*AIR OR GAS
Sales Manual Section 332
PRODUCT SPECIFICATION PS 83939-E
Lockout Relay
83939-E1
B. Mounting
When installing the No. 83939-E 1 Lockout
Relay,
care should be taken to prevent any foreign matter
from entering the ports. Provisions should be
made to
prevent foreign matter from entering the ports
which are left open to the atmosphere.
The relay may be installed in any position, but
vertical (upright) is recommended. The relay
should be
securely mounted, using the two slots (clearance
for No. 10 screws), provided in the mounting
bracket (See Figure 1).
J. I. C. S
y
mbol
F
orm
N
o.
P
-
2317
(R
ev.
B)
GENERAL DESCRIPTION
The No. 83939-E1 Lockout Relay is a two-way,
diaphragm-actuated, non-venting, normally open
valve. It is used in the safety system to lock out or
block certain portions of the control system or a line in
a control system upon receipt of a signal at PORT 1.
(See Figure 1). It will reopen with the loss of pressure
at PORT 1, and has a connection which may be used to
cancel the actuating pressure at PORT 1.
SPECIFICATIONS
Construction: Aluminum body; stainless steel cover,
bracket and springs; elastomer coated fabric
diaphragms and gaskets; stainless steel and
aluminum valve with resilient seat.
Supply Pressure: ...........................................See Figure 2.
CAUTION: DO NOT EXCEED MAXIMUM PRESSURES
Maximum Pressure: ......................................See Figure 2.
Mounting: .................................................................Surface
Dimensions: ...................................................See Figure 1.
Connections: ................................................ 1/8"-27 NPT.
Approximate Shipping Weight: ............. 12 ozs. (.340 kg)
Ordering Information:
Specify: No.
83939-E1
INSTALLATION
A. General
Tubing and fittings used to connect the relay
must be free of chips, dirt, and moisture or other
foreign material.
It is recommended that an "anti-seize" type
thread compound be applied to the second or third
male thread in moderate amount. Do not allow
compound to be deposited inside the relay. Thread
sealing tape is not recommended.
For continuous, trouble-free operation, the
supply to the relay must be clean and dry.
2
DIMENSIONS
Fi
g
ure 1
OPERATION (See Figure 3 )
With no pressure applied to the diaphragm
through Port 1, Port 3 (supply port) is connected
through this normally open relay to Port 2.
When sufficient pressure is applied to the
diaphragm through Port 1, the stem moves down and
forces the lower poppet on seat,
closing Port 3 to Port 2. Loss of pressure through Port
1 will allow the stem to return to its original position.
At the same time, the lower spring will force the
lower poppet off seat, opening Port 3, again, to Port
2. Also, the relay may be reopened by applying an
equalizing pressure through Port 4.
NOTE
:
G
rap
h
A
i
n
di
ca
t
es ac
t
ua
ti
ng pressure
(P
or
t
1) required to keep valve closed at various
supply pressures (Port 3). Also, Graph A
indicates actuating pressure (Port 1) minus
equalizing pressure (Port 4) required to
keep valve closed at various supply
pressures (Port 3).
NOTE
:
G
rap
h
B
i
n
di
ca
t
es
d
ecreas
i
ng ac
t
ua
ti
ng
pressure (Port 1) required to open valve at
various supply pressures (Port 3). Also,
Graph B indicates decreasing actuating
pressure (Port 1) minus equalizing
pressure (Port 4) required to permit same
action.
CAUTION: DO NOT EXCEED MAXIMUM PRESSURES.
Figure 2
3
Figure 3 Figure 4
MAINTENANCE
WARNING: Disassemble carefully - spring load
forces present.
A. If excessive leakage occurs at valve seat,
disassemble the relay. Clean poppet and seat with
soft, dry cloth (See Figure 4).
B. If relay does not function properly due to
contamination by foreign matter, disassemble and
clean all metal parts with non-flammable solvent
and dry thoroughly.
C. After reassembly, check for external leakage.
Retighten assembly screws as necessary. Gasket
cement should not be used to seal leaks due to the
possibility of plugging small passages or
damaging the operating characteristics of the
diaphragms.
CAUTION:
If cleaning is required, do not subject "O" rings,
valve poppets, diaphragms or gaskets to cleaning
fluid, acetone, or any halogenated hydrocarbons such
as vapor degrease liquids, etc. Clean only with a soft,
dry cloth.
Upon reassembly, all "O" rings are to be
lubricated with a silicone-type lubricant. Do not
permit lubricant to get on poppet or valve seats.
4
Q-3580 (5/01) Printed in U.S.A.
NOTE: For complete kit containing all "O" Rings, gaskets,
diaphragms, and poppet to service one unit, order Repair Kit No.
82665-B3. Repair Kit includes Details 6,7,11 and 13 - also
instruction manual and lubricant.
PARTS LIST
DET.
NO.
NO.
REQ’D DESCRIPTION DWG.
NO.
1 4 Screw 33713-H2409
2 4 Lockwasher 36600-L0609
3 1 Mounting Bracket 24637-C2
4 1 Relay Body 31857-E1
5 1 Head & Stem
Assembly
85013-81
6 1 O-Ring 36240-C10
7 1 Plug & Guide
Assembly
99264-B1
8 1 Nameplate 30036-G2
9 1 Relay Body 31857-D1
10 1 Spring 25121-A1
11 2 Gasket 33665-B 1
12 1 Spring 24598-A1
13 1 Diaphragm 24498-A1
14 1 Spacer 33430-A2
PARTS LIST

Other Robertshaw Relay manuals

Robertshaw CR-101-A1 User manual

Robertshaw

Robertshaw CR-101-A1 User manual

Robertshaw 83939-D Series User manual

Robertshaw

Robertshaw 83939-D Series User manual

Robertshaw CR-103-A Series User manual

Robertshaw

Robertshaw CR-103-A Series User manual

Popular Relay manuals by other brands

BPC CXPLUSR operating instructions

BPC

BPC CXPLUSR operating instructions

Basler BE1-81O/U instruction manual

Basler

Basler BE1-81O/U instruction manual

AJAX WallSwitch user manual

AJAX

AJAX WallSwitch user manual

Basler BE1-47N instruction manual

Basler

Basler BE1-47N instruction manual

FANOX P Series manual

FANOX

FANOX P Series manual

sisel ENDA EPDA1 Series instructions

sisel

sisel ENDA EPDA1 Series instructions

SICK ReLy MULT1 operating instructions

SICK

SICK ReLy MULT1 operating instructions

Merz UHOO-16 manual

Merz

Merz UHOO-16 manual

frako RM 2106/12 operating instructions

frako

frako RM 2106/12 operating instructions

Schweitzer Engineering Laboratories SEL-321-5 instruction manual

Schweitzer Engineering Laboratories

Schweitzer Engineering Laboratories SEL-321-5 instruction manual

ABB CAP 501 Installation and commissioning manual

ABB

ABB CAP 501 Installation and commissioning manual

Seg MRM3 manual

Seg

Seg MRM3 manual

GE DGP instruction manual

GE

GE DGP instruction manual

Zamel PBM-01 instruction manual

Zamel

Zamel PBM-01 instruction manual

Siemens SIPROTEC 4 user manual

Siemens

Siemens SIPROTEC 4 user manual

Seg MRN3 manual

Seg

Seg MRN3 manual

Johnson Controls MR4PMUHV manual

Johnson Controls

Johnson Controls MR4PMUHV manual

Eaton EMT6-K Instruction leaflet

Eaton

Eaton EMT6-K Instruction leaflet

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.