Ed. 11/2006
User, Installation and Service Manual for F1 Gas Unit Heaters8
SECTION 3 - INSTALLATION
GENERAL RULES
WARNING!
- A qualified service engineer following the manufacturer’s instructions must carry out the
installation.
- Qualified engineer means those having specific technical competence according to
national/international standards. In any case all necessary information could be obtained
directly by Qualified Engineer or Manufacturer.
- An incorrect installation can cause damages to people, animals and property. In case of
erroneous installation, the manufacturer cannot be held responsible for such damages.
- The units must be installed according to the national and international norms regarding this
type of appliances and applications.
Install the gas supply lines, the electric power lines and a suitable support bracket for the unit
according the approved installation project.
Installation procedures should be as follows:
A. Unpack the unit, carefully checking that it has not been damaged. Every unit is factory tested before
shipment, therefore, if there are damages, report them immediately to the carrier.
B. The minimum distance from the wall behind the unit must be enough for air circulation. The
minimum distance from the lateral walls is given by Figure 3.
C. The recommended height from the floor to the heater base is 2.5 to 3.5 m. It is not
recommended to install the appliance under the 2.5m height.
D. A gas cock and a pipe union must be provided for gas supply.
E. Make sure that an adequate gas supply from the gas network is provided, particularly if the unit
is supplied with:
Natural gas - G20:
Be sure that the pressure of the gas network, with the unit in operation, is set at 20 mbar (0.29
psig, 8.03 in.WG.) allowed tolerance between 17 and 25 mbar (0.25 to 0.36 psig; 6.9 to 10.0
in.WG.).
LPG (Propane – Butane mix) - G30:
For the first pressure drop required in the supply, it is advisable to install a pressure
governor near the liquid gas tank so as to reduce the pressure to 1.5 bar (22 psig). A
pressure governor for a second pressure drop should be placed near the heater to reduce
the pressure to 30 mbar (0.43 psig; 12.0 in.WG.) allowed tolerance between 20 and 35
mbar (0.29 to 0.50 psig; 8.1 to 14 in.WG.).
LPG (Pure Propane) - G31:
For the first pressure drop required in the supply, it is advisable to install a pressure
governor near the liquid gas tank so as to reduce the pressure to 1.5 bar (22 psig). A low
pressure governor for a second pressure drop should be placed near the heater to reduce
the pressure to 37 mbar (0.43 psig; 12.0 in.WG.) allowed tolerance between 25 and 45
mbar (0.29 to 0.50 psig; 8.1 to 14 in.WG.).
NOTE: In the case of doubt, adjust the appliance as for the propane- butane mix.
F. Carry out the electrical connections according to the installation wiring diagram (see figure 19),
checking that the voltage supply is 230/50Hz single-phase. For this operation make sure that:
- all electrical supply parameters are according to those required on the type plate of the appliance.
- wire type is H05 VVF 3x1 mm2 with a maximum external diameter of 8.4 mm.
- when connecting, ensure that the earth wire is longer than the live wires, so that it will be the last
wire to break if the supply cable is stretched, thus ensuring a good earth continuity.