
4
The following instructions are designed for the user of the water heater. The user may not
install or adjust the appliance in any way that requires the removal of the front of the unit. To
remove the front cover of the unit you must be certified competent to do so. Information for
the Installer is given on page 19.
All work done on this appliance must be done by a qualified gas engineer. A qualified
gas engineer must carry an up to date CORGI Registered Gas Installer picture
identification card while working on gas appliances. If you are unsure do not be afraid
to ask the engineer to show you the card. If you are still not satisfied call CORGI on
0870 401 2300 and verify the engineers name with their database. This is for your own
safety.
Responsibilities of the USER
The user must abide by all warnings given in this book. The user must only reference the
user section of the book, and may not carry out any procedure listed in the installer section.
The user must have the unit checked and maintained annually by a gas engineer.
The user must periodically check the water filter on the inlet to the appliance.
The user must not use the appliance in any way that it was not meant to be used. The user
may only use the heater as detailed in the User portion of this manual.
Interference with a sealed component is not permitted.
In case of defect parts only use genuine Rinnai components for replacement.
Conversion to other gas types should only be carried out by a qualified installer or a gas
distributor according to the practice in the country where the unit is installed.
The user must not store or use any flammable vapours or liquids in the vicinity of this or any
other appliance.
The user should familiarise themselves with the water heaters gas service valve and the
main gas valve to the premises.
Attention: air surrounding the water heater, venting and vent termination(s) is used for combustion
and must be free of any compounds that cause corrosion of internal components. These include
corrosive compounds that are found in aerosol sprays, detergents, bleaches, cleaning solvents, oil
based paints/ varnishes, and refrigerants. Therefore Rinnai recommends outdoor models be used for
these locations where possible.
The water heater, venting and vent termination(s) should not be installed in any areas where the air
may contain these corrosive compounds. If it is necessary for a water heater to be located in areas
which may contain corrosive compounds, Rinnai strongly recommends the following:
Indoor/Internal Water Heaters:
* DO NOT install in areas where contaminated air is present
* Consider before installation where air has the ability to travel within the building
* Where possible, install the water heater in a sealed closet so that it is free of contaminated indoor air
* Chemicals that are corrosive in nature should not be stored or used near the water heater
Outdoor/External Water Heaters and Vent Terminations of Indoor/Internal Water Heaters:
* Install as far away as possible from exhaust vent hoods
* Install as far away as possible from air inlet vents. Corrosive fumes may be released through these
vents when air is not being brought in through them.
* Chemicals that are corrosive in nature should not be stored or used near the water heater or vent
termination.
Damage and repair due to corrosive compounds in the air is not covered by warranty.
IF YOU SMELL GAS
Isolate the gas supply and get out of the building. Do not try to light any appliance. Do
not turn any light or other electrical switch on or off. Do not use any telephone in the
building. Call your gas engineer from a safe location and follow their instructions.
If you cannot reach your gas engineer ring the following: National Grid 0800 111 999
USERS INSTRUCTIONS