RVP 6536D891 User manual

QUICK REFERENCE GUIDE
P.C. BOARD/WALL THERMOSTAT
FOR
6536D891 & 6536D881
TWO TON PACKAGED
HEAT PUMPS
RV Products
A Division of Airxcel, Inc.
P.O. Box 4020
Wichita, KS 67204
1-316-832-4357 (Dealer Only Technical Help)
Web: www.rvcomfort.com
Support: [email protected]
Sales: [email protected]
1976-469 (1-07)

TABLE OF CONTENTS
I. Wall Thermostat Installation and Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
II. Heat Pump Operation Sequence - Cooling Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
III. Heat Pump Operation Sequence - Heating Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
IV. 6535C320 Printed Circuit Board Function Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Printed Circuit Board 9-Pin Thermostat Plug Connector . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Printed Circuit Board Indoor Blower Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Printed Circuit Board Compressor Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Printed Circuit Board Freeze Sensor Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Printed Circuit Board Outdoor Blower Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Printed Circuit Board Heating (Heat Pump) Section. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
V. Wiring Diagram - 6536 “D” Series Two Ton Packaged Heat Pump. . . . . . . . . . . . . . . . . . . . . . . 15

3
I. WALL THERMOSTAT INSTALLATION AND
OPERATING INSTRUCTIONS
APPLICATION
The 6536A335* thermostat is intended for use with an RV
Products 2-stage heat pump.
The thermostat connects to the heat pump with a 9 pin plug
through a lifeline (RVP part number 6795C4351). The OEM
(Original Equipment Manufacturer) must supply the 12 VDC
wiring and the furnace control wiring which connects to the 3
pin plug on the thermostat. The OEM supplies the mating
receptacle for the 3 pin plug. RV Products suggests the
thermostat wiring be minimum 18 gauge. The furnace control
circuit must not exceed 1 amp. The thermostat is equipped
with a replaceable fast-acting 2 amp fuse located on the base
of the thermostat. The fuse is designed to “open” if the
furnace is mis-wired or there is a short in the system. Before
replacing fuse, the cause of the failure must be located and
corrected.
OPERATION
The display indicates room temperature and the word ROOM
is shown on the LCD until the temperature selector is pressed;
at which time the display temporarily indicates the setpoint
temperature and the word SET is shown on the LCD. Each
time the UP arrow is pressed, the setpoint will increase. Each
time the DOWN arrow is pressed, the setpoint will decrease.
Once the temperature selector button is no longer pressed for a
few seconds, the room temperature will again be displayed, and
the word ROOM will be displayed on the LCD.
In electric heat mode, if the heat pump is unable to satisfy the
thermostat, the heat pump goes into lockout. DIFF will display
on the thermostat LCD indicating backup heating is required to
satisfy the thermostat.
In gas heat mode, the gas furnace will provide the only source
of heat and the heat pump is locked out.
NOTE
The temperature displays in degrees Fahrenheit as a factory set
default (See Figure 2). To display in degrees Celsius, move the
jumper marked “F” and “C” to bridge between middle pin and
position “C”, then cycle 12 volt power off and then back on.

4
WIRING THE WALL THERMOSTAT
OEM must supply these mating parts to connect
these thermostats per Figure 1. The plugs must be
connected to motorcoach wiring harness before the
base if secured to the wall.
Heat Pump Example To Bring On Gas Furnace As Backup Heat
Setpoint Indoor Temperature Operation
70 70+ No functions occur
\\\ 69 Heat Pump turns on (Primary heat source)
71 Heat Pump turns off (Thermostat satisfied)
69 Heat Pump turns on
65 Gas Furnace turns on, Heat Pump turns off (Heat Pump not able to
satisfy Thermostat) (First strike for backup heat counter)
71 Gas Furnace turns off (Thermostat satisfied)
69 Heat Pump turns on
65 Gas Furnace turns on, Heat Pump turns off (Heat Pump is again unable
to satisfy Thermostat), (Backup heat counter reaches 3rd strike and Heat
Pump is locked out for 2 hours), backup heat counter is reset if Heat
Pump is running for more than 20 minutes and does not call for backup
heat
71 Gas Furnace turns off (Thermostat satisfied)
69 Gas Furnace turns on (Becomes Primary heat source)
71 Gas Furnace turns off (Thermostat satisfied)
\\\ After 2 hour lockout
69 Heat Pump turns on (Resumes as Primary heat source)
65 Gas Furnace turns on, Heat Pump turns off (Becomes primary heat
source) (Heat Pump is locked out for another 2 hours)
71 Gas Furnace turns off (Thermostat satisfied)
\\\ After 2 hour lockout
69 Heat Pump turns on (Resumes as primary heat source)
71 Heat Pump turns off (Thermostat satisfied)
(Backup heat counter is reset any time Heat Pump satisfies thermostat
setpoint and does not need Gas Furnace)
The word “DIFF” will display on LCD when backup heat is operating
and the heat pump is locked out. There is a 30 second delay between
Stage 1 and Stage 2. There is also a 3 minute anti-short cycle delay time
for cooling.

5
The chart below shows the system functions with the 6536A335* thermostat. After the entire
air conditioning system (and furnace system) is installed, check each position function.
6536A335* 2-STAGE HEAT PUMP WITH BACKUP HEAT THERMOSTAT OPERATION TABLE
Mode Switch Fan Mode
Switch Fan Speed
Switch Calling Operation
1Cool Auto Lo No No functions occur in this mode
2Cool Auto Lo Stage 1
1 Degree Above Set ID fan low, compressor #1 and OD blower low
cycle as needed
3Cool Auto Lo Stage 2
2 Degrees Above Set ID fan low, compressors #1 and #2 and OD blower
high cycle as needed
4Cool On Lo No ID fan low continuous
5Cool On Lo Stage 1
1 Degree Above Set ID fan low continuous, compressor #1 and OD
blower low cycle as needed
6Cool On Lo Stage 2
2 Degrees Above Set ID fan low continuous, compressors #1 and #2
and OD blower high cycle as needed
7Cool Auto Hi No No functions occur in this mode
8Cool Auto Hi Stage 1
1 Degree Above Set ID fan high, compressor #1 and OD blower low
cycle as needed
9Cool Auto Hi Stage 2
2 Degrees Above Set ID fan high, compressors #1 and #2 and OD
blower high cycle as needed
10 Cool On Hi No ID fan high continuous
11 Cool On Hi Stage 1
1 Degree Above Set ID fan high continuous, compressor #1 and OD
blower low cycle as needed
12 Cool On Hi Stage 2
2 Degrees Above Set ID fan high continuous, compressors #1 and #2
and OD blower high cycle as needed
13 Off Auto Lo or Hi No No functions occur in this mode
14 Off On Lo No ID fan low continuous
15 Off On Hi No ID fan high continuous
16 Gas Heat Auto or On Lo or Hi No No functions occur in this mode
17 Gas Heat Auto or On Lo or Hi Stage 1 Heater will be energized to run
18 Gas Heat Auto or On Lo or Hi Stage 2 There is no provision for 2nd stage heat when
operating in the gas heat mode
19 Elec Heat Auto or On Lo or Hi No No functions occur in this mode
20 Elec Heat Auto or On Lo or Hi Stage 1 Heat pump will run ID fan high, both compressors,
OD fan high and both reversing valves
21 Elec Heat Auto or On Lo or Hi Stage 2 Backup heater will be energized to run

6
II. HEAT PUMP OPERATION SEQUENCE
COOLING MODE

7
III. HEAT PUMP OPERATION SEQUENCE
HEATING MODE

8
IV. 6535C320 PRINTED CIRCUIT BOARD
FUNCTION CHART

9
PRINTED CIRCUIT BOARD 9-PIN THERMOSTAT PLUG CONNECTOR
The figure above depicts the 9-pin printed circuit board socket as if you were looking straight at it.
NOTE
1. Pin connections in this p.c. board socket are identical to those in the
thermostat.

10
PRINTED CIRCUIT BOARD INDOOR BLOWER SECTION
Note: Both High and Low Indoor Blower speeds operate on Circuit #1
HIGH SPEED INDOOR BLOWER OPERATION
1. Begins with a call from the thermostat, 12 volt positive (+) to terminal #7 (GH) in the 9-pin connector. (Black wire at the
thermostat). The Ground (-) is Blue in terminal #4.
2. The High Speed relay closes on the board. 115 volts (HOT leg) signal should appear on Indoor Blower High Out terminal.
The 115 volt Neutral leg to the motor is not routed through the printed circuit board.
3. The 115 volts (HOT leg) power continues from terminal Indoor Blower High to the High Speed motor tap.
4. The motor starts and runs on High Speed until the signal is lost from the thermostat.
LOW SPEED INDOOR BLOWER OPERATION
1. Begins with a call from the thermostat, 12 volt positive (+) to terminal #9 (GL) in the 9-pin connector. (Purple wire at the
thermostat). The Ground (-) is Blue in terminal #4.
2. The Low Speed relay closes on the board. 115 volts (HOT leg) signal should appear on Indoor Blower Low Out terminal. The
115 volt Neutral leg to the motor is not routed through the printed circuit board.
3. The 115 volts (HOT leg) power continues from terminal Indoor Blower Low to the Low Speed motor tap.
4. The motor starts and runs on Low Speed until the signal is lost from the thermostat.

11
PRINTED CIRCUIT BOARD COMPRESSOR SECTION
COMPRESSOR #1 COOLING OPERATION
1. Begins with a call from the thermostat, 12 volt positive (+) to terminal #5 (Y1) in the 9-pin connector. (Yellow wire at the
thermostat). This call is subject to thermostat time delays. The Ground (12 VDC-) is Blue in terminal #4.
2. 12 VDC passes through the circuit board to terminals Comp 1 Coil Yellow and Comp 1 Coil Blue. (Subject to 115 VAC power
through the Circuit 1 Exclusion Relay and the Freeze Switch).
3. 12 VDC exits these terminals and goes to the Compressor #1 relay coil.
4. The Compressor Relay #1 closes.
5. Compressor #1 starts and runs until the compressor signal is satisfied at the thermostat. (What else might shut the
compressor off?)
COMPRESSOR #2 COOLING OPERATION
1. Begins with a call from the thermostat, 12 volt positive (+) to terminal #6 (Y2) in the 9-pin connector. (Orange wire at the
Thermostat). Subject to a 2-degree temperature differential and a thermostat time delay. The Ground (12 VDC-) is Blue in
terminal #4.
2. 12 VDC passes through the circuit board to terminals Comp 2 Coil Orange and Comp 2 Coil Blue.
3. 12 VDC exits these terminals and goes to the compressor #2 relay coil.
4. The compressor relay #2 closes. (Subject to available 115 VAC power).
5. Compressor #2 starts and runs until the compressor #2 signal is satisfied at the thermostat.

12
PRINTED CIRCUIT BOARD FREEZE SENSOR SECTION
INDOOR COIL SENSOR
1. The Indoor Coil Sensor terminals are connected to a thermister located in the evaporator (Indoor) coil.
2. This sensor is an active part of the circuit only in the cooling mode.
3. This sensor is ignored if “W” (Electric Heat) is energized.
4. This sensor opens if the TEMPERATURE of the INDOOR COIL (not ambient air temperature) reaches 28 degrees F. The
sensor closes at 55 degrees F.
5. If this sensor opens, the p.c. board will not output 12 volts DC to either Comp 1 terminals or the Comp 2 terminals on the
board.
OUTDOOR COIL SENSOR
1. The Outdoor Coil Sensor terminals are connected to a thermister located in the condenser (Outdoor) coil.
2. This sensor is an active part of the circuit only in the heating mode.
3. This sensor is ignored whenever “W” (Electric Heat) is NOT energized.
4. This sensor opens if the TEMPERATURE of the OUTDOOR COIL (not ambient air temperature) reaches 18 degrees F. The
sensor closes at 38 degrees F.
5. If this sensor opens, the p.c. board will shut down all Heat Pump functions.
GREEN L.E.D. LIGHT OPERATION (FREEZE SENSOR)
LED Indicators: Green Flash Codes: - - - System Normal
DOB Timer Running - - - -
ID Or OD Freeze Temp Out Of Range - - - - - - - - -
AC1 Line Voltage Out Of Range ----- ---- ----
Red: On If AC2 Voltage Is In Range And Stage 2 Is Calling

13
PRINTED CIRCUIT BOARD OUTDOOR BLOWER SECTION
LOW SPEED OUTDOOR BLOWER OPERATION
1. Begins with a 115 volt (HOT leg) signal received from AC1 to Outdoor Blower Low on p.c. board to #4 terminal on compressor
#1 relay.
2. 12 volts D.C. between yellow and blue on compressor relay #1 from thermostat and p.c. board. Closes relay and sends 115
volts AC to Outdoor Blower Low Speed terminal #2 on Comp 1 relay red wire.
3. The Outdoor Blower starts and runs on Low speed until compressor #1 goes off or the second stage cooling is energized.
HIGH SPEED OUTDOOR BLOWER OPERATION
1. Begins with a 115 volt (HOT leg) signal received from AC2 to Outdoor Blower High on p.c. board to #4 on Comp #2 relay.
2. Immediately the relays will open the circuits to Outdoor Blower Low Out, Outdoor Blower Common.
3. 12 volts D.C. signal between orange and blue on Comp #2 relay from thermostat through p.c. board. Closes Comp #2 relay
and sends 115 VAC to Outdoor Blower High terminal #2 on relay and then out black wire to outdoor blower.
4. The Outdoor Blower starts and runs on High speed until compressor #2 goes off.
PRINTED CIRCUIT BOARD HEATING SECTION
.

14
HEAT PUMP OPERATION (HEAT MODE)
1. Begins with a call from the thermostat, 12 volt positive (+) to terminal #8 (W) in the 9-pin connector. (White with Black stripe
wire at the thermostat). The Ground (-) is Blue in terminal #4.
2. The p.c. board takes over at this time and controls all functions of the heat pump.
3. 115 VAC should appear between the Rev Valve Out terminals.
4. This voltage continues to the reversing valve solenoid coils and switches both reversing valves to the heat position.
5. The High Speed Indoor Blower relay closes on the board. 115 volts (HOT leg) signal should appear on the Indoor Blower
High Out terminal. The 115 volt NEUTRAL leg to the motor is not routed through the printed circuit board.
6. The 115 volts (HOT leg) power continues from terminal to the High Speed motor tap and the motor begins to run on High
Speed.
7. 12 VDC passes through the circuit board to terminals Comp 1 Yellow and Comp 1 Blue. (Subject to 115 VAC power through
the Circuit 1 Exclusion Relay and the Outdoor Coil Sensor).
8. 12 VDC continues from terminals Comp 1 Coil to the Compressor #1 relay coil.
9. The Compressor Relay #1 closes and Compressor #1 comes on.
10. The Outdoor Blower starts on Low Speed 2-seconds later (See Outdoor Blower Section).
11. After a 30-second time delay, 12 VDC passes through the circuit board to Comp 2 Coil terminals.
12. The Compressor Relay #2 closes. (Subject to available 115 VAC power). Compressor #2 starts and runs along with outdoor
blower on High. Low drops out.
13. The unit continues in the Heating Mode until the thermostat is satisfied.

V. WIRING DIAGRAM - 6536 SERIES TWO TON PACKAGED HEAT PUMP
This manual suits for next models
1
Table of contents
Other RVP Heat Pump manuals
Popular Heat Pump manuals by other brands

Harmopool
Harmopool Harmo PAC Series instruction manual

Fujitsu
Fujitsu WATERSTAGE WOYG112LHT Maintenance Document

Raypak
Raypak 6350 Series Installation & operating instructions

Sanyo
Sanyo ECO-i WCHDZ32053 datasheet

HIdRos
HIdRos LSA/HP Series Technical manual

Fondital
Fondital WHDHP 300 SSH Installation, use and maintenance handbook

Dimplex
Dimplex SI 22TU Installation and operating instructions

Daikin
Daikin ERGA04DAV3A Installer's reference guide

Zodiac
Zodiac Z550iQ Instructions for installation and use

Trane
Trane 4TTA4 Installation and operation manual

Vaillant
Vaillant geoTHERM SERIES operating instructions

LG
LG MULTI-V SE Series owner's manual