SMOKE
RED LED
GAS
BLUE LED
AUDIBLE & VISUAL SIGNALS
HORN
OPERATIONAL SUMMARY
CONDITION / RECOMMENDATION
Silent Off
Off Off Condition: AC power is present. DC power is present.
Recommendation: None
CO
RED LED
Silent Off
Off Off Condition: Alarm is powered by battery backup. AC
Power is not present.
Recommendation: Check the breaker or fuse box for
power. If the breaker or fuse box looks normal, call a
licensed electrician for assistance.
3 beeps,
2 second pause,
3 beeps,
6 second pause,
4 beeps,
5 second pause,
1 beep
Blinks On in
sync with
the 1 beep
Blinks On during
the cycle of
3 beeps and
turns off
Blinks On in sync
with the cycle of
4 beeps and
turns off
Condition: The test/silence button has been pressed. The
test sequence lasts for approx. 20 seconds.
Recommendation: None
Off
Off Off
Horn does not
sound when
other alarms
are active
or when
interconnected
alarm’s
test/reset
button is
pressed
3 Beeps,
2 second pause,
repeat
Off
Blinks On
approx. once
every second
Off Condition: Originating Smoke Alarm.
Recommendation: If hazard is identified, take all
precautions if an alarm sounds by calling an Emergency
Service and getting out of the home.
3 Beeps,
2 second pause,
repeat
Off
Off Off Condition: Non-originating Smoke Alarm.
Recommendation: Another interconnected smoke alarm
has sensed smoke, causing all interconnected units to
sound. If hazard is identied, take all precautions if an
alarm sounds by calling an Emergency Service and getting
out of the home.
4 Beeps,
5 second pause,
repeat
Off
Off Blinks On in
sync with
4 beeps
Condition: Originating CO Alarm.
Recommendation: If hazard is identified, take all
precautions if an alarm sounds by calling an Emergency
Service and getting out of the home.
4 Beeps,
5 second pause,
repeat
Off
Off Off Condition: Non-originating CO Alarm.
Recommendation: An interconnected CO alarm has
sensed CO, causing all interconnected units to sound.
If hazard is identied, take all precautions if an alarm
sounds by calling an Emergency Service and getting
out of the home.
1 Beep,
2 second pause,
repeat
Off
Off Blinks On
in sync
with the
1 beep
Condition: Originating GAS Alarm.
Recommendation: If hazard is identified, take all
precautions if an alarm sounds by calling an Emergency
Service and getting out of the home.
1 Beep,
2 second pause,
repeat
Off
Off Off Condition: Non-originating GAS Alarm.
Recommendation: An interconnected GAS alarm has
sensed GAS, causing all interconnected units to sound.
If hazard is identied, take all precautions if an alarm
sounds by calling an Emergency Service and getting
out of the home.
3 Beeps,
2 second pause,
repeat
Off
Blinks On
approx. once
every second
Off or Blinks
On in
sync with
the 1 beep
Condition: Nuisance Alarm.
Recommendation: If there is no hazard present, verify the
alarm imounted in the correct location (see User’s Manual).
Reset alarm as instructed below.
Horn sounds
when no
hazard is
present
Off
Off or Blinks
On approx.
every second
Off or Blinks
On in sync
with 4 beeps
4 Beeps,
5 second pause,
repeat
Blinks
On in sync
with 4 beeps
Off Off
POWER
GREEN LED
On and Blinks
Off approx
every 20
seconds
Off and Blinks
On approx
every 40
seconds
Turns off
when the
3 beeps start
*See below
Turns off
when the
3 beeps start
Turns off
when the
4 beeps start
Turns off
when the
3 beeps start
Turns off
when the
4 beeps start
Turns off
when the
1 beep starts
Turns off
when the
1 beep starts
Turns Off when
the 3 beeps
start
Turns off
when the
beeps start
Turns off
when the
4 beeps start
Condition: Smoke alarm when cause of alarm is known
and poses no threat.
Recommendation: The smoke alarm Silence Feature can
be activated by pressing and releasing the Test/Silence
button on the initiating alarm while in alarm condition.
Silence mode will last for approx. 8-12 minutes (with the
red LED blinking on approx. every 10 seconds).
Condition: CO alarm when cause of alarm is known and
poses no threat.
Recommendation: The CO alarm Silence Feature can be
activated by pressing and releasing the Test/CO Silence
button on the initiating alarm while in alarm condition. The
alarm will remain silent for approx. 5 minutes (with the red
LED blinking on approx. every 10 seconds), depending on
the level of CO detected. If CO levels drop below alarm
levels, the alarm will remain silent and return to normal
operation. If CO levels remain constant or increase, this
indicates a potentially dangerous situation and the horn
will sound again. Ventilate area.
Condition: One or more alarms not responding to
interconnected alarm.
Recommendation: Press and hold the smoke alarm
Test/Silence button for at least 5 seconds. If still no alarm,
turn off AC Power at the circuit breaker or fuse box and
disconnect the alarm from the mounting bracket and make
sure the connector plug is securely attached on units that
did not alarm. If still no alarm, have a licensed electrician
make sure the yellow wire is not mistakenly or accidentally
connected to the white (neutral) wire.

17
Page 16
SMOKE
RED LED
GAS
BLUE LED
AUDIBLE & VISUAL SIGNALS
HORN
OPERATIONAL SUMMARY
CONDITION / RECOMMENDATION
Silent Off
Off Off Condition: AC power is present. DC power is present.
Recommendation: None
CO
RED LED
Silent Off
Off Off Condition: Alarm is powered by battery backup. AC
Power is not present.
Recommendation: Check the breaker or fuse box for
power. If the breaker or fuse box looks normal, call a
licensed electrician for assistance.
3 beeps,
2 second pause,
3 beeps,
6 second pause,
4 beeps,
5 second pause,
1 beep
Blinks On in
sync with
the 1 beep
Blinks On during
the cycle of
3 beeps and
turns off
Blinks On in sync
with the cycle of
4 beeps and
turns off
Condition: The test/silence button has been pressed. The
test sequence lasts for approx. 20 seconds.
Recommendation: None
Off
Off Off
Horn does not
sound when
other alarms
are active
or when
interconnected
alarm’s
test/reset
button is
pressed
3 Beeps,
2 second pause,
repeat
Off
Blinks On
approx. once
every second
Off Condition: Originating Smoke Alarm.
Recommendation: If hazard is identified, take all
precautions if an alarm sounds by calling an Emergency
Service and getting out of the home.
3 Beeps,
2 second pause,
repeat
Off
Off Off Condition: Non-originating Smoke Alarm.
Recommendation: Another interconnected smoke alarm
has sensed smoke, causing all interconnected units to
sound. If hazard is identied, take all precautions if an
alarm sounds by calling an Emergency Service and getting
out of the home.
4 Beeps,
5 second pause,
repeat
Off
Off Blinks On in
sync with
4 beeps
Condition: Originating CO Alarm.
Recommendation: If hazard is identified, take all
precautions if an alarm sounds by calling an Emergency
Service and getting out of the home.
4 Beeps,
5 second pause,
repeat
Off
Off Off Condition: Non-originating CO Alarm.
Recommendation: An interconnected CO alarm has
sensed CO, causing all interconnected units to sound.
If hazard is identied, take all precautions if an alarm
sounds by calling an Emergency Service and getting
out of the home.
1 Beep,
2 second pause,
repeat
Off
Off Blinks On
in sync
with the
1 beep
Condition: Originating GAS Alarm.
Recommendation: If hazard is identified, take all
precautions if an alarm sounds by calling an Emergency
Service and getting out of the home.
1 Beep,
2 second pause,
repeat
Off
Off Off Condition: Non-originating GAS Alarm.
Recommendation: An interconnected GAS alarm has
sensed GAS, causing all interconnected units to sound.
If hazard is identied, take all precautions if an alarm
sounds by calling an Emergency Service and getting
out of the home.
3 Beeps,
2 second pause,
repeat
Off
Blinks On
approx. once
every second
Off or Blinks
On in
sync with
the 1 beep
Condition: Nuisance Alarm.
Recommendation: If there is no hazard present, verify the
alarm imounted in the correct location (see User’s Manual).
Reset alarm as instructed below.
Horn sounds
when no
hazard is
present
Off
Off or Blinks
On approx.
every second
Off or Blinks
On in sync
with 4 beeps
4 Beeps,
5 second pause,
repeat
Blinks
On in sync
with 4 beeps
Off Off
POWER
GREEN LED
On and Blinks
Off approx
every 20
seconds
Off and Blinks
On approx
every 40
seconds
Turns off
when the
3 beeps start
*See below
Turns off
when the
3 beeps start
Turns off
when the
4 beeps start
Turns off
when the
3 beeps start
Turns off
when the
4 beeps start
Turns off
when the
1 beep starts
Turns off
when the
1 beep starts
Turns Off when
the 3 beeps
start
Turns off
when the
beeps start
Turns off
when the
4 beeps start
Condition: Smoke alarm when cause of alarm is known
and poses no threat.
Recommendation: The smoke alarm Silence Feature can
be activated by pressing and releasing the Test/Silence
button on the initiating alarm while in alarm condition.
Silence mode will last for approx. 8-12 minutes (with the
red LED blinking on approx. every 10 seconds).
Condition: CO alarm when cause of alarm is known and
poses no threat.
Recommendation: The CO alarm Silence Feature can be
activated by pressing and releasing the Test/CO Silence
button on the initiating alarm while in alarm condition. The
alarm will remain silent for approx. 5 minutes (with the red
LED blinking on approx. every 10 seconds), depending on
the level of CO detected. If CO levels drop below alarm
levels, the alarm will remain silent and return to normal
operation. If CO levels remain constant or increase, this
indicates a potentially dangerous situation and the horn
will sound again. Ventilate area.
Condition: One or more alarms not responding to
interconnected alarm.
Recommendation: Press and hold the smoke alarm
Test/Silence button for at least 5 seconds. If still no alarm,
turn off AC Power at the circuit breaker or fuse box and
disconnect the alarm from the mounting bracket and make
sure the connector plug is securely attached on units that
did not alarm. If still no alarm, have a licensed electrician
make sure the yellow wire is not mistakenly or accidentally
connected to the white (neutral) wire.

18
Page 17
GAS
BLUE LED
AUDIBLE & VISUAL SIGNALS
HORN
OPERATIONAL SUMMARY (continued)
CONDITION / RECOMMENDATION
Horn has
stopped
sounding
Off Off Condition: Latching smoke LED indicator. The alarm has
previously detected smoke and had alarmed.
Recommendation: Follow the reset instructions to remove
the latching LED.
CO
RED LED
Silent
(alarmed
previously)
Off or Blinks
On approx
every 5
seconds
until reset
Off or Blinks
On approx
every 5
seconds
until reset
Condition: Alarm needs to be reset due to abnormal
operation/previous alarms.
Recommendation: To reset the alarm, hold the Test/Silence
button for 10 seconds or until the blue LED turns on. This
will clear the alarm origination and latching LEDs. Reset
after each alarm event.
Horn has
stopped
sounding
Off
Off Condition: Latching CO LED indicator. The alarm has
previously detected CO and had alarmed.
Recommendation: Follow the reset instructions to remove
the latching LED.
Horn has
stopped
sounding
Off Off Condition: Latching GAS LED indicator. The alarm has
previously detected GAS and had alarmed.
Recommendation: Follow the reset instructions to remove
the latching LED.
1 Chirp
approx.
every 40
seconds
Off Off Condition: Low battery.
Recommendation: Check to make sure a battery is present
in the drawer, the battery activation pull tab has been
completely removed, battery polarity is correct and the battery
terminals are making contact with the smoke alarm contacts
in the battery drawer. If chirp continues, replace the 9V battery
(see User’s Manual for recommended battery types).
3 Chirps
approx.
every 20
seconds
Off Off Condition: Sensor Trouble/Sensor End-of-Life Alarm.
Recommendation: Reset the alarm. If this does not clear
the problem, replace alarm.
2 Chirps
approx.
every 20
seconds
Off Off Condition: Product End-of-Service Life Notication.
Recommendation: Replace the alarm immediately. The
product end-of-service life notication can be temporarily
silenced for a 10 hour period for up to 20 days. After 20
days, the warning cannot be silenced. The alarm should be
replaced immediately.
Silent
(alarmed
previously)
Off or Blinks
On approx.
every 5
seconds until
reset
Off or
Blinks On
approx.
every 5
seconds
until reset
* During 120 volt operation On and Blinks Off approx. every 20 seconds.
During 9 volt (DC backup) operation, blinks On approx. every 40 seconds.
POWER
GREEN LED
On and Blinks
Off approx
every 20
seconds
On and Blinks
Off approx
every 20
seconds
On and Blinks
Off approx
every 20
seconds
On and Blinks
Off approx
every 20
seconds
On and Blinks
Off approx
every 20
seconds
On and Blinks
Off approx
every 20
seconds
On and Blinks
Off approx
every 20
seconds
On and Blinks
Off approx
every 20
seconds
SMOKE
RED LED
Off and Blinks
On approx
every 5
seconds
until reset
Off and Blinks
On approx
every 5
seconds
until reset
Off or Blinks
On approx
every 5
seconds
until reset
Off
Off
Off
Off or Blinks
On approx
every 5
seconds
until reset
Off and Blinks
On approx
every 5
seconds
until reset
Condition: Previous alarm condition at unidentied source.
Recommendation: QUICK FIND®Alarm Origination - In an
interconnected system, it is difcult to determine which alarm
initiated the alarms to sound. The QUICK FIND®feature will
immediately allow you to locate the originating alarm (once the
alarms have stopped sounding). To initiate QUICK FIND®, press
the Test/Silence button on any alarm. After releasing the button,
the test sequence will sound and then stop. Then, the originating
alarm will continue to sound for approx 50 seconds. In a non-
interconnected installation, it is necessary to test each alarm
to determine the originating alarm. Reset the originating alarm.

19
Page 17
GAS
BLUE LED
AUDIBLE & VISUAL SIGNALS
HORN
OPERATIONAL SUMMARY (continued)
CONDITION / RECOMMENDATION
Horn has
stopped
sounding
Off Off Condition: Latching smoke LED indicator. The alarm has
previously detected smoke and had alarmed.
Recommendation: Follow the reset instructions to remove
the latching LED.
CO
RED LED
Silent
(alarmed
previously)
Off or Blinks
On approx
every 5
seconds
until reset
Off or Blinks
On approx
every 5
seconds
until reset
Condition: Alarm needs to be reset due to abnormal
operation/previous alarms.
Recommendation: To reset the alarm, hold the Test/Silence
button for 10 seconds or until the blue LED turns on. This
will clear the alarm origination and latching LEDs. Reset
after each alarm event.
Horn has
stopped
sounding
Off
Off Condition: Latching CO LED indicator. The alarm has
previously detected CO and had alarmed.
Recommendation: Follow the reset instructions to remove
the latching LED.
Horn has
stopped
sounding
Off Off Condition: Latching GAS LED indicator. The alarm has
previously detected GAS and had alarmed.
Recommendation: Follow the reset instructions to remove
the latching LED.
1 Chirp
approx.
every 40
seconds
Off Off Condition: Low battery.
Recommendation: Check to make sure a battery is present
in the drawer, the battery activation pull tab has been
completely removed, battery polarity is correct and the battery
terminals are making contact with the smoke alarm contacts
in the battery drawer. If chirp continues, replace the 9V battery
(see User’s Manual for recommended battery types).
3 Chirps
approx.
every 20
seconds
Off Off Condition: Sensor Trouble/Sensor End-of-Life Alarm.
Recommendation: Reset the alarm. If this does not clear
the problem, replace alarm.
2 Chirps
approx.
every 20
seconds
Off Off Condition: Product End-of-Service Life Notication.
Recommendation: Replace the alarm immediately. The
product end-of-service life notication can be temporarily
silenced for a 10 hour period for up to 20 days. After 20
days, the warning cannot be silenced. The alarm should be
replaced immediately.
Silent
(alarmed
previously)
Off or Blinks
On approx.
every 5
seconds until
reset
Off or
Blinks On
approx.
every 5
seconds
until reset
* During 120 volt operation On and Blinks Off approx. every 20 seconds.
During 9 volt (DC backup) operation, blinks On approx. every 40 seconds.
POWER
GREEN LED
On and Blinks
Off approx
every 20
seconds
On and Blinks
Off approx
every 20
seconds
On and Blinks
Off approx
every 20
seconds
On and Blinks
Off approx
every 20
seconds
On and Blinks
Off approx
every 20
seconds
On and Blinks
Off approx
every 20
seconds
On and Blinks
Off approx
every 20
seconds
On and Blinks
Off approx
every 20
seconds
SMOKE
RED LED
Off and Blinks
On approx
every 5
seconds
until reset
Off and Blinks
On approx
every 5
seconds
until reset
Off or Blinks
On approx
every 5
seconds
until reset
Off
Off
Off
Off or Blinks
On approx
every 5
seconds
until reset
Off and Blinks
On approx
every 5
seconds
until reset
Condition: Previous alarm condition at unidentied source.
Recommendation: QUICK FIND®Alarm Origination - In an
interconnected system, it is difcult to determine which alarm
initiated the alarms to sound. The QUICK FIND®feature will
immediately allow you to locate the originating alarm (once the
alarms have stopped sounding). To initiate QUICK FIND®, press
the Test/Silence button on any alarm. After releasing the button,
the test sequence will sound and then stop. Then, the originating
alarm will continue to sound for approx 50 seconds. In a non-
interconnected installation, it is necessary to test each alarm
to determine the originating alarm. Reset the originating alarm.

20
Other manuals for RSA-200
1
Table of contents
Other Roost Smoke Alarm manuals
Popular Smoke Alarm manuals by other brands

Elkron
Elkron SD610 Installation, programming and functions manual

Universal Security Instruments
Universal Security Instruments MIB3050S manual

Bosch
Bosch FCD-350 installation instructions

Carrier
Carrier KIDDE P4010ACS-WF user guide

INSTEON
INSTEON Smoke Bridge owner's manual

Honeywell
Honeywell NOTIFIER FSP-951-SELFT Installation and maintenance instructions