manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Safe Signal
  6. •
  7. Security Sensor
  8. •
  9. Safe Signal WFDTNA User manual

Safe Signal WFDTNA User manual

SS-200-036 1 I56-4165-D
WFDTNA Vane-type Water ow Detectors
INSTALLATION AND MAINTENANCE INSTRUCTIONS
SPECIFICATIONS
Contact Ratings: Two sets of SPDT (Form C); 10 A @ 125/250 VAC ; 2.5 A @ 24 VDC
Triggering Threshold Bandwidth (Flow Rate): 4 – 10 GPM
Static Pressure Rating: 375 PSI (Max.)
Dimensions, Installed: WFDTNA – 4in H x 3½ in W x 6¾ in D
Operating Temperature Range: 32°F to 120°F (0°C to 49°C)
Enclosure Rating: WFDTNA – NEMA Type 4, as tested by Underwriters Laboratories, Inc. (UL) (IP56)
The WFDTN can be installed between 2×4 stud wall construction.
IMPORTANT
Please Read Carefully And Save
This instruction manual contains important information about the installation and
operation of water flow detectors. Purchasers who install water flow detectors for use
by others must leave this manual or a copy of it with the user. Read all instructions
carefully before beginning.
CAUTION
The model WFDTNA is a vane-type water flow detector for use in wet-pipe fire sprin-
kler systems only. Vane-type water flow detectors shall not be used as the sole initiat-
ing device in both deluge and preaction systems; water flow detectors used in these
types of systems may result in an unintended discharge caused by a surge, trapped air
or a short retard time.
WARNING
Installation must be performed by qualified personnel and in accordance with all na-
tional and local codes and ordinances.
Shock hazard: Disconnect power source before servicing. Serious injury or death
could result.
Risk of explosion: Not for use in hazardous locations. Serious injury or death could
result.
PRINCIPLES OF OPERATION
Vane-type water flow detectors mount to water filled pipes in fire sprinkler systems.
Water flow in the pipe deflects a vane. Deflection of the vane produces a switched
output, usually after a specified delay.
All WFDTNAs have a pneumatically controlled mechanical delay mechanism. Delays
do NOT accumulate; they reset if the flow of water stops or drops below minimum
triggering flow rate before the entire delay has elapsed. All detectors will activate on
a sustained flow of water of 10 gallons per minute (gpm) or greater downstream of
the device.
COMPATIBLE PIPE TEES/RISERS
The WFDTNA is supplied with 12 paddles. One paddle is provided for each size of
the threaded, sweat or plastic tee. See Figure 1 and approximate tee depth chart. Each
paddle has an indication that shows the pipe size and type of tee to be used with. The
WFDTNA also fits 1", 1½", and 2" Reliable riser manifolds when used with paddle
tree P02-0032-300 (purchased separately).
APPROXIMATE TEE DEPTH REQUIREMENTS (SEE FIGURE 1)
Tee Depth readed Sweat CPVC CPVC/Spears/
NIBBCO CPVC/Tyco/NIBBCO
1 × 1 × 1˝ 21/8˝13/4˝21/4˝215/32˝213/16˝
11/4× 11/4 × 1˝ 21/2˝21/8˝N/A N/A N/A
11/2× 11/2 × 1˝ 23/4˝21/4˝N/A N/A N/A
2 × 2 × 1˝ 31/4˝23/4˝N/A N/A N/A
FIGURE 1. MOUNTING DIMENSIONS:
3-1/2"
2-5/8"
4"
TEE DEPTH
DESIGNED TO FIT WITHIN 2 X 4 STUD WALL CONSTRUCTION
PLASTIC VANE
TEE FITTING
INSTALLA
TION GAUGE
END OF PADDLE TREE MUST
FIT BETWEEN TOP OF TEE
AND BOTTOM OF FLANGE
TEE
ADAPTER
INSTALLATION GUIDELINES
Before installing any water flow alarm device, be thoroughly familiar with:
NFPA 72: National Fire Alarm Code
NFPA 13: Installation of Sprinkler Systems
NFPA 25: Inspection, Testing, and Maintenance of Water-based Fire Protection
Systems, Section 5.3.3.2
NFPA 13D: Standard for 1 and 2 Family Dwellings and Manufactured Homes
NFPA 13R: Standard for Multi-family Dwellings
CAN/ULC S524: Installation of Fire Alarm Systems
Also, follow other applicable NFPA and ULC standards, local codes and the require-
ments of the authority having jurisdiction.
W039000
SS-200-036 2 I56-4165-D
Failure to follow these directions may result in failure of the device to report a water
flow condition. Safe Signal is not responsible for devices that have been improperly
installed, tested or maintained.
1. Mount the detector where there is adequate clearance for installation and re-
moval and a clear view of it for inspection. See Figure 1 for mounting dimen-
sions.
2. Locate the detector 6 to 7 feet above the floor to protect from accidental damage.
3. On horizontal runs, position the detector on top or side of the pipe. Do not
mount it upside down because condensation may collect in the housing and
impair the operation of the detector.
For vertical flow applications, mount detector on pipe where upflow conditions
exist. Failure to do so may prevent unit from operating properly.
4. Mount detector at least 6 inches from a fitting which changes the direction of
the water flow, or no less than 24 inches from a valve or drain.
5. BE SURE DIRECTION-OF-FLOW ARROW AND DIRECTIONAL COVER
MATCHES ACTUAL DIRECTION OF FLOW IN THE PIPE. See Figure 5.
FIGURE 2. ASSEMBLY DIAGRAM:
FLOW
COVER TAMPER
SWITCH (OPTIONAL P/N CTS)
COVE
R
TIMER
ASSEMBLY
(P/N FS-R
T)
GASKET
ACTUATOR
LEVER
WATERFLOW
GROUND SCREW
MOUNTING
PLATE
PADDLE
1" NPT
THREAD
TAMPER PROOF
WRENCH (P/N WFDW)
FILISTER HEAD
SCREW
MOUNTING INSTRUCTIONS
1. The WFDTNA water flow detector is designed to fit only the appropriate tee
fitting.
NOTE: The outlet branch of tee must have a 1-inch NPT thread. Do not use a
reducer to achieve the correct thread size. Failure to follow this instruction will
result in failure of the detector to report a water flow condition.
2. WFDTNA units are shipped without paddles mounted to the actuator. Select
the correct size paddle for the type of tee being used. Align hole on stem of
paddle with hole on actuator lever. Fasten together using a #4-40×3/8-inch fil-
lister head screw supplied in bag assembly. See Figure 2. Use only the screw
provided with the unit. Drive screw head through hole in paddle until it seats
to actuator lever surface. No washer is required. For paddle replacement refer to
Maintenance section.
3. Carefully roll the vane opposite the direction of flow and insert through tee.
Thread detector onto tee fitting and tighten with wrench. Use of thread seal-
ant or tape is recommended. Use height gage (located at end of paddle tree) to
ensure proper depth of detector on tee fitting. See Figure 1. Height gage must fit
between top of tee fitting and under side of hex tee adapter. A gap between gage
and tee adapter is acceptable. When correctly installed, the detector must face
in the proper direction of water flow and be aligned with the pipe, the provided
directional cover illustrates flow direction for device.
4. Remove the cover. Move the actuator lever back and forth to check for binding.
If the vane binds, remove the detector and correct the problem before proceed-
ing.
CAUTION
Be sure the direction-of-flow arrow and directional cover point in the right direction, other-
wise a water flow condition will go unreported. See Figure 2 and Figure 5.
PREOPERATION TESTING
1. Fill the sprinkler system with water and check for leaks around the WFDTNA.
If there is a leak, check to see that the fittings are tight. If leak persists, drain the
system and remove the detector (see removal instructions under Maintenance).
Check for damaged threads or cracked fitting. Reinstall the detector and check
again for leaks. Do not proceed until all leaks have been stopped.
2. Connect an ohmmeter or continuity tester across (COM and B-NO) terminal
switch contacts. The ohmmeter should show an open circuit, no continuity.
3. Deflect the actuator lever and hold it until the pneumatic delay shaft releases the
switch buttons. The ohmmeter or continuity tester should show a short circuit
after the delay has elapsed. If there is no delay, check the setting of the delay
adjustment dial.
FIELD WIRING
WARNING
High Voltage. Electrocution Hazard. Do not handle live AC wiring or work on a de-
vice to which AC power is applied. Doing so may result in severe injury or death.
When utilizing switches at voltages greater than 74VDC or 49VAC
means to provide all–pole disconnection must be incorporated in the fixed wiring,
such as a circuit breaker.
1. The WFDTNA has two SPDT switches. Switch contacts (COM and B-NO) are
closed when water is flowing and open when water is not flowing. Connect the
switches as shown in Figure 6 depending on the application.
2. When connected to a listed sprinkler/fire alarm control panel, the initiating cir-
cuit must be unable to be silenced.
3. A ground screw is provided with all units. When grounding is required, clamp
wire with screw in hole located between conduit entrance holes. See Figure 3.
4. Use proper waterproof conduit fittings where required.
W038800
SS-200-036 3 I56-4165-D
FIGURE 3. KNOCKOUT PLUG REMOVAL:
GROUND
GROUND
SCREW
SCREW
W038301
MECHANICAL DELAY ADJUSTMENT
The pneumatic delay is preset at approximately 30 seconds at the factory. To adjust the
delay, turn the adjustment dial on the delay mechanism. Turn clockwise to increase
the delay, counterclockwise to decrease the delay. Delay can be adjusted over a range
from 0-90 seconds maximum. See Figure 4. As a point of reference when setting time
delay in dark environments the notch in the dial indicates an approximate 30 second
time delay and the larger of the three tabs indicates an approximate 60 second time
delay.
NOTE: Set the delay to the minimum required to prevent false alarms due to flow
surges.
After extended service, parts of the detector may become worn reducing the time de-
lay and causing false alarms. If this happens, increase the delay. If the delay is already
at maximum, replace the mechanical delay assembly. Refer to Maintenance section
for ordering replacement parts.
OPERATIONAL TESTING
Always notify a central station monitoring water flow alarms before repairing, main-
taining or testing water flow alarm devices.
1. Replace the cover and tighten the security screws with the tamper proof wrench.
Store the wrench in a secure place.
2. Open the inspector’s test valve and time how long it takes for the detector to
indicate a flow condition. The detector should remain activated until the inspec-
tor’s test valve is closed. Air pockets in the sprinkler system may increase the
apparent time delay.
FIGURE 4. DELAY ADJUSTMENT DIAL:
NOTE: RETARD TIME MAY EXCEED 90 SECONDS. ADJUST
AND VERIFY THAT TIME DOES NOT EXCEED 90 SECONDS.
NUMBER ON DIAL IS APPROXIMATE TIME DELAY IN SECONDS
DELAY
ADJUSTMENT
DIAL
W038500
MAINTENANCE
To prevent accidental water damage, control valves should be shut tightly and the sys-
tem completely drained before water flow detectors are removed or replaced.
Inspect detectors in accordance with applicable ULC codes and standards and/or the
authority having jurisdiction for leaks and replace if leaks occur. Test detectors at least
quarterly as described under Operational Testing to insure proper operation. Test
more often if required by the authority having jurisdiction.
Under normal conditions Safe Signal water flow detectors should provide years of
trouble-free service. However, if the delay mechanism becomes faulty, a replacement
kit is available. To replace the delay mechanisms, request Part No. FS-RT. Complete
instructions are enclosed with replacement parts. The delay mechanism can be easily
replaced without removing the detector from the pipe or draining the pipe. If damage
occurs to paddle, order replacement kit, request Part No. PRK9. Refer to procedure
below for removal of detector on pipe. Do not repair or replace any other water flow
detector components in the field. If any other part of the detector does not perform
properly, replace the entire detector. Failure to follow this instruction may result in
failure of the detector to report a water flow condition.
Proceed as follows to remove a detector.
1. Drain the pipe.
2. Turn off electrical power to the detector, and then disconnect wiring.
3. Unscrew WFDTNA from tee fitting.
4. Lift detector clear of pipe.
CAUTION
If a vane breaks off in a pipe, find and remove it. Failure to do so may restrict the
proper flow of water to part of the sprinkler system.
FIGURE 5. DIRECTIONAL COVER:
NOTCHED COVER INDICATES FLOW DIRECTION AT A
DISTANCE FROM MULTIPLE VIEWING ANGLES
W038200
SS-200-036 4 I56-4165-D
1. Water flow detectors may not work or operate properly if sprinkler piping being monitored
is plugged with pipe scale, mud, stones or other foreign material. Sprinkler systems should
be checked regularly for such blocking material, following the instructions in Chapter 5 of
NFPA Standard 13A and CAN/ULC S536.
2. Alarms generated by the activation of water flow detectors may not be received by a central
station if telephone or other communication lines to the detector are out of service, disabled,
or open.
3. Vane-type water flow detectors have a normal service life of 10-15 years. Hard water sys-
tems, however, may substantially reduce water flow detector service life.
WARNING
THE LIMITATIONS OF WATER FLOW ALARM DEVICES
4. Water flow detectors are not a substitute for insurance. Building owners should always
insure property and lives being protected by sprinkler systems.
5. If valves controlling the water supply to a sprinkler system are closed, vane-type water flow
detectors will not work. All valves controlling a sprinkler water supply should be sealed or
locked in the normally open position. The normally open position should be monitored by
a sprinkler supervisory switch.
Please refer to insert for the Limitations of Fire Alarm Systems
FIGURE 6. FIELD WIRING:
CONTACT RATINGS
125/250 VAC 10 AMPS
24 VDC2.5 AMPS
ULC-LISTED
COMPATIBLE
CONTROL PANEL
POWER
24VDC
OR
120VAC
INITIATING
LOOP
SSM24-X
SSV120-X
NOTE: COMMON AND B-NO
CONNECTIONS WILL CLOSE
WHEN VANE IS DEFLECTED, I.E.,
WHEN WATER IS FLOWING. DUAL
SWITCHES PERMIT
APPLICATIONS TO BE COMBINED
ON A SINGLE DETECTOR.
SCHEMATIC OF
INDIVIDUAL
SWITCH IN
"NO WATERFLOW"
CONDITION
BREAK WIRE AS
SHOWN FOR
SUPERVISION OF
CONNECTION. DO
NOT ALLOW
STRIPPED WIRE
LEADS TO EXTEND
BEYOND SWITCH
HOUSING. DO NOT
LOOP WIRES.
A-NC
B-NO
COM
SUGGESTED EOL
RESISTOR
+
-
+
-
W039300
THREEYEAR LIMITED WARRANTY
SAFE SIGNAL warrants that the equipment herein shall conform to said descriptions as to all af-
firmation of fact and shall be free from defects of manufacture, labeling, and packaging for a pe-
riod of three (3) years from the invoice date to the original purchaser, provided that representative
samples are returned to SAFE SIGNAL for inspection. Upon a determination by SAFE SIGNAL
that a product is not as warranted, SAFE SIGNAL shall, at its exclusive option, replace or repair
said defective product or parts thereof at its own expense except that Purchaser shall pay all
shipping, insurance, and similar charges incurred in connection with the replacement of the
defective product or parts thereof. This Warranty is void in the case of abuse, misuse, abnormal
usage, faulty installation, or repair by unauthorized persons, or if for any other reason SAFE
SIGNAL determines that said product is not operating properly as a result of causes other than
defective manufacture, labeling, or packaging.

Other Safe Signal Security Sensor manuals

Safe Signal WFDTNRN User manual

Safe Signal

Safe Signal WFDTNRN User manual

Safe Signal WFDNFT User manual

Safe Signal

Safe Signal WFDNFT User manual

Safe Signal WFDTN User manual

Safe Signal

Safe Signal WFDTN User manual

Safe Signal WFDN User manual

Safe Signal

Safe Signal WFDN User manual

Safe Signal WFD20EN User manual

Safe Signal

Safe Signal WFD20EN User manual

Safe Signal WFDNFS User manual

Safe Signal

Safe Signal WFDNFS User manual

Popular Security Sensor manuals by other brands

Ltech HS-ZB-A manual

Ltech

Ltech HS-ZB-A manual

Quandify CubicDetector QCD01 manual

Quandify

Quandify CubicDetector QCD01 manual

Satel SLIM-PIR-PRO manual

Satel

Satel SLIM-PIR-PRO manual

Schonstedt SPOT instruction manual

Schonstedt

Schonstedt SPOT instruction manual

Teledata SF2000 quick start guide

Teledata

Teledata SF2000 quick start guide

RKI Instruments GX-2012 Operator's manual

RKI Instruments

RKI Instruments GX-2012 Operator's manual

GMI D1180D instruction manual

GMI

GMI D1180D instruction manual

Sinfonia Technology EA-15B quick start guide

Sinfonia Technology

Sinfonia Technology EA-15B quick start guide

STI STI-1215 manual

STI

STI STI-1215 manual

EMX CarSense 303 instruction manual

EMX

EMX CarSense 303 instruction manual

BEMKO SES24WH instructions

BEMKO

BEMKO SES24WH instructions

Falltech SteelGrip Temporary Cable Horizontal... User instruction manual

Falltech

Falltech SteelGrip Temporary Cable Horizontal... User instruction manual

Sealey VS600.V2 instructions

Sealey

Sealey VS600.V2 instructions

ADT Safewatch Plus quick guide

ADT

ADT Safewatch Plus quick guide

Shelly Shelly Motion manual

Shelly

Shelly Shelly Motion manual

FIBARO FGDW-002 user manual

FIBARO

FIBARO FGDW-002 user manual

Kolibri Bishop user manual

Kolibri

Kolibri Bishop user manual

Emos M0007A manual

Emos

Emos M0007A manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.