Rinnai ROF4500 User manual

This appliance shall be installed in accordance with:
• Manufacturer’s Installation Instructions
• Current AS/NZS 3000, AS/NZS 3500 & AS 5601
• Local Regulations and Municipal Building Codes
This appliance must be installed, serviced and removed by an Authorised Person.
All Rinnai gas products
are A.G.A. certied.
Distributed and serviced in Australia under a Quality
System certied as complying with ISO 9001 by SAI
Global
Luminaire® Outdoor Gas Fire
Operation / Installation Manual
Models: ROF4500, 4501,
4502, 4100, 4101, 4102
A luminous effect appliance. Not certified as a space heater.
FOR OUTDOOR USE ONLY - this appliance shall not be installed or used indoors

Rinnai Australia - ii - Rinnai Luminaire® Outdoor Gas Fire - Operation and Installation Manual
This appliance must be installed by an Authorised person. The installation of gas must conform to
local regulations.
The installation must also comply with the instructions supplied by Rinnai.
Your Rinnai Luminaire® Outdoor Gas Fire has been approved by the Australian Gas Association.
The A.G.A. Approval Number is shown on Data plate.
Please keep this instruction booklet in a safe place for future reference.
The Rinnai Luminaire® Outdoor Gas Fire does not need to be installed by a registered gas fitter if
connecting to a 9 kg LPG cylinder.
Ensure you read and understand the separate Warranty terms and conditions form
accompanying this appliance.
• Installations and connections for Universal LPG and NG connections must
be completed by a certified gas fitter when installed in reticulated system.
• Improper Installation, adjustment, alteration, service or maintenance can
cause property damage, personal injury or loss of life. For assistance or
additional information consult an authorised person.
• This appliance is for OUTDOOR use only. Refer to page 7 for details.
• DO NOT operate appliance indoors.
• DO NOT store or use petrol or other flammable vapours and liquids in the
vicinity of this Rinnai Luminaire® Outdoor Gas Fire.
• DO NOT operate in an unventilated area. Refer to page 7 for details.
• DO NOT obstruct the flow of air around this appliance whilst in use. Refer
to “Clearances and Location” section page 7.
• Certain materials or items when placed near the Rinnai Luminaire®
Outdoor Gas Fire may be affected by the radiant heat and could be
damaged.
Keep all items away from your Rinnai Luminaire® Outdoor Gas Fire. Refer
page 3 for details.
• Keep Rinnai Luminaire® Outdoor Gas Fire away from combustible
materials. Maintain the Clearances as shown on page 7 and page 14.
• DO NOT light unit or attempt to light this appliance with the stainless steel
Weather/Cover on.
• DO NOT place cover on while unit is operating.
• DO NOT use with any other gas than that stated on data label.
• NOT TO BE USED AS A COOKING APPLIANCE.
• NOT TO BE USED FOR ANY OTHER PURPOSE OTHER THAN A LUMINOUS
EFFECT GAS FIRE.
• DO NOT USE TO DRY CLOTHES.
• DO NOT USE SOLD FUELS, WOOD, HEAT BEADS ETC. ON THIS
APPLIANCE. ONLY USE BURNER MATERIAL SUPPLIED.
Please keep these instructions in a safe place for future reference
Please take a moment to complete the following information:
Your Retailer: ______________________________________________
Name: ______________________________________________
Address: ______________________________________________
Telephone No. ______________________________________________
Date of Purchase: ________ / ________ / _______________________
WARNING
REGULATORY INFORMATION
WARRANTY INFORMATION
WARNINGS

Rinnai Australia - iii - Rinnai Luminaire® Outdoor Gas Fire - Operation and Installation Manual
REGULATORY INFORMATION ..............................................................................................ii
WARNINGS ..............................................................................................................................ii
WARRANTY INFORMATION ...................................................................................................ii
CARTON CONTENTS ............................................................................................................ 1
ACCESSORIES CONTENTS .................................................................................................. 2
SAFETY INFORMATION ........................................................................................................ 3
CLEARANCES AND LOCATION ............................................................................................ 7
CUSTOMER INFORMATION - OPERATION ......................................................................... 8
ABNORMAL FLAME PATTERN ............................................................................................. 9
INSTALLERS INFORMATION - TROUBLESHOOTING ......................................................... 9
SERVICING ............................................................................................................................. 9
SPECIFICATIONS ................................................................................................................ 10
INSTALLATION APPLICATIONS .......................................................................................... 12
GAS CONNECTION .............................................................................................................. 13
APPLIANCE LOCATION ....................................................................................................... 14
KITSET INSTALLATION - NON COMBUSTIBLE FRAME .................................................... 15
KITSET INSTALLATION - COMBUSTIBLE FRAME ............................................................. 16
DOOR ASSEMBLY ............................................................................................................... 17
FASCIA INSTALLATION ....................................................................................................... 19
MASONRY INSTALLATION .................................................................................................. 21
FREESTANDING UNIT ......................................................................................................... 22
BURNER MATERIAL ............................................................................................................ 22
CHECKLIST .......................................................................................................................... 23
INSTALLERS / GAS FITTER DETAILS ................................................................................ 23
CONTACT INFORMATION ................................................................................................... 23
TABLE OF CONTENTS

Rinnai Australia - 1 - Rinnai Luminaire® Outdoor Gas Fire - Operation and Installation Manual
Burner Only
Burner Assembly x 1 Granite Cover x 2 & Granite Trim x 6 Pumice/Stones/Pebbles x 1 each
Stainless Steel Weather - Cover x 1 Instruction Manual/Warranty Sheet LP Hose & Regulator Assy x 1
One Sided Unit
Burner and Box Assembly x 1 Granite Cover x 2 & Granite Trim x 6 Pumice/Stones/Pebbles x 1 each
Fascia Trim Kit Components x 1 Instruction Manual/Warranty Sheet LP Hose & Regulator Assy x 1
Angle Brackets x 4 Lintel x 1 Stainless Steel Weather-Coverx1
Two Sided See-Through Unit
Burner and Box Assembly x 1 Granite Cover x 2 & Granite Trim x 6 Pumice/Stones/Pebbles x 1 each
Fascia Trim Kit Components x2 Instruction Manual/Warranty Sheet LP Hose & Regulator Assy x 1
Angle Brackets x 4 Lintel x 2 Stainless Steel Weather-Coverx1
Granite Trim x 6
Granite Cover x 2
Granite Trim x 6
Granite Cover x 2
M4 x 8 Pan head -
10pcs
M5 x 10 Pan head - 8pcs
Trim Bracket – 4pcs Left side Trim – 1pce
Bottom Trim – 1
p
ce
Top Trim – 1pce
Right side Trim – 1pce
Granite Trim x 6
Granite Cover x 2
M4 x 8 Pan head -
10pcs
M5 x 10 Pan head - 8pcs
Trim Bracket – 4pcs Left side Trim – 1pce
Bottom Trim – 1
p
ce
Top Trim – 1pce
Right side Trim – 1pce
CARTON CONTENTS

Rinnai Australia - 2 - Rinnai Luminaire® Outdoor Gas Fire - Operation and Installation Manual
Accessories
Glass Door Kit:
M4 x 8 - 4 pieces
M5 x 10 - 2 pieces
Fascia Trim Kit Components x 1
Universal LPG - NG Gas Conversion Kit
M4 x 8 Pan head -
10pcs
M5 x 10 Pan head - 8pcs
Trim Bracket – 4pcs Left side Trim – 1pce
Bottom Trim – 1
p
ce
Top Trim – 1pce
Right side Trim – 1pce
ACCESSORIES CONTENTS

Rinnai Australia - 3 - Rinnai Luminaire® Outdoor Gas Fire - Operation and Installation Manual
Clothing or other flammable materials should not
be hung from the appliance, or be placed on or
near the appliance.
Children and adults should be alerted to the
hazards of high surface temperatures, burns and
clothing ignition.
Do no allow anyone to sit or lean against the
appliance.
Young children and the infirm should be
supervised at all times when they are in the area of
the appliance.
Do not spray aerosols in the vicinity of this
appliance while it is in operation. Most contain
inflammable contents or an inflammable propellant
which may ignite creating a dangerous situation.
Do not use or store flammable materials near this
appliance.
Keep unit away from combustible materials.
Combustible materials must not be placed where
the unit could ignite them.
Appliance must be secured into a permanent
fixture.
Solid fuels shall not be burned in this Rinnai
Luminaire Outdoor Gas Fire.
Ensure no leaves, cobwebs or any other foreign
debris is on the burner material prior to lighting.
People, other organisms, materials or objects that
are near this appliance when it is in operation may
be subjected to prolonged exposure to radiant
heat. Personal injury or material damage may
occur.
Do not operate this appliance with the stainless
steel weather cover on.
SAFETY INFORMATION

Rinnai Australia - 4 - Rinnai Luminaire® Outdoor Gas Fire - Operation and Installation Manual
General Safety Information
Before Installation
Check that the Rinnai Luminaire Outdoor Gas Fire supplied is correct for the gas type being used. The
gas type is clearly labelled on the appliance. Dataplate is located under left hand stone cover.
Appliance is labelled “Universal LPG”, or “Natural Gas”. Label is located under right hand stone cover.
If the appliance is “Universal LPG” it is normally used with a 9 kg gas cylinder. However, it is possible
to install appliance on a reticulated “Universal LPG” supply. ie. 45 Kg. cylinder domestic supply.
Pipe sizing for reticulated Natural or Universal LPG gas supplies must be in accordance with an
approved sizing chart such as the one in AS 5601.
Natural Gas:
1. Must be connected to the reticulated supply either by hard plumbing or the use of an
approved hose.
2. Must be installed with the pressure regulator supplied for Natural Gas.
3. Connection to the reticulated gas supply must incorporate an isolation valve.
4. The isolation valve must be closed when the Rinnai Luminaire Outdoor Gas Fire is not in use.
• Failure to comply with these Instructions could result in a fire or explosion
which could cause serious injury, death or property damage.
• This appliance must be installed and commissioned by an authorised person
only.
• This is a permanently fixed luminous effect appliance for outdoor areas only.
Not to be used for cooking, food preparation or food warming.
If you smell gas:
1. Shut off gas to the appliance, at its source if possible.
2. Extinguish any open flame.
3. Perform gas leak check procedure.
4. If odour continues, immediately call Rinnai service person refer page 23.
• Never connect the appliance directly to the gas cylinder / reticulated gas supply
without a Regulator.
• Always use the hose and regulator supplied (Universal LPG models only).
• Never store your gas cylinder indoors. Gas cylinders must be stored outdoors
in a well ventilated area out of reach of children or the infirm.
• DO NOT test for gas leaks with an open flame.
• DO NOT allow children or the infirm to operate or handle any parts of the
appliance.
• Ensure all PVC plastic coating material is removed before operating unit.
WARNING
WARNING
WARNING
WARNING
SAFETY INFORMATION CONTINUED

Rinnai Australia - 5 - Rinnai Luminaire® Outdoor Gas Fire - Operation and Installation Manual
Hose and Regulator (used with gas cylinder):
1. Where applicable a pressure hose and regulator assembly supplied with the Rinnai
Luminaire Outdoor Gas Fire are suitable for use on bottled LP gas only.
2. The pressure regulator and hose assembly supplied with the appliance MUST be used.
3. Replacement pressure regulators and hose assemblies must be those specified by Rinnai for use
with this appliance.
4. The pressure regulator supplied has been fixed to have an outlet pressure of 2.75 kPa.
A different pressure is not suitable.
5. Propane or universal LP gas cylinders must be installed and positioned to conform with
AS 5601, Appendix J - “LP Gas Cylinders”.
6. When the appliance is not in use, the hose and regulator must only be disconnected from the
cylinder. The hose and regulator must not be disconnected from the unit unless it is being
replaced. Such replacement must only be carried out by an authorised person.
7. Inspect the gas hose when replacing the gas cylinder, or once per year, whichever is more
frequent. If the hose is cracked, cut, abraded, discoloured or damaged in any other way, the Rinnai
Luminaire Outdoor Gas Fire must not be used. The hose must be replaced if damaged or when
local regulations require this. Contact your supplier or local regulating authority if uncertain. Such
replacement must only be carried out by an authorised person.
Gas Cylinder
1. This Rinnai Luminaire Outdoor Gas Fire is designed for use with a 9 kg LP Gas cylinder.
This cylinder should conform to AS 2030.1 - 1999.
2. The Rinnai Luminaire Outdoor Gas Fire is designed for use in the vapour withdrawal mode.
Therefore it is important to always store and use the gas cylinder in an upright position.
3. For storage and when refilling / exchanging cylinders, disconnect the hose and regulator at the
cylinder end only. DO NOT disconnect the hose and regulator from the appliance end.
4. The gas cylinder should be refilled by a reputable gas dealer, or exchanged at a reputable gas
cylinder exchange outlet. Gas cylinders should be inspected and re-qualified periodically in
accordance with local statutory regulations. A dented or rusty gas cylinder may be hazardous and
should not be used.
5. DO NOT subject the gas cylinder to excessive heat.
6. Always close the cylinder valve when this unit is not in use.
7. Gas cylinders must be stored outdoors in a well ventilated area out of reach of children and must
not be stored in a building, garage or any other enclosed area.
8. When in use Gas Cylinders must be installed and positioned to conform with AS 5601 Appendix J -
“LP Gas Cylinders”.
SAFETY INFORMATION

Rinnai Australia - 6 - Rinnai Luminaire® Outdoor Gas Fire - Operation and Installation Manual
Gas Installation Using a Gas Cylinder
Step 1. Read and understand the information in
this manual, in particular the items under
"Safety Information".
Step 2. Ensure the control knob is in the "OFF"
position as shown.
Step 3. Connect the regulator to the gas cylinder
by turning the coupling nut anti-clockwise
to tighten to a full stop (left hand thread).
The seal has now engaged. An additional
one half to three quarter turn is required to
complete the connection. If your regulator
has a plastic type hand wheel DO NOT
use tools. Tighten by hand only.
Use a spanner on brass hexagon type
nuts, DO NOT over tighten.
Step 4. Make a soapy solution by mixing one part
liquid detergent (such as dish-washing
liquid) and four parts water.
Step 5. Open the gas valve on the cylinder by
turning it anticlockwise.
Step 6. Apply the soapy solution to all visible gas
connections in the vicinity of the cylinder
and regulator. Gas leaks will show as
small bubbles gradually increasing in size
in the soapy solution.
Step 7. If there is a gas leak from the connection
between the regulator and gas cylinder,
close the gas valve on the cylinder by
turning it clockwise. Disconnect the
regulator and hose assembly from the
cylinder by turning the coupling nut
clockwise to disengage. Inspect for debris
inside the cylinder fitting and the fitting at
the end of the regulator. Remove debris
and reconnect as per step 3). Retest for
gas leaks.
Step 8. Removal of the gas hose, regulator and
cylinder is the reverse of the connection
procedure.
If there is still a gas leak from the connection between the regulator and gas
cylinder or any other connections contact your gas supplier or Rinnai for
assistance. Connections other than the connection between the regulator
and gas cylinder must only be altered by an authorised person.
If gas leaks are present DO NOT operate the Rinnai Luminaire® Outdoor Gas
Fire.
OFF
ON OFF
CAUTION
SAFETY INFORMATION

Rinnai Australia - 7 - Rinnai Luminaire® Outdoor Gas Fire - Operation and Installation Manual
Clearances
The following minimum clearances from combustible materials must be maintained:
• Top: 1000 mm - measured from top of cover in the closed position.
• Rear: 1000 mm - measured from the rear main panel.
• Sides: 300 mm - measured from the side main panel.
• Openings around the base of the appliance provide air for cooling and combustion and must not be
obstructed.
Location
‘Outdoor Use’ is defined as use in an above ground, open air situation with natural ventilation, without
stagnant areas and where gas leakage and products of combustion are rapidly dispersed by wind and
natural convection.
The following figures are diagrammatic representations of ‘Outdoor Use’ as defined:
An enclosure with walls on all sides, but
with at least one permanent opening at
ground level and no overhead cover.
Within a partial enclosure that includes an
overhead cover and no more than 2 walls.
Within a partial enclosure that includes an
overhead cover and more than 2 walls the
following shall apply:
• At least 25% of the total wall area is
completely open and
• At least 30% of the remaining wall area
is open and unrestricted.
In the case of balconies at least 20% of
the total wall area shall be and remain
open and unrestricted.
CLEARANCES AND LOCATION

Rinnai Australia - 8 - Rinnai Luminaire® Outdoor Gas Fire - Operation and Installation Manual
The Rinnai Luminaire Outdoor Gas Fire is easy to operate via the use of the control knob on the front
of the Fire.
All Rinnai appliances meet or exceed the safety Australian standards required for gas regulations.
Your Rinnai Luminaire Outdoor Gas Fire has the following safety devices:
• Burner lights with a low gas rate (lights to pilot).
• Flame failure device, if the gas is on and there is no flame the gas is automatically shut off.
Before starting the appliance
When starting the appliance for the first time ensure all packing and packaging materials has been
removed. This includes protective pvc coating to stainless steel and foam protection.
Before starting ensure that debris such as leaves or other objects are cleared from the unit, doors are
open, cover removed and the gas is turned on.
Operating the appliance
Step 1. Press the control knob
and S-L-O-W-L-Y turn
counterclockwise until
you hear a click. This
step is ‘lighting to pilot’
and you are looking for
the pilot flame in the
pilot flame housing.
At this point the pilot
light should be
visible continue to
hold the knob down.
Step 2. Keep holding down for a further 5 seconds to active the flame and then release. Steps 1 &
2 may need repeated several times to ignition the Fire. If main burner has not ignited within
5 attempts see troubleshooting section refer to page 9.
Step 3. Once the appliance is on it is best to run on a high setting for a period of time in order to
establish a flame pattern and allow the unit to heat up, approximately 30 minutes. You can
adjust the flame by selecting between the high and low settings.
Step 4. To turn off press the control knob and turn clockwise to the ‘OFF’ position. When shutting
down your Rinnai Luminaire Outdoor Gas Fire it is important you replace the cover once
the Unit has cooled down.
Step 5. If using ULPG gas cylinder ensure you turn ‘OFF’ at the isolator valve at the cylinder.
.
• Outdoor Fires are not fully weatherproof and should NOT be directly exposed to
the rain. A stainless steel cover has been provided with the unit to protect the
burner and burner material when not in use.
• Remember to remove the cover before starting this appliance. It is
recommended when positioning the appliance, that it is in a location that is
protected/covered to prevent full exposure to the rain.
.
• REMOVE THE WEATHER COVER BEFORE LIGHTING.
• DO NOT OPERATE APPLIANCE WITH THE COVER ON.
Pilot
(turn slowly to this position
unit you hear a “click”)
OFF position
Pilot
OFF
High
Setting
Low
Setting
CAUTION
WARNING
CUSTOMER INFORMATION - OPERATION

Rinnai Australia - 9 - Rinnai Luminaire® Outdoor Gas Fire - Operation and Installation Manual
ABNORMAL FLAME PATTERN
Rinnai Luminaire Outdoor Gas Fire has a distinct flame pattern. This should look the same every time
you start your Fire, after an initial warm up period of approximately 30 minutes.
Abnormal flame performance and flame pattern can indicate a problem with your appliance, such as
blocked gas injectors or burner material has shifted from when the unit was first installed. There are
some warning signs that could indicate a problem.
• Unusual smell from the appliance.
• Continued difficulty or delay in establishing a flame.
• Flame appears either very short or very long.
• Flame only burns part way across the burner.
• Soot building up on the inside of the glass door or burner material.
• If any of the above signs occur, please contact Rinnai.
Symptom Causes Solution
Unit will not light
• No Gas • Check that the gas is turned on
• Check cylinder is not empty
• Air in gas pipe • Repeat lighting sequence five times until gas
has replaced air in hose or pipe.
• Incorrect gas type • Ensure gas type is correct for appliance.
• Faulty control valve • Contact Rinnai see details page 23.
• No Spark
Minor popping sound
during ignition
• Unburnt gas coming through
pumice/stones igniting
• No action, normal operation.
Major popping sound
during ignition or during
operation
• Incorrect gas type • Check gas type is correct for appliance.
• Damaged burner • Contact Rinnai see details page 23.
• Blocked burner • Inspect and clean burner ports
• Unbalanced burner material • Inspect burner material refer to page 22 for
correct positioning.
• Incorrect gas pressure • Check gas pressure is correct for appliance.
Burner does not
immediately stop burning
when unit is turned off
• Reside of gas in pumice
continues to burn
• No action, normal operation
Normal Abnormal
.
To keep your Rinnai Luminaire Outdoor fire performing in top condition. Rinnai recommends that you
To keep your Rinnai Luminaire Outdoor fire performing in top condition. Rinnai recommends that you
have it serviced every 2 years by a qualified service person.
Regular servicing is not covered by the Rinnai warranty.
Do not attempt to carry out any service work other than that mentioned in the troubleshooting section
If you have any other faults or problems, please refer to your installer or contact Rinnai.
INSTALLERS INFORMATION - TROUBLESHOOTING
SERVICING

Rinnai Australia - 10 - Rinnai Luminaire® Outdoor Gas Fire - Operation and Installation Manual
Open Fronted Radiant / Convector Rinnai Luminaire Outdoor Gas Fire
with manual control.
Comes in 3 designs:
• Freestanding table top unit
• Open One sided cabinet (with optional glass bi-fold doors)
• Open Two sided see-through unit (with optional glass bi-fold doors)
Gas Type: Universal LPG / NG
Suitability: This is a permanently fixed luminous effect appliance
outdoor areas only. Not to be used for cooking food preparation or food
warming.
Burner 304 stainless steel tube burner
Combustion Method Aerated bunsen type burner
Data Plate Left hand side of burner under granite cover
Gas Control
Gas control valve consisting of an inlet connection, Piezo ignitor, thermocouple flame
failure and manual control knob.
The valve operating sequence is to turn the valve to the pilot position before lighting
the main burner. Only, when the pilot has established can the gas valve be turned to
high and low combustion settings.
Gas Connection (ULPG) 9 kg ULPG Cylinder: Quick Disconnect (QDC)
‘Rectus Type 21’
NG: 5/8” UNF flared connection to
NG Regulator
Ignition System Intermittent pilot
Input ULPG: 45-25 MJ/h (High to Low) NG: 41-22 MJ/h (High to Low)
Pilot
SIT®single injector pilot assembly with fixed aeration and replaceable fixed pilot
injector for NG and ULPG. Pilot assembly also contains a pilot ignition electrode and
thermocouple for flame failure.
Internal Piping
Burner is supplied through an aluminium pipe from the gas control to the burner
injector block. Pilot burner is supplied gas via aluminium pipe directly from the gas
control.
Pressure Test Point Incorporated into main burner injector block measuring burner pressure
Regulator Pressure regulator with exchangeable spring for NG
Safety Devices Light to Pilot and Flame Failure Safety Device (FFD)
Flue Gas Outlet Top Louvre discharge (Cabinet models only)
Weight Burner Assembly: 20 kg Body Assembly: 30 kg (Burner + Body: 50 kg)
ULPG NG
Pilot Injector # 35 # 62
Main Injector 1.90 mm 3.60 mm
Test Point Pressure (High) 2.45 kPa 0.43 kPa
Test Point Pressure (Low) 0.80 kPa 0.13 kPa
Minimum Supply Pressure 2.50 kPa 1.13 kPa
Maximum Supply Pressure 3.50 kPa 3.50 kPa
Include Dimensions
With Fascia & Doors - mm
(fascia add 40 mm)
SPECIFICATIONS

Rinnai Australia - 11 - Rinnai Luminaire® Outdoor Gas Fire - Operation and Installation Manual
Burner Assembly
The major component of the Rinnai
Luminaire Outdoor Gas Fire is the
burner assembly. This consists of a
tube burner mounted in an open tray
filled with pumice and stones/pebbles.
A SIT®pilot burner is positioned along
the tube burner to ensure positive
lighting and is covered by a perforated
guard to prevent the pumice from
blocking the burner.
The gas control, pressure regulator and spark igniton system is positioned at the right end of the tube
burner.
The complete assembly is housed within a stainless steel body incorporating a removable cover.
The cover is placed over the burner for protection from wind and rain when the unit is not in use.
DO NOT attempt to light the appliance when the cover is in place.
DO NOT place the cover on the appliance when the flame is on.
Body Assembly - (Open One Sided Cabinet)
The outer body assembly is optional and must be used
if installing into a non combustible enclosure. It consists
of a 5-sided construction with an open front (pictured) or
open front and back. If a body assembly is ordered, this
comes assembled complete with burner assembly
inside.
Enclosure must be constructed of masonry or non-
combustible material.
Body Assembly with Glass Bi-Fold Doors
The body assembly has optional tempered glass double
bi-fold doors to reduce the affect of wind and rain on the
burner. The appliance can operate with the doors open
or closed.
The unit is able to operate with the bi-fold doors closed.
Air being induced into the combustion chamber through
the lower half of the open front and expelled out the top
or through the top louvres on the glass door.
Closing the bi fold doors does not affect the operation of
the appliance. Adequate ventilation is supplied via the
louvres and gaps at the side and top of the unit.
SPECIFICATIONS CONTINUED

Rinnai Australia - 12 - Rinnai Luminaire® Outdoor Gas Fire - Operation and Installation Manual
The Rinnai Luminaire Outdoor Gas Fire is designed and required to be built into a permanent fixture.
The table below details the available installations options, components needed and optional
accessories.
Installation Components Needed Optional Accessories
Freestanding Unit • Burner Assembly Universal LPG • NG Conversion Kit
Open One Sided Unit • One Sided Assembly • Glass Bi-Fold Doors
• NG Conversion Kit
Open Two Sided See-Through Unit • Burner Assembly Universal LPG • Glass Bi-fold Doors
• NG Conversion Kit
Non-combustible enclosed masonry, open
one or two sides
• Burner Assembly Universal LPG • NG Conversion Kit
Comes complete with burner assembly
INSTALLATION APPLICATIONS

Rinnai Australia - 13 - Rinnai Luminaire® Outdoor Gas Fire - Operation and Installation Manual
Connecting a 9 kg LPG Cylinder
A Quick Disconnect (QDC) gas connection is provided with the hose and regulator.
Step 1. Place the gas cylinder onto a supporting base.
Step 2. Fasten regulator and hose assembly to cylinder valve outlet. Tighten firmly. When
connecting the hose and regulator assembly to the gas cylinder, take care to avoid
unnecessary twisting of the flexible hose. DO NOT over tighten connection.
Step 3. Open the gas cylinder valve one full turn to allow the gas to flow.
Step 4. Leak test all accessible connections thoroughly using a soapy water solution (1 part liquid
detergent and 4 parts water) prior to using the appliance. Bubbles will appear if connections
are not properly sealed. Tighten or rectify as necessary and retest.
Step 5. Refer to page 6 for full instructions.
Fixed Universal LPG and NG Connections
Fixed Universal LPG
connection
A 3/8” BSP fixed connection is also supplied with this unit.
This connection is for installations connected to a permanent fixed
Universal LPG connection (that supplies gas to other appliances in the
premises).
Natural Gas In order to connect to NG a conversion kit is required. This can be
purchased as an accessory item available from Rinnai.
Installation and connections for fixed NG and Universal LPG connections
must be completed by a certified gas fitter.
The Stainless Steel flexi pipe is to be drawn through the base of the unit.
Ensure it is bent evenly and not kinked. See “Gas positioning diagram” on
page 21 for dimensions and positioning of the gas line opening.
WARNING
CAUTION
GAS CONNECTION

Rinnai Australia - 14 - Rinnai Luminaire® Outdoor Gas Fire - Operation and Installation Manual
The Rinnai Luminaire Outdoor Gas Fire must be installed as a permanent fixture in an outdoor area.
Determining and consideration of the position for the Rinnai Luminaire Gas Outdoor Fire will be
dependent on the configuration of the unit purchased. Additional considerations such as protection
from direct rain, wind and sea spray, openable windows, debris from trees as well as location to
neighbouring properties also needs to be considered, gas supply and clearances from combustibles
will influence where you can position this appliance.
Location will also be depended on the type of unit purchased and if being installed into a combustible
cavity.
General Clearances
Inbuilt Freestanding
Minimum of 2 x 200 cm2 ventilation slots to be incorporated into the structure.
One at the top of the storage area and one at the base.
Structure Clearances Required Additional Detail
Below eaves,
balconies or other
projections (A)
1000 mm minimum
If the projection is a shade cloth or material awning
then this is deemed as a combustible material and
the recommended clearance is 1500 mm.
From the ground or
other surface (E)
Inbuilt - 100 mm minimum
Freestanding - 900 mm minimum Ground level to bottom of fireplace.
Walls (D) 500 mm Side of unit to side wall.
Gas Meters 1000 mm
Drain of Soil Pipe 150 mm
Openable Windows
and doors 1000 mm
From an openable window, door or non mechanical
air inlet, or any other opening into a building with the
exception of sub-floor ventilation.
Mechanical Air Inlet 2000 mm For example: air conditioning unit.
Mantles (B) and (C) 500 mm / 300 mm
Minimum vertical clearance of 500 mm with a
maximum mantle depth of 300 mm. If mantle depth
is more than 300 mm you will need 1000 mm of
vertical clearance.
1 m safe distance Fixed objects such as outdoor furniture, umbrellas and plants should be at least 1 m away
from the unit when it is in operation.
Installation specific
clearances
Additional clearances also need to be observed for specific installation applications, these
are detailed on the following pages.
Ensure clearing for
servicing
Ensure enough room is maintained for servicing, cleaning and general access to the
appliance.
Ventilation of structure
When using a 9 kg gas cylinder a minimum of 2 x 200 cm2ventilation slots must be used
(1 x top and 1 x bottom = 400 cm2total) to ensure safe ventilation of all structures housing
cylinders.
Mantel
A
B
C
D
Roof or Overhang
Additional structure or sidewall
E - min. 100mm
300mm
1m
1m
1m
E= 900mm Min.
600mm
Max.
1280mm Max.
100mm
300mm
100mm
APPLIANCE LOCATION

Rinnai Australia - 15 - Rinnai Luminaire® Outdoor Gas Fire - Operation and Installation Manual
Steel framing options are available for the one sided and two sided see-through units. For ease of
installation Rinnai provide the durable steel frame as a kitset.
Prepare framing dimensions
Construct framing to specific installation dimensions shown.
To enhance the durability of the framing we suggest the frame is mounted on a paved slab 250 mm
(above unpaved ground) and 150 mm (above paved ground). We also recommend having a 25 mm
air gap to stop LPG from pooling and to allow moisture to drain easily from the enclosure.
The minimum clearances to combustible framing materials are:
For the Open See-Through Cabinet you will need to observe these clearances on both faces.
Non-combustible cladding and frame materials are required when dimension
B = 1180 mm.
Install body/burner assembly into frame
When purchasing a cabinet option the body and
burner come pre-assembled. simply unpack, fit and
secure assembly into the frame using bottom fascia
brackets.
For the see-through unit you will need to ensure the
control knob is facing the correct way for easy
operation.
Drill hole in bottom bracket and fit screw to secure
assembly.
Above Side Below Behind
500 mm 25 mm 0 mm 30 mm (One sided cabinet)
Non Combustible Combustible
A = 555 mm
B = 1180 mm*
C (two sided) = 470 mm**
C (one sided) = 500 mm**
D = 500 mm ***
A = 555 mm
B = 1225 mm*
C (two sided) = 470 mm**
C (one sided) = 500 mm**
D = 500 mm ***
* Includes 25 mm side clearances
** Includes cladding (for one sided unit 500 mm
dimension measures front cladding only)
*** If due to design this dimension required to be less
than 500 mm, you will need an additional steel lintel.
This can be ordered as a spare part from Rinnai.
slab used to elevate enclosure above ground to
enhance durability of framing
25 mm air gap to stop LPG pooling at base and
also to allow moisture to drain easily
A
B
D
C
metal lintel
cladding
KITSET INSTALLATION - NON COMBUSTIBLE FRAME

Rinnai Australia - 16 - Rinnai Luminaire® Outdoor Gas Fire - Operation and Installation Manual
Attach metal lintel and angled clearance brackets
Luminaire Outdoor Fire cabinet options are supplied with a metal lintel and angled clearance brackets.
These are required for installations where combustible framing is used.
• Metal lintels Open One-Sided Cabinet (1), Open See-Through Cabinet (2)
• Angled clearance brackets Open One-sided Cabinet (4), Open See-Through Cabinet (4)
Metal lintel
Designed to sit about the unit and replace combustible framing in areas exposed to high
temperatures. The minimum distance above the unit to a combustible frame is 500 mm.
To fit
Step 1. Take out and undo four fastenening screws at
either end.
Step 2. Flip side sections 180° and loosely refit
screws.
Step 3. Adjust to desired length before tightening.
Angled clearance brackets
Designed to ensure combustible framing is greater than 25 mm from the sides of the unit as shown.
Top View - Open One-Sided Cabinet
Top View - Open See-Through Cabinet
side sections need to be rotated 180°
and secured into framing above unit.
1225 mm (min)
cabinet non combustible
cladding
clearance bracket
timber stud
1180 mm (min)
1195 mm (max)
min 500mm
1225 mm (min)
cabinet
non combustible cladding
clearance
bracket
timber stud
1180 mm (min)
1195 mm (max)
470mm
KITSET INSTALLATION - COMBUSTIBLE FRAME

Rinnai Australia - 17 - Rinnai Luminaire® Outdoor Gas Fire - Operation and Installation Manual
Door Assembly Installation Instructions
The assembly is comprised of tempered glass double bi-fold doors with stainless steel surrounds and
fixings. This offers wind protection when the unit is on and when not in use protection from wind, rain
and nesting animals.
The assembly fixed to the cabinet frame of the Rinnai Luminaire Outdoor Fire, so is only suitable for
installations where a cabinet (also called a body assembly) has been installed.
The unit can operate with the doors open or closed, however for best radiant heat the doors should
be open during operation.
Suitable for Non Combustible cladding and frame materials.
Rinnai accepts no responsibility for deterioration of cladding or finishes.
Cabinet installation - door assembly is suitable
Only has a burner assembly installed - door assembly IS NOT suitable.
If the doors are closed during operation DO NOT touch the glass.
The glass can reach very high temperatures and cause severe burns.
Young children should be supervised at all times when the unit is in
operation.
WARNING
DOOR ASSEMBLY
This manual suits for next models
5
Table of contents
Other Rinnai Outdoor Fireplace manuals
Popular Outdoor Fireplace manuals by other brands

The Fireplace
The Fireplace JETMASTER 700 D installation instructions

Superior
Superior VRE4543EN Installation and operation instructions

Napoleon
Napoleon PATIOFLAME GPFN Installation and operation instructions

Endless Summer
Endless Summer Dakota GAD19101ES owner's manual

Vermont Castings
Vermont Castings ODGSR36A Homeowner's installation and operating manual

FEUERHAND
FEUERHAND PYRON user manual