Rivacold RIVC000001 Manual

Mod: AN203T-2F
Production code: FAL016G012-DI
06/2022

RIVC000001 REV. 00 11/10/10
UK
RIVC000001
USE AND MAINTENANCE HANDBOOK

RIVC000001 Pag. 10 REV. 00 11/10/10
UK
ENGLISH
7STARTING THE MACHINE
Before starting the Blocksystem, make sure of the following:
•All locking screws are correctly tightened
•All electrical connections have been made correctly.
•The coldroom door is closed so that the door microswitch contact is closed.
7. 1
Control panel description
Green “COMPRESSOR” LED
OFF: The compressor is off
LIT: The compressor is operating.
BLINKING: The switch on request is pending (delays or protective devices activated)
Green “FANS” LED
OFF: The fans are off
LIT: The fans are operating
BLINKING: The switch on request is pending (delays or protective devices activated)
Green “DEFROSTING” LED
OFF: Defrosting is not activated
LIT: Defrosting is in progress
BLINKING: Manual defrosting is in progress; a defrosting request is pending (delays or protective
devices activated); network synchronised (master/slave) defrosting
Yellow “ALARM LED”
OFF: No alarm is in progress
LIT: A serious alarm is in progress (and alarm relay activated)
BLINKING: A non-serious alarm is in progress or a serious alarm has been silenced (alarm relay
deactivated)
“SETPOINT” key + “SETPOINT/REDUCED SET” green LED
LIT: The setpoint is displayed
BLINKING: The reduced set is activated
ENTER” key: This is used to set the setpoint, to access the programming menu, and to view the
machine status (if held down for 1 second); to enter the programming mode, this key must be held
down for 5 seconds.
“UP” key: This is used to command manual defrosting (if held down for more than 5 seconds) as well
as to increase the value of the parameter being displayed and to scroll forwards through the menu list.
“ON/OFF” key: This is used as a manual on-off control, to confirm a parameter value and it also
allows you to return to the previous menu. To switch the machine on or off, hold this key down for
more than 5 seconds.
“DOWN” key: This is used to command the lights manually (if held down for 1 second); it also
decreases the value of the parameter being displayed and scrolls back through the menu list.
set
on
off
set
on
off

RIVC000001 Pag. 11 REV. 00 11/10/10
UK
7. 2
Switching on/off
When the machine is energised, the display will read OFF and show the coldroom temperature
alternately. To switch the Blocksystem on (off), hold down the “ON/OFF” key on the front of the machine
for more than 5 seconds.
7. 3 Coldroom temperature adjustment
The temperature ranges within which the Blocksystem can operate are as follows:
Minimum Maximum
High Temperature (HBP) +2 +10
Medium Temperature
(MBP)
-5 +5
Low Temperature (LBP) -25 -15
The temperature adjustment setpoint can be accessed directly for display or adjustment purposes.
•Press and release SETPOINT: the display will read “SEt” (the procedure is slightly different if there
are alarms in progress; see the machine status display paragraph)
•Press SETPOINT: the green SET LED will switch on and the Setpoint value will be displayed
•Press UP or DOWN to set the new value
•Press SETPOINT or ON/OFF (or wait for the 5-second timeout) to confirm the value (the SET LED
will switch off and the display will read “SEt”)
•Press ON/OFF (or wait for the 5-second timeout) to return to the normal display mode
7. 4 How to vary parameters
Blocksystem operation is governed by parameters that have been stored in the memory of the electronic
control unit by the manufacturer (see the parameters table). These factory settings should not be varied
unless strictly necessary, and in all cases such operations are only to be carried out by qualified staff.
Parameters are not only divided by function, they are also divided according to their security/accessibility
levels:
Level 0 Setpoint parameters direct access (see paragraph 7.3)
Level 1 frequently used parameters access without password (see paragraph 7.5)
Level 2 configuration parameters access with password (see paragraph 7.7)
Parameters can be varied as follows:
From the keyboard
Via LAN network (Master/Slave)
Via Supervision network
7. 5 How to vary level 1 parameters
Hold down SET for 5 seconds until the display reads “reg” (adjustment parameters)
Press UP or DOWN until the required menu appears on the display
Press SET to access the menu; the code number for the first parameter in the selected menu will
appear
Press UP or DOWN until the required parameter appears
Press SET to view the value of the parameter
Press UP or DOWN to set the required value
Press SET to confirm the value and return to the parameters list; press ON/OFF to confirm the
value and return to the menu list
Press ON/OFF to pass from the parameters list to the menu list
Press ON/OFF again to exit the editing procedure,
If no key is pressed for more than 15 seconds, any value shown on the display will be stored in the
memory for the relevant parameter and there will be a forced exit from the parameters variation
procedure.
7. 6 Machine status display
Press and release SET: the display will read “SEt” or “AAL” if there are any alarms in progress
Press UP or DOWN until the required status is displayed
AAL alarms in progress (if present)
SEt setpoint

RIVC000001 Pag. 12 REV. 00 11/10/10
UK
Pb1 coldroom temperature probe value
Pb2 evaporator temperature probe value
Pb3 probe 3 value (if present)
Out relay outputs status
InP digital inputs status
Press SET to view the value
For alarm status, output status or input status, press UP or DOWN to scroll through the alarms in
progress, the outputs or the inputs,
Press SET or ON/OFF (or wait for the 5-second timeout) to return to the status list
Press ON/OFF (or wait for the 5-second timeout) to return to the normal display mode
.
Code Level Descr. Range Unit
List of -PPS passwords
PPA Parameters access password
Entering a pre-set password will give access to protected parameters
0 … 255
List of -rEG adjustment parameters
SEt 0 Setpoint LSE …HSE °C [°F]
diF 1 Differential
temperature > setpoint + diff. -> adjustment On
temperature ≤setpoint -> adjustment Off
0.1 … 50.0 °C [°F]
List of -Pro probe parameters
CA1 1 Probe 1 calibration
CA2 1 Probe 2 calibration
CA3 1 Probe 3 calibration
The value assigned to this parameter is added to
(positive value) or taken away from (negative
value) the temperature detected by the probe
-20.0 … 20.0
°C [°F]
List of -CPr compressor parameters
Ont 1 Compressor ON time in the event of
probe failure
0 … 60 min
OFt 1 Compressor OFF time in the event of
probe failure
In the event of an adjustment probe error, the
compressor is enabled in cyclical mode with set
operation and off times. In particular:
Ont=0: the compressor remains off
Ont>0 and OFt=0: the compressor remains on
0 … 60 min
dOn 1 Compressor activation delay
The time, starting from the switch on request, after which the compressor is effectively
activated.
In the event of network control in sequential mode, this represents the activation delay from
compressor to compressor
0 … 250 sec
dOF 1 Minimum compressor OFF time
The time, starting from the moment of deactivation, for which it is not possible to restart the
compressor
0 … 60 min
dbi 1 Delay between switch on times
The time, starting from the moment of previous activation, for which the compressor cannot be
restarted.
0 … 60 min
OdO 1 Outputs delay at power-on (compressor, fans, defrosting)
This is used to delay the enabling of adjustments after the instrument has been switched on for
a set amount of time.
The transition from stand-by to machine activated (ON command from the keyboard) bypasses
this delay
0 … 60 min
List of -dEF defrosting parameters
dtY* 1 Defrosting type
0 = heating element: ends at temperature or after maximum safe time (timeout)
1 = hot gas: ends at temperature or after maximum safe time (timeout)
For defrosting using a heating element, there is a 1 second delay between the compressor
switching off and the defrosting relay being triggered
0,1
dit 1 Defrosting interval
The maximum time (from start to start) between two consecutive defrosting cycles. When this
time expires, a defrosting cycle is enabled (cyclical defrosting). The timer is reset at each
defrosting request (even if not cyclical).
0 = cyclical defrosting disabled
0 … 250 h
dct 1 Defrosting interval count mode
0 = counts if the compressor is operating
1 = counts all the time
0,1
dOH 1 Defrosting start delay at power-on
The time, as from when the instrument is switched on, for which any defrosting requests are
frozen (manual defrosting excluded)
0 … 250 min
dEt* 1 Defrosting timeout
When the set time expires, defrosting is in any case ended, even if the defrost end temperature
has not been reached, passing on to the drip phase
1 … 250 min
dSt* 1 Defrost end temperature
The probe 2 temperature above which defrosting is ended. If, at the start of a defrosting cycle,
the temperature is greater than that set, no defrosting will be carried out. In the event of a
probe 2 malfunction, the defrosting cycle will in any case terminate after reaching a time limit
-50.0 … 199.0°C [°F]

RIVC000001 Pag. 13 REV. 00 11/10/10
UK
Code Level Descr. Range Unit
dS2 1 Defrost end temperature for the second evaporator
The probe 3 temperature above which defrosting for the second evaporator is ended. If, at the
start of a defrosting cycle, the temperature is greater than that set, no defrosting will be carried
out. In the event of a probe 3 malfunction, the defrosting cycle will in any case terminate after
reaching a time limit.
This function is only enabled if P01=3o4, Co4=3 and CP0=2 (alarm relay used for second
evaporator defrosting and probe 3 used to detect the temperature of the second evaporator). In
this case, the dripping phase will begin after the defrosting cycles of both evaporators have
ended.
-50.0 … 199.0°C [°F]
dPO 1 Defrosting at power-on
0 = disabled
1 = defrosting when the instrument is switched on
0,1 flag
List of -FAn fan parameters
FSt 1 Fans switch on temperature -50.0 … 199.0 °C [°F]
Fot 1 Fans switch off temperature -50.0 … 199.0 °C [°F]
FAd 1 Fans switch on and off differential
probe2 ≥FSt: fans off
Fot ≤probe2 < (FSt – FAd): fans on
probe2 < (Fot – FAd): fans off
1.0 … 90.0 °C [°F]
Fdt 1 Post-dripping time
The time after the dripping phase, during which the fans remain switched off
0 … 60 min
dt 1 Dripping time
The time after a defrosting cycle during which the compressor and the evaporator are stopped
in order to favour evaporator dripping
0 … 60 min
dFd 1 Fans deactivated during defrosting
0 = fans activated (operation set from FPt)
1 = fans deactivated
0,1 flag
FCO 1 Fans activated with compressor off
0 = fans deactivated
1 = fans activated (operation set from FPt)
2 = fans in duty cycle operation
0 … 2
Fon 1 Fans ON time during duty cycle operation (FCO=2) 1 … 60 min
FoF 1 Fans OFF time during duty cycle operation (FCO=2) 1 … 60 min
List of -ALr alarm parameters
AFd 1 Temperature alarm threshold differential
This sets the re-entry temperature threshold after a high- or low-temperature alarm condition
1.0 … 90.0 °C [°F]
HAL 1 Maximum alarm threshold
Above this value (absolute or referred to the setpoint) an alarm is triggered
If the reference is relative, the unmarked value is added to the setpoint
-50.0 … 199.0 °C [°F]
LAL 1 Minimum alarm threshold
Below this value (absolute or referred to the setpoint) an alarm is triggered
If the reference is relative, the unmarked value is subtracted from the setpoint
-50.0 … 199.0 °C [°F]
PAO 1 Temperature alarm delay at power-on 0 … 10 h
dAO 1 Temperature alarm delay after defrost
The time, starting from the end of the dripping phase, during which no alarm is signalled.
In the event of contemporaneous network defrosting, the time refers to the defrosting end
command
0 … 999 min
OAO 1 Temperature alarm delay after door closure
The time, after the door is closed again and during which no alarm is signalled
0 … 10 h
dAt 1 Defrosting alarm timeout enabling
This enables the signalling of any defrosting end due to the maximum time limit being reached
(timeout).
0 = signal disabled
1 = signal enabled
0,1 flag
List of -diS display parameters
ndt 1 Decimal point display
0 = display without decimal point
1 = display with decimal point.
0,1 flag
ddL 1 Display during the defrosting phase
0 = normal display (as set from the ddd par.)
1 = freezes the temperature value displayed at the start of defrosting until the end of defrosting
and the reaching of the setpoint
2 = “dF” until the end of defrosting and the reaching of the setpoint
The ddL parameter can be controlled only if the standard display (ddd par.) includes the
adjustment probe (probe 1 or network probe)
0,1,2
Ldd 1 Defrosting display block timeout
The time, starting from the end of defrosting (end of dripping phase),after which the normal
display is in any case restored
0 … 255 min
dro 1 °C or °F selection
0 = °C
1 = °F
This selection only affects temperature measurements. The values of the parameters
concerning temperature maintain their current values and therefore, they must be varied
manually to adapt them to the Fahrenheit scale.
0,1 flag

RIVC000001 Pag. 14 REV. 00 11/10/10
UK
Code Level Descr. Range Unit
List of -CnF configuration parameters
LOC
(**)
1 Keyboard lock
0 = keyboards disabled
1 = main terminal keyboard enabled
2 = secondary terminal keyboard enabled
3 = keyboards enabled (the first to request a service has precedence until completion)
0 … 3
rEL 1 Software release
A read-only value that identifies the software version
0.0 … 99.9
List of -Lan(***) network parameters
dEA 1 Supervision network address (for Master only)
The address to be set on each master must take into account the number of slaves present in the
LAN network preceding it: “dEA”=”dEA[previous master]”+”L01[previous master]”+1
The Supervision network address for a Slave is “dEA[master]”+”L00”)
1 … 199
(*) For models
PTM068Z012,PTM080Z012,PTL060Z012,PTL080Z012,PTM110Z012,PTM140Z012,PTM200Z012,PTL130Z012,PTL1
80Z012,PTL200Z012,PTL260Z012,PTM300Z012, PTM370Z012, PTL350Z012 and PTL450Z012, the dtY,dEt and dSt
parameters have the following values (Defrosting by heater):
dtY 1 Defrosting type
0 = heating element: ends at temperature or after maximum safe time (timeout)
1 = hot gas: ends at temperature or after maximum safe time (timeout)
For defrosting using a heating element, there is a 1 second delay between the compressor
switching off and the defrosting relay being triggered
0,1
dEt 1 Defrosting timeout (Defrosting by heater)
When the set time expires, defrosting is in any case ended, even if the defrost end temperature
has not been reached, passing on to the drip phase
1 … 250 min
dSt 1 Defrost end temperature (Defrosting by heater)
The probe 2 temperature above which defrosting is ended. If, at the start of a defrosting cycle,
the temperature is greater than that set, no defrosting will be carried out. In the event of a
probe 2 malfunction, the defrosting cycle will in any case terminate after reaching a time limit
-50.0 … 199.0°C [°F]
(**) Note : To release the keypad, hold down “SET” and “ON/OFF” together for at least 5 seconds.
(***) Note : The “LAn” network parameter only serves in the event of MASTER/SLAVE or REMOTE CONTROL
operation
7. 7
ADVANCED ELECTRONIC CARD PROGRAMMING FOR BLOCKSYSTEM
1. Level 2 programming
The procedure for editing level 2 parameters is protected by a password and can be carried out in the
following manner: enter the programming mode by holding down the “set” key for at least 7 seconds
until the display reads “reg”, which corresponds to the adjustment parameters directory, then proceed
as follows:
Press the “down” key (the display will read “PPS”)
Press the “set” key (the display will read “PPA”)
Press the “set” key again (the display will read “0”)
Press the “up” key until the display reads 22 (the level 2 password)
Press the “set” key to confirm the password
At this point, using the “up” and “down” keys, you can access all of the electronic card parameters
shown in the annexed programming chart.
Once you have edited the required parameters, press the “ON/OFF” key twice until the display shows
the cold room temperature (or wait for 15 seconds without pressing any keys); this way the edited
parameters will be stored to the memory.
CAUTION!
THE FOLLOWING SECTION EXPLAINS THE NECESSARY PROCEDURE IN THE EVENT THAT
PARAMETERS ARE EDITED WITHOUT FOLLOWING ANY CRITERIA OR THAT THE CARD SETTINGS
ARE LOST. IN ANY CASE, WE ADVISE THAT YOU FOLLOW THESE STEPS ONLY AFTER THE
APPROVAL OF A RIVACOLD TECHNICAL ENGINEER.

RIVC000001 Pag. 15 REV. 00 11/10/10
UK
2. Restoring the factory settings
CAUTION: the following procedure will restore all factory settings for the electronic card. We advise
that you only do this if strictly necessary and in any case, that you are assisted by a technical engineer
from Rivacold.
Cut off the power to the Blocksystem.
Press the “set” and “down” keys at the same time, then switch the Blocksystem on again while holding
down these keys.
Release the keys when the display reads “–3”.
At this point, the electronic card will re-start and its parameters will have returned to those set in the
factory. The display will read “Um” for 1 second; it will then show the temperature read by the cold
room probe.
PLEASE NOTE: THIS OPERATION RESTORES THE FACTORY SETTINGS FOR A MEDIUM-
TEMPERATURE MACHINE APPLICATION (-5/+5°C) WITH “HOT GAS” DEFROSTING.
IF YOU ARE USING AN APPLICATION OTHER THAN “MEDIUM TEMPERATURE” AND/OR A
DIFFERENT TYPE OF DEFROSTING (NOT “HOT GAS”), YOU MUST FOLLOW THE INSTRUCTIONS
IN THE FOLLOWING SECTION, AND REFER TO THE “CPP PARAMETER PROGRAMMING CHART”.
3. Rapid programming according to the application required
Level 2 programming contains a parameter known as “CPP” (to be found in the “cnf” directory) which
is used for the rapid programming of parameters according to application and defrosting types (see
following chart).
CPP parameter programming chart
Defrosting Hot gas Hot gas Fan Heating
element Heating
element
Application -5/+5°C -25/-15°C +2/+10°C -5/+5°C -25/-15°C
Menu Code no. CPP=1 CPP=2 CPP=3 CPP=4 CPP=5
REG SEt 2.0 -18.0 5.0 2.0 -18.0
REG diF 2.0 2.0 2.0 2.0 2.0
REG HSE 5.0 -15.0 10.0 5.0 -15.0
REG LSE -5.0 -25.0 2.0 -5.0 -25.0
DEF dtY 1 1 0 0 0
DEF dEt 15 15 15 30 30
DEF dSt 10.0 15.0 10.0 15.0 15.0
Fan FSt 8.0 -5.0 50.0 8.0 -5.0
Fan Fdt 1 2 0 1 2
Fan dt 2 2 0 2 2
Fan dFd 1 1 0 1 1
Follow the instructions in paragraph 1 to access level 2 programming
Press the “up” or “down” keys until you reach the “CnF” directory
Press the “set” key (the LOC parameter will appear)
Press the “up” key until you reach the “CPP” parameter
Press the “set” key (the number 0 will appear)
Press the “up” key until you reach the number corresponding to the required program
Then press the “set” key to confirm.
8. ALARM SIGNALS
In the event of an alarm, the card normally activates the following:
•The relevant alarm code is shown on the display. In particular, the control alternates the alarm
code and the temperature that is normally shown on the display; if there is more than one alarm,
they are displayed in succession, alternated with the temperature
•The alarm LED is switched on
•The alarm relay is triggered.
For some alarms and signals, the LED and/or relay are not triggered. The table below gives a detailed
description for each alarm and the relevant actions undertaken.
Pressing any button will deactivate the relay (if triggered) and the LED will blink, while the alarm code will
remain on the display. The LED will switch off and the alarm code will disappear only when the cause
behind it has ceased. The alarm codes are listed in the table below:

RIVC000001 Pag. 16 REV. 00 11/10/10
UK
Code
displayed
Description/Control LED
enable
Relay
enable
Reset Mode
E1 cold room probe temperature error
if a probe is used for adjustment, the compressor will
be activated cyclically and defrosting cycles will be
disabled;
if a balanced network probe is enabled, adjustment
will continue, bypassing the malfunctioning probe
yes yes automatic when the
condition ceases
E2 End defrostin probe g error
defrosting will end due to timeout
yes yes automatic when the
condition ceases
3rd probe error (condenser temperature)
the associated controls are disabled
blink. noE3
3rd probe error (2nd evaporator temperature)
defrosting will end due to timeout
yes yes
automatic when the
condition ceases
heat alarm (*)
adjustment is disabled
yes no automatic when the
condition ceases
HP pressure switch alarm(*)
adjustment is disabled
yes no automatic when the
condition ceases
LP pressure switch alarm(*)
adjustment is disabled
yes no automatic when the
condition ceases
E4 repeated heat alarm
adjustment is disabled permanently
yes yes at switch on
E5 repeated HP pressure switch alarm
adjustment is disabled permanently
yes yes at switch on
E6 repeated LP pressure switch alarm
adjustment is disabled permanently
yes yes at switch on
LO low temperature alarm yes yes automatic when the
condition ceases
HI high temperature alarm yes yes automatic when the
condition ceases
EE data saving alarm
default parameters are loaded
yes yes at power-on or after
the parameter has
been stored to
memory
Ec condenser cleaning alarm blink. no automatic when the
condition ceases
Er network alarm (**) yes yes automatic when the
condition ceases
Ed defrosting timeout alarm blink. no automatic at the start
of the next defrost
Od door open timeout alarm
normal operation is enabled again
blink. no automatic when the
condition ceases
nx slave x alarm (on master only) yes progr. automatic when the
condition ceases
Ux slave x not connected (on master only)
the slave is not controlled
blink. no automatic when the
condition ceases
u0 master not connected (on slave only)
the slave is released from the network and operates
autonomously
blink. no automatic when the
condition ceases
dx slave x download failed(on master only) blink. no manual or automatic
when the condition
ceases
(*) There is no reading on the display.
(**) Network alarms are where, subsequent to programming, the alarm command is communicated from the
master to all network devices, in the event that the alarm relay is triggered on the master itself
During operation, in specific conditions the following signals are displayed:

RIVC000001 Pag. 17 REV. 00 11/10/10
UK
Code
displayed
Description Notes
OFF unit in stand-by (operation disabled) remains until the next ON command
dF defrosting in progress see par. “ddL”
dFu defrosting not performed displayed for 2 seconds when the defrosting
command is not performed because the evaporator
temperature is already above the defrosting end
temperature (parameter dst)
uM master unit
uSx slave x unit
at switch on, the network configuration of the unit is
displayed
Cn terminal/control connection interrupted the terminal is not receiving data from the control
If the terminal/control connection does not operate correctly at switch on, the terminal display will read “88,8” and
the LEDs will all be switched off.
9.EMERGENCY SYSTEM
PLEASE NOTE: A specialist technical engineer must only perform the operations described here below.
If the electronic control unit breaks down or presents operating anomalies and it is impossible to replace
it immediately, there is an EMERGENCY SYSTEM that can be used to maintain the unit in operation until
it can be replaced.
To use this system, proceed as follows:
1. Cut off power to the Blocksystem
2. Remove all jumpers between the L terminals and the common contacts of the card relays (terminals
25-28-33-36-38)
3. As shown in the diagram, connect a thermostat between the L terminal, the NO terminals (terminals
32,37) and the NC terminal (terminal 34) of the compressor, defrosting and fan relays (COMP, DEF
and FAN)
4. Fit a jumper between the L terminal and the NO terminal of the ON/OFF relay (terminal 26
supplying power to the crankcase heaters, door and waste, where fitted).
5. Connect the Blocksystem back to the mains power, setting the thermostat to the required
temperature.
6. PLEASE NOTE: This connection can only be used momentarily. Contact your dealer as soon as
possible to replace the malfunctioning card.
7. PLEASE NOTE: Defrosting will be cut out for the entire emergency phase and for this reason, we
recommend that cold room door opening be kept to a minimum.
8. When fitting the new control unit, restore all of the connections described in points 2,3,4 and 5.
Key:
T = Thermostat T
Table of contents
Popular Controllers manuals by other brands

LED Technologies, Inc.
LED Technologies, Inc. R208 user manual

Halma
Halma ALICAT SCIENTIFIC MC Series Get started

Regin
Regin RVAZ4-230 Instruction

HIK VISION
HIK VISION DS-C12L Series user manual

Krom Schroder
Krom Schroder IC 40 operating instructions

RMG
RMG 672 OPERATING AND MAINTENANCE INSTRUCTIONS/ SPARE PARTS