ON
1 2
2nd set
of levels
Always disconnect the power supply to do the wiring.
The wiring between the detector/transmitter and the station should NEVER be installed in
a conduit together with power, control or supply cables.
Cables for wiring the relay contact should have an adequate section depending on the unit
to be connected.
Certain international standards maintain that the power supply of the alarm should
originate from a different circuit to that used by the refrigeration and ventilation system.
Please ensure that you comply with current local regulations.
Indicators
Wiring
Second alarm set is recommended for R-32 and R-1234YF refrigerants.
GASES DETECTED
R-32, R-454A, R-454C, R-455A, R-1234YF
DEFAULT LEVELS
SECOND SET OF LEVELS
PRE-ALARM
ALARM
PRE-ALARM
ALARM
1000 ppm
1500 ppm
2000 ppm
4000 ppm

Other AKO Gas Detector manuals

AKO AKO-57625-1 User manual

AKO

AKO AKO-57625-1 User manual

AKO AKO-575744NR User manual

AKO

AKO AKO-575744NR User manual

AKO AKO-57625 User manual

AKO

AKO AKO-57625 User manual

AKO AKO-52201 User manual

AKO

AKO AKO-52201 User manual

AKO AKOGAS AKO-576410 User manual

AKO

AKO AKOGAS AKO-576410 User manual

AKO AKO-5761 Series User manual

AKO

AKO AKO-5761 Series User manual

AKO 57624 User manual

AKO

AKO 57624 User manual

AKO 52201 User manual

AKO

AKO 52201 User manual

AKO AKO-522014 User manual

AKO

AKO AKO-522014 User manual

AKO AKO-575744NR User manual

AKO

AKO AKO-575744NR User manual

Popular Gas Detector manuals by other brands

PureAire Universal Gas Detector instruction manual

PureAire

PureAire Universal Gas Detector instruction manual

GEV FMG 1282 user manual

GEV

GEV FMG 1282 user manual

Medem AGDS-2 installation instructions

Medem

Medem AGDS-2 installation instructions

Honeywell 3000 MkIII Series Technical manual

Honeywell

Honeywell 3000 MkIII Series Technical manual

Dräger X-am 8000 Instructions for use

Dräger

Dräger X-am 8000 Instructions for use

LANDTEC SEM5000 user guide

LANDTEC

LANDTEC SEM5000 user guide

Emerson Rosemount 936 Reference manual

Emerson

Emerson Rosemount 936 Reference manual

RKI Instruments GX-3R Pro Operator's manual

RKI Instruments

RKI Instruments GX-3R Pro Operator's manual

Crowcon IRmax Installation, Operating and Maintenance Instruction

Crowcon

Crowcon IRmax Installation, Operating and Maintenance Instruction

Emerson MRLDS 450 user guide

Emerson

Emerson MRLDS 450 user guide

sauermann SGTP-CO quick start guide

sauermann

sauermann SGTP-CO quick start guide

Honeywell BW MaxXT II Quick reference guide

Honeywell

Honeywell BW MaxXT II Quick reference guide

FORENSICS DETECTORS FD-90E-RED Operation manual

FORENSICS DETECTORS

FORENSICS DETECTORS FD-90E-RED Operation manual

Joy-it SEN-MQ4 manual

Joy-it

Joy-it SEN-MQ4 manual

sewerin EX-TEC SR5 operating instructions

sewerin

sewerin EX-TEC SR5 operating instructions

Oldham OLCT 10N user manual

Oldham

Oldham OLCT 10N user manual

IMR EX610 user manual

IMR

IMR EX610 user manual

Detcon DM-700 Safety manual

Detcon

Detcon DM-700 Safety manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.