Sage SIP Guide

SAGE THERMAL GAS MASS LOW METER
Operations and
Instruction Manual
or Prime Models SIP and SRP
DOCUMENT NUMBER 100-0065
REVISION 16 - SIP/SRP (SAGE PRIME™)
Make the Wise Choice.
Choose Sage low Meters.
SAGE METERING, INC.
8 Harris Court, D1
Monterey, CA 93940
1-866-677-SAGE (7243)
Tel 831-242-2030
Fax 831-655-4965
www.sagemetering.com


O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l 3
S A G E M E T E R I N G , I N C .
R V. 16-SIP/SRP
Table of Contents
Introduction Wel ome . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
SECTION A Unpa king Your Sage Meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Getting Started Maintenan e . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Installation and Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Lo ating Proper Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Insertion Flow Meter Appli ation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Sage Valve Assembly Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Compression Fitting Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Installation Instru tions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Captive Flow Conditioners . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Probe Insertion Guideline Drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Installation Depth Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Large Du t or Sta k Appli ations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
In-line Flow Meter Appli ation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Terminal Hookup Prime Integral (Series SIP) . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
24 VDC Prime Integral Terminals Series SIP . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
AC Powered Prime and DC Powered Prime PLUS
Integral Terminals (Series SIP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Terminal Hookup Prime Remote (Series SRP). . . . . . . . . . . . . . . . . . . . . . . . . . . 21
24 VDC Prime Remote Terminals (Series SRP) . . . . . . . . . . . . . . . . . . . . . . . . . . 22
AC Powered Prime and DC Powered Prime PLUS
Remote Series Terminals (Series SRP). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Jun tion Box Wiring Terminals for Remote Style Meters . . . . . . . . . . . . . . . . . 24
SECTION B Prin iple of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Specifications Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Sage PRIME Styles & Spe ifi ations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Sage PRIME Organi (OLED) Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Approvals. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
SECTION C SIP Series Integral Style Flow Meters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Drawings SRP Series Remote Style Flow Meters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Remote Bra ket Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Mounting Hardware:
SVA05 Series Isolation Valve Assembly for Insertion Meters . . . . . . . . . . . . 38
STCF Series Teflon Ferrule Compression Fitting . . . . . . . . . . . . . . . . . . . . . . 38
SVA05 Series Isolation Valve Assembly Detail . . . . . . . . . . . . . . . . . . . . . . . . 38
Mounting Plate for Thin Walled Du ts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
continued on next page

S A G E M E T E R I N G , I N C . O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
4
R V. 16-SIP/SRP
SECTION C SVA05LP Low Pressure Isolation Valve Assembly. . . . . . . . . . . . . . . . . . . . . . . . 39
Drawings In-Line and Insertion Flanges. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
SECTION D Common Diagnosti s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Diagnostics In-Situ Calibration Che k . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
SECTION E Limited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Warranties and Service Work Can ellation/Return Poli y. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Returning Your Sage Flow Meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Return Material Authorization Form . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
SECTION F Modbus Register Listing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Modbus Modbus Proto ol & Fun tion Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Sage Register Output Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Sage Addresser Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Sage Addresser Typi al Printout (Version 3.14) . . . . . . . . . . . . . . . . . . . . . . . . . 62
SECTION G Sage Prime™ Field Programmable “Dongle” . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Appendix Corre tion Fa tors For Varying Gas Mixes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Installations Where Pipe Condensation May Develop . . . . . . . . . . . . . . . . . . . 66
J-Box and Upstream Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
What Is a Thermal Mass Flow Meter? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68

O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l 5
Welcome
We are pleased that you have pur hased a Sage Metering Mass Flow Meter for your
requirement. We hope that you are satisfied with the performan e, operation and
design of our highly pre ise, NIST tra eable Thermal Gas Mass Flow Meter.
Sage Metering is your sour e for monitoring, measuring and ontrolling the gas mass
flow in your industrial pro ess, building management system or environmental appli -
ation. Our high performan e, NIST Tra eable,Thermal Mass Flow Meters will help
in rease produ tivity, redu e energy osts, maximize produ t yields, and/ or help redu e
environmental insult. Sage provides high quality In-Line and Insertion Thermal Mass
Flow Meters for a wide variety of industrial, ommer ial, and environmental monitoring
needs, in luding arbon redit verifi ation for Greenhouse Gas redu tion.
Sage Meters measure mass flow dire tly — there is no need for an illary instrumentation
su h as temperature or pressure transmitters. Furthermore, our instruments have ex ep-
tional signal sensitivity, have no moving parts, require little if any maintenan e, have
negligible pressure drop and have a turndown up to 100 to 1, and resolve as mu h as
1000 to 1. Sage Flow Meters an measure the mass flow rate and onsumption of air,
oxygen, natural gas, nitrogen, digester gas, biogas, flare gas, hydrogen, argon, arbon
dioxide and other gases and gas mixes.
Sage Prime is the latest addition to our family of high performan e Thermal Mass Flow
Meters. It features a bright graphi al display of Flow Rate,Total and Temperature, robust
industrial en losure, and easy to a ess power and output terminals. Sage Prime has a
dual- ompartment windowed en losure featuring a very high ontrast photo-emissive
OLED display with a new photo ell a tivated S reen Saver. The rear ompartment,
whi h is separated from the ele troni s, has large, easy to a ess and well marked ter -
minals, for ease of ustomer wiring. It is powered by 24 VDC (12 VDC optional, or
115/230 VAC). The power dissipation is under 2.5 watts (e.g. under 100 ma at 24 VDC
for the DC version.)
Please let us know if we an assist you in any way with your Sage Meter, or if you
have any questions about its installation, operation, or features. Simply phone us at
866-677-SAGE (7243), or visit our website at www.sagemetering. om to onta t a
fa tory representative in your area. (To a ess this manual on the website, enter in
user name: sage; pass ode 7243737 when prompted.)
Sin erely,
Robert Steinberg
President
S A G E M E T E R I N G , I N C .
R V. 16-SIP/SRP


Section
GETTING STARTED
A


O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
UNPACKING YOUR SAGE METER
Your Sage flow meter is a sensitive, yet rugged,
pre ision built ele troni instrument. Upon delivery,
are should be taken when opening the shipping
ontainer and removing your meter. The meter
should be inspe ted for any damage that may have
o urred during transit. If damage is found, please
onta t the arrier immediately to pla e a laim for
damaged goods. The ontents of the ontainer
should be he ked against the pa king list for any
dis repan ies. If there are any questions as to the
ontents or onfiguration of the equipment in lud-
ing alibration ranges, or, mounting hardware,
onta t Sage Metering as soon as possible. Please
save shipping ontainer and pa kaging materials
(in luding PVC tube probe prote tor on Sage
Insertion Flow Meters) in ase the unit needs to
be returned for any reason.
MAINTENANCE
Sage thermal mass flow meters essentially require
little or no maintenan e. While the sensing element
is somewhat resistant to dirt and parti ulate build
up, it may be ome ne essary to lean it from time to
time if mounted in extremely dirty environments.
NOTE: ALWAYS REMOVE THE POWER PRIOR TO
ANY CLEANING OR MAINTENANCE. A detergent or
appropriate non- orrosive solvent for removing the
buildup may be required. A soft brush an be used
to gently lean the sensing element’s surfa e, using
aution to avoid damaging the sensor elements
(the RTDs). If any disassembly is ne essary, onta t
Sage Metering, In . for instru tions. In general, it is
recommended t at your Sage T ermal Mass Flow
Meter be returned to t e factory if cleaning,
repair, or recalibration is needed. T is is usually
t e most cost-effective and reliable alternative.
CALIBRATION
Sage Prime has ontinuous diag nosti s. The raw
ali bration milliwats (mw) is always displayed in the
upper left hand orner of the meter's display. At any
time, you an he k this reading at a “no flow” on-
dition and ompare the reading to the original re -
ported “zero flow” value noted on the last few lines
of your meter’s Certifi ate of Conforman e or the
flow meter’s data tag. This diagnosti pro edure not
only he ks the sensor performan e and the “live
zero” alibration point, but it verifies that the sensor
is lean. It essentially provides a means to validate
the meter’s performan e, verifies that there is no shift
or drift, and eliminates the need for annual fa tory
alibrations. This simple field diagnosti pro edure
also verifies that the sensor is free from ontamina-
tion, even without inspe tion. See “In-Situ
Calibration Che k” on page 46.
Getting Started
9
S A G E M E T E R I N G , I N C .
R V. 16-SIP/SRP
aCAUTION cable glands shipped with unit are for shipping purposes only.
Remove shipping cable glands before installing.
aCAUTION If installing in a Class I hazardous location the installation
must comply with appropriate electrical codes.
aCAUTION Installer must supply proper ground and bond wire for the
transmitter and the sensor per appropriate electrical codes

S A G E M E T E R I N G , I N C . O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
10
INSTALLATION AND MOUNTING
■Che k the Certifi ate of Conforman e in luded
with your Sage Thermal Mass Flow Meter for
system pressure, temperature, gas omposition,
power input, and signal output.
■It is re ommended that the flow meter be inserted in
a lo ation of maximum straight run. It is suggested
that there be a minimum of 15 pipe diameters of
straight run upstream, and 5 diameters downstream,
depending on the onditions. See hart on page 11.
Note, obstru tions su h as valves, blowers, expand -
ers and PVC and HDPE pipes will require addition-
al straight run ( onta t fa tory for assistan e).
■Che k the orientation1: Standard alibration flow
dire tion is left to right when fa ing the flow
meter. Gas flow dire tion is marked with an arrow
on in-line flow meters; UPSTREAM is marked on
insertion probes.
■Do not rotate probe1, or errors may o ur. If en lo-
sure is fa ing in orre tly, rotate the en losure 180˚,
but do not rotate the probe. The UPSTREAM mark
still needs to be fa ing Upstream.
■Hook up the system per the wiring diagram provid-
ed with your Sage flow meter (see inside of rear
ompartment over for terminal designation).
Double he k that wiring for the proper power and
signal onne tions are orre t.
■Che k that all plumbing and ele tri al hook-ups
are in a ordan e with OSHA, NFPA, and all other
safety requirements.
■For Remote Style Meters (SRP) be sure t e Remote
Electronics is matc ed wit t e Transmitter’s
Junction Box and its attac ed Probe or Flow
Body. T ere will be Metal Serial Number Tags
on bot t e Transmitter as well as t e Remote
Electronics enclosure. Do not mismatc t e seri-
al numbers of t e Remote Electronics and t e
Junction Box, or calibration errors will occur.
LOCATING PROPER WIRING DIAGRAM
1) Look at the sti ker on your meter. The first three
digits des ribe the basi model that you have.
Refer to the appropriate page numbers below for
your wiring diagram
2) SIP: see page 19
3) SRP: see page 22 for input/output terminals;
see page 24 (Jun tion Box Wiring Terminals
for Remote Style Meters)
WIRING
Follow the instru tions below to remove the rear ap
for wiring. CAUTION: Do not open the display side!
Before removing the rear ap to a ess the wiring
terminals it is essential to ompletely remove the
s rew assembly on the side of the rear en losure to
free up the threads so the lid an be removed. Note
there is a Red Tag atta hed to the s rew assembly
stating “Remove Screw Before Opening Lid”.
After the wiring is ompleted (see pages 18 to 23
for wiring details), please lose the lid, and reinsert
the s rew assembly in the same manner.
Note: See “Approvals” page for Hazardous Location
Approvals (DC Powered Meters Only)
R V. 16-SIP/SRP
1The Integral Style of Sage Prime Insertion Meters have the Display oriented as shown on page 14.
If an alternate orientation of the display or enclosure is required (ie. installation into a vertical pipe)
please furnish a sketch or drawing and specify “ROTATE” on purchase order. However if it is later
determined that the enclosure needs to be rotated that procedure can be done in the field. However
if the display needs to be rotated then the meter must be sent back to Sage to be modified. Do not
attempt this in the field. An RMA will be required prior to returning the meter (see page 51). The
procedure for rotating the enclosure is as follows: Clamp the enclosure of the Prime in a vise with the
probe pointing up to the ceiling. Then take a 7/8 wrench and turn the probe to the proper orienta-
tion. Lock the probe into its new position with a set screw (not provided).

O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l 11
S A G E M E T E R I N G , I N C .
R V. 16-SIP/SRP
LOW PRO ILE AND INSTALLATION
CONSIDERATIONS
Insertion Flow Meters, although generally easier to
install that In-Line Flow Meters, require proper
installation, and a well developed flow profile, in
order to perform properly. Please refer to the se tion
on the following pages titled PROBE INSERTION
GUIDELINE DRAWING (page 14) and INSTALLA-
TION DEPTH CHART (page 15).
SAGE VALVE ASSEMBLY OPERATION
Valve assemblies (SVA05 and SVA05LP) are an op -
tional mounting hardware for Insertion Style Flow
Meters (see pages 38 and 39). They allow the removal
of insertion-style meters for servi e, leaning, re ali -
bration, relo ation, et . without the need to “shut-
down” your pro ess. The probe insertion depth is
adjustable to permit sensor to be lo ated at enter
to optimize measurement a ura y. (Refer to PROBE
IN SERTION GUIDE LINE DRAWING and CHART, pages
14 & 15.) The ball valve will seal off leaks of the
pro ess gas at the point of insertion after the probe
assembly has been removed. The assembly in ludes
a valve, threadolet, ompression fitting with Teflon
ferrule, a able restraint, and two ollar lamps.
A threaded half oupling (3/4" FNPT) properly sized
to a om modate the isolation valve retra tor assem-
bly must be fitted to the pipe/du t to whi h the
insertion probe will be inserted. Avoid T-Fittings
since t ey will disturb t e flow profile, and effec-
tively reduce t e measurement area. Dire t thread-
ing together (or with ne essary bushings) of the
retra tor assembly may be required. In other ases,
the threadolet must be welded in pla e and a lear-
an e hole must be drilled through the pipe/ du t to
a ept the probe assembly. If t e pipe/duct is under
pressure during installation, a ot tap drill (not
available t roug Sage Metering) may be required.
LOW CONDITIONING AND STRAIGHT RUN
Although a minimum of 15 pipe diameters of
upstream straight run is ommonly re ommended,
to absolutely assure that the flow profile is well
developed at the point of measurement, either use
Flow Conditioners (standard in Sage In-Line Flow
Meters, 1/2" and larger, and also available as assem-
blies for Insertion Flow Meters, see page 13), or
onsider additional straight run. The Chart below
provides examples of the amount of straight run
that would virtually assure that there are no flow
disturban es at the point of measurement.
N O T E :
Detailed
Drawings
are shown
on pages
38 & 39.
Insertion low Meter Application
MPORTANCE OF FLOW COND T ON NG
Recommended Pipe Diameters Upstream
One 90˚ Elbow
Two 90˚ Elbows
in the same plane
Two 90˚ Elbows
in different planes
4:1 Area Reduction
4:1 Area Expansion
Multiple Disturbance
3
5
9
3
10
TBD
1
This column applies to In-Line Flow Meters which come standard with built-in Flow Conditioners as well as Insertion Meters
when provided with upstream Captive Flow Conditioners (see page 13).
D S T U R B A N C E
15
20
At least 40
15
At least 30
To Be Determined
W THOUT
FLOW COND T ON NG
Minimum ndustry
Recommendation
WITH FLOW
COND T ON NG1
Sage
Recommendation

S A G E M E T E R I N G , I N C . O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
12
R V. 16-SIP/SRP
COMPRESSION ITTING OPERATION
A bored through tube fitting, properly sized to
a ommodate an insertion probe’s parti ular OD,
an be provided by the user or pur hased as an
option from Sage Metering (see page 38). Prior to
installation, a learan e hole to a ommodate the
insertion probe assembly must be drilled in the
pipe/du t. A fitting (1/2" FNPT) is then welded in
pla e or threaded into the half-threadolet whi h has
been welded to the pipe/du t. The probe insertion
depth is adjustable to permit sensor to be lo ated at
enter, to optimize measurement a ura y. (Refer to
PROBE INSERTION GUIDELINE DRAWING and
CHART, pages 14 & 15.)
nsert the probe shaft tubing into the
compression fitting to the position indicated
in the Probe nsertion guidelines.
While holding the fitting body steady,
tighten the nut one and one-quarter
turns to the 9 o’clock position.
INSTALLATION INSTRUCTIONS
1. Insert tubing into the tube fitting.
2. Make sure that the tubing is positioned properly
per the PROBE INSERTION GUIDELINE DRAW-
ING AND CHART, pages 14 & 15.
3. Due to t e variations of tubing diameters, a
common starting point is desirable. T erefore,
tig ten t e nut until t e tubing will not turn
by and or move axially in t e fitting.
4. S ribe the nut at the 6 o’ lo k position.
5. While holding fitting body steady, tighten the nut
11⁄4turns to the 9 o’ lo k position.

O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l 13
S A G E M E T E R I N G , I N C .
ANSI Class Flanges
(user supplied)
Largest of the
Two Perforated
Plates
Flow Conditioning
Assembly is
inserted here.
One Pipe
Diameter
FLOW
Gaskets
One Pipe
Diameter
Straight Run Requirement
from this Flange
CAPTIVE LOW CONDITIONERS
Can Be Installed in Conjunction with Insertion Style low Meters
NOTE: The larger of the two perforated plates of the Sage
Flow Conditioning assembly is positioned between two flanges
and two gaskets as shown. The smaller of the two perforated
plates of the conditioner will freely slide into the application
pipe, facing downstream. The probe mounting hardware will be
placed one diameter downstream of the downstream plate.
Probe location must be one pipe ID diameter downstream of
Flow Conditioners or errors will occur.
Front View of one of the Conditioning Plates
IMPORTANT T e location of t e probe must be exactly one pipe ID diameter (i.e., 4” in a 4” pipe; 6” in
a 6” pipe, etc.) downstream of t e Captive Flow Conditioning assembly. T e Captive Flow Conditioners
are always designed to be separated by one pipe diameter. See drawing below. T e probe location must
be one pipe ID diameter downstream of Flow Conditioner, or errors will occur.
Note: See table on page 11
(last Column) for Straig t Run
Requirement

S A G E M E T E R I N G , I N C . O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
14
R V. 16-SIP/SRP
PROBE INSERTION GUIDELINE DRAWING1
Choose the longest straight-run se tion of pipe avail-
able to allow a uniform, well-developed flow profile.
Allow for a minimum of 15 pipe diameters of straight
run upstream, and 5 diameters downstream, depend-
ing on the onditions. See hart on page 11. Note,
obstru tions su h as valves, blowers expanders and
PVC and HDPE pipes will require additional straight
run ( onta t fa tory for assistan e). Avoid, if possible,
installations immediately downstream of bends, fans,
nozzles, heaters and espe ially valves, or anything
else installed in the line that may ause nonuniform
flow profiles and swirls. Otherwise signal output
errors ould result, unless signifi antly more straight
run is provided, or in the absen e of suffi ient straight
run, Flow Conditioners (page 13) are in stalled ( on-
ta t Sage for assistan e if needed). Refer to page 13 to
see the benefits of in orporating Flow Conditioners.
Insertion styles are available through Sage Metering,
In . with a standard 1/2" OD probe support assem-
bly; 3/4" is also available. Stan dard probe lengths
are 6", 12", 15", 18", 24", 30", 36" and 48". A ommon
method of mounting the probe assembly through
a pipe wall or du t (if ambient air) is with a ompres-
sion fitting (STCF05). A Sage valve assembly (SVA05)
is useful and highly re ommended for
pressurized appli ations or other gases,
su h as Natural Gas. Flange mounting
is optionally available.
Sage insertion style flow meters an be assembled
and alibrated for use in virtually any size pipe or
du t (as small as 1”). Sage insertion flow meters
in lude a probe assembly that supports the sensing
element (a self-heated flow sensor and a tempera -
ture/referen e sensor); a sensor drive ir uit; mi ro -
pro essor meter board, and trans mitter en losure.
The probe assembly must be inserted into the orre t
position in the pro ess gas flow onduit to allow the
gas to flow through the sensor “window” a ross the
sensor element. The “sensing point” or a tive part of
the sensor (0.5" from the end of the probe) should be
positioned as per the drawing below and the
Installation Depth Chart on page 15.
Installation Depth
The enter of the pipe (assuming a well developed
turbulent flow profile) is fairly flat, and easy to
lo ate. See “Installation Depth Chart” on next page
to determine proper insertion depth.
Z
Y
X
4" PIPE SHOWN
LESS THAN IDEAL LOCATION
Contact Factory for Assistance
GOOD LOCATION2,3
(See Installation Depth Chart for X and Y Dimension)
2. Probe should be inserted per Installation Depth Chart (see following page),
so sensors are in the center of the pipe.
3. The portion of the probe that remains outside of the pipe, is simply the factory
ordered probe length (i.e. “-15” = 15 inches) minus the “Y” dimension.
Center
of Pipe
PRIME
84
˚F
13546 SCFM
467469670 SCF
88mW
1. SIP Industrial Meter shown in drawing. Note, probe is not bi-directional.

O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l 15
S A G E M E T E R I N G , I N C .
INSTALLATION DEPTH CHART
Methods for Probe Insertion to Pipe Center
ME T HO D 1
Using harts below, sele t pipe size ( olumn 1),
determine X. Insert probe until the end tou hes the
bottom of the pipe (ID), mark probe as it exits top
of fitting. Lift probe distan e “X” and tighten om -
pression fitting.
ME T HO D 2
Using harts below1, sele t pipe size ( olumn 1),
determine Y. Subtra t Y from the fa tory supplied
probe length. That differen e Z (see drawing on page
14) should be outside of the pipe, and is measured
from the bottom of the en losure of the probe weld
to pipe OD.
P PE S ZE OD D XYP PE AREA
1"
1.5" 1.900 1.500 .15" 1.56" 0.0123
2" 2.375 1.939 .35" 1.82" 0.0205
2.5" 2.875 2.323 .55" 2.07" 0.0294
3" 3.500 2.900 .80" 2.38" 0.0459
4" 4.500 3.826 1.30" 2.86" 0.0798
6" 6.625 5.761 2.25" 3.95" 0.1810
8" 8.625 7.625 3.25" 4.90" 0.3171
10" 10.750 9.750 4.25" 6.00" 0.5185
12" 12.750 11.374 5.13" 7.00" 0.7056
14" 14.000 12.500 5.70" 7.50" 0.8522
16" 16.000 14.312 6.60" 8.60" 1.1172
18" 18.000 16.124 7.50" 9.60" 1.4180
24" 24.000 21.562 10.25" 12.60" 2.5357
S C H E D U L E 4 0 P P E 2S C H E D U L E 8 0 P P E 2
P PE S ZE OD D XYP PE AREA
1"
1.5" 1.900 1.610 .20" 1.56" 0.0141
2" 2.375 2.067 .40" 1.82" 0.0233
2.5" 2.875 2.469 .60" 2.07" 0.0332
3" 3.500 3.068 .90" 2.38" 0.0513
4" 4.500 4.026 1.40" 2.86" 0.0884
6" 6.625 6.065 2.40" 3.95" 0.2006
8" 8.625 7.981 3.40" 4.90" 0.3474
10" 10.750 10.020 4.40" 6.00" 0.5476
12" 12.750 11.938 5.50" 7.00" 0.7773
14" 14.000 13.124 6.00" 7.50" 0.9394
16" 16.000 15.000 7.00" 8.60" 1.2272
18" 18.000 16.876 8.00" 9.60" 1.5533
24" 24.000 22.625 10.75" 12.60" 2.7919
C O S U L T F A C T O R Y C O S U L T F A C T O R Y
1 For other Pipe Schedules such as Schedule 10 contact Sage however the Y dimension will
be the same for any Schedule Pipe
2The 1" Pipe Size needs to have the Probe “Bottomed Out” (option “BOT"); the calibration
method for the 11⁄2" Pipe is either as shown below or with option “BOT”

S A G E M E T E R I N G , I N C . O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
16
R V. 16-SIP/SRP
PRIME
84
˚F
13546 SCFM
467469670 SCF
88mW
PRIME
84
˚F
135 46 SCFM
467469670 SCF
88mW
PRIME
84
˚F
135 46 SCFM
467469670 SCF
88mW
PRIME
84
˚F
13546 SCFM
467469670 SCF
88mW
CON IGURATION OR UTILIZING OUR (4) SAGE INSERTION MASS LOW METERS OR LARGE ROUND
PIPES OR DUCTS LARGER THAN 36" TO MINIMIZE E ECTS O VARYING LOW PRO ILES
(It is recommended that actory be contacted to assist with applications of this nature)
The outputs of the four meters will be averaged
by customer’s PLC or other method to improve
overall accuracy in measuring the flow rate.
( or medium sized round pipes [18" to 36"],
two meters, on the opposite side of the same
diameter, may be sufficient [insert parallel to an
upstream 90 degree bend for optimal benefit.])
Note, in this configuration, each sensor needs
to be averaged.
1/2" NPT
User Entry
for Wiring
1/2" NPT
User Entry
for Wiring
3/4" NPT for
Probe Support
3/4" NPT for
Remote Cable
3/4" NPT for
Remote Cable
Large Duct or Stack Applications

O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l 17
S A G E M E T E R I N G , I N C .
R V. 16-SIP/SRP
IN-LINE LOW METERS
In-line mounting styles are available through Sage
Metering, In . in sizes from 1/4" pipe through 4"
pipe. Threaded male NPT ends are standard up to
2-1/2"; ANSI 150lb flanged ends are re ommended
for 3" and 4" models. Conta t the fa tory if optional
end mounting styles are required. Pipe sizes in ex ess
of 4" require the insertion style mass flow meter.
The in-line style flow meter assembly flow se tion is
typi ally spe ified to mat h the user’s flow onduit
and is plumbed dire tly in the flow line by thread-
ENGTH “ ” SAME AS NON-F ANGED METER
(See table on page 27. For example, 1"x8" flow
body has an 8" length. The length will be the same
whether an NPT flow body, or whether flanged.
If a flanged flow body, the 8" dimension will be
a Face-to-Face dimension.)
LOW CONDITIONING SCREENS OR IN-LINE LOW BODIES 1/2" AND UP1
Screens shown
with NPT fitting.
1Note Flow conditioning is also available for Insertion Meter applications (see page 13)
ing, flanging, welding, et . DO NOT USE REDUCERS.
It in ludes the sensing element (a self-heated flow
sensor and a temperature/referen e sensor) mounted
dire tly in the spe ified flow se tion for exposure to
the pro ess gas; a sensor drive ir uit; mi ropro essor
meter board, and transmitter en losure.
All in-line Flow Meters, 1/2" and up have built-in
Flow Conditioners. See Table (page 10) for Upstream
Straight run requirements. Note, the 1/4" and 3/8"
do not have Flow Conditioners and thus require
more straight run.
In-Line low Meter Application

S A G E M E T E R I N G , I N C . O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
18
R V. 16-SIP/SRP
Prime Integral (Series SIP)
SEE “WIRING” ON PAGE 10 OR INSTRUCTIONS ON HOW TO REMOVE REAR LID;
SEE OLLOWING PAGES OR TERMINAL HOOKUP
1RED AC1 COM 1
2S1 AC2 B + 2
3RED SPARE A – 3
4WHITE
4-20mA PWR
4
5S2 4-20mA 5
6WHITE VDC GND 6
A B C
24 VDC
PULSE
VDC IN
+
VDC GND
–
INTEGRAL
INSIDE COVER VIEW INSIDE BODY VIEW
1/2" NPT
User Entry
for Wiring
3/4" NPT for
Probe Support
NO CUSTOMER ACCESS
DO NOT OPEN THIS SIDE
DISP AY SIDE
1/2" NPT
View Entry
(ONE ON EACH SIDE)
F OW
TERMINA B OCK SIDE

O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l 19
S A G E M E T E R I N G , I N C .
24 VDC Prime Integral Terminals (Series SIP)
(APPROVED OR HAZARDOUS SERVICE6)
1RED AC1 COM 1
2S1 AC2 B + 2
3RED SPARE A – 3
4WHITE
4-20mA PWR
4
5S2 4-20mA 5
6WHITE VDC GND 6
A B C
24 VDC
PULSE
VDC IN
+
VDC GND
–
INTEGRAL
INSIDE COVER VIEW
NOTE: The Sage Prime
draws 2.4 watts maximum
(i.e. ≅ 100ma @24VDC)
–+
CUSTO M ER
RET U R N
EXT E R N A L LY P OWER E D
4–2 0 m A BY CU S TOMER +
*
DESCR PT ON TERM NALS NOTES
DC nput Power: B5 B6
24 VDC7,8 + VDC – VDC G D
nternally Powered: C5 C6 Do not remove
4-20 mA 4-20 mA Return any Jumpers
SIG AL DRIVE
nternally Powered: C4 C6 Do not remove
Pulsed Output G D any Jumpers
Externally Powered: C5 B4 Remove B4 & B5
4-20 mA 4-20 mA 4-20 mA Jumper
SIG AL DRIVE EXTER AL SOURCE
Externally Powered9:C4 B3 Remove B4 & B5
Pulsed Output JU CTIO FOR Jumper and Connect
PULSE RETURN C4 Resistive Jumper
to B3
MODBUS C2 C3 C1 Modbus Ground10
RS485(+) RS485(–) MODBUS GROUND
(REQ’D)
*B4 and B5 UMPER
Remove jumper for Externally Sourced 4-20
mA. In this mode, user supplies 9-27 Volts to
externally power the 4-20 mA loop, and the
4-20 mA loop becomes optically isolated.
1Specify the Sage Prime PLUS option in order to have the Modbus Ground (Terminal C1 COM) isolated
from the 24 VDC Sage Power Supply Ground (Terminal B6). All other features of Prime PLUS are
identical to the standard Sage Prime except other voltage available. (See footnote 8)
2It is important to connect the Ground when using Modbus communications or ground loop problems
may develop. Improper wiring can also damage internal circuitry
3Note, if customer externally powers the 4-20 mA by removing the jumper the Pulse voltage output
is also effected: The voltage output of the Pulse will follow the customer power (i.e. 24 VDC external
power will result in a 24 VDC Pulse [maximum of 50 mA]; 12 VDC external power will result in a
12 VDC Pulse)
4Pulse width 250 msec default (adjustable with Addresser software)
5Using Sage Addresser a Low Flow Cutoff (LFC) commonly referred to as Min Cutoff or Zero Cutoff
can be entered into the FLOW MIN Functions. In Versions 1.82 or higher the Low Flow Cutoff and
the 4-20 mA Scaling are independent of each other. For example: A Low Flow Cutoff (LFC) of
10 SCFM on a Meter with a Full Scale of 100 SCFM will report 0 on the Display and 4 mA on the
output. The output will remain at 4 mA until the LFC is exceeded: (ie: 25 SCFM=8 mA). Thus the
4 mA will always be zero based
6Class I Div 2 Groups B C D T4 and ATEX Ex na IIC T4
724 VDC ±10%
8Other DC voltages (5 VDC 12 VDC 48 VDC) available on Prime PLUS. Contact Sage
9Assumes the 4-20 mA is Externally Powered
10 Modbus Ground becomes isolated from the B6 Power Supply Ground only on Prime PLUS version
(specify “PLUS”)
INSIDE BODY VIEW
1/2" NPT
User Entry
for Wiring
3/4" NPT for
Remote Cable
(on Remote Style SRP)
**
**Note, Flow Meter is supplied with a 10K
(1/2 watt) metal film resistor (Resistive
umper) connected across Terminals C4 and
C6. For externally powered operation, in
addition to removing B4 & B5 umpers, it
is necessary to connect C4 Resistive umper
to Terminal B3 instead of C6. Note, B3 must
be connected to the External Sources com-
mon in order to enable the optically isolated
pulse output. In this mode, Pulse Output is
optically isolated. Pulsed Output voltage will
depend on customer source voltage. Use
Sage Resistive umper only!
**
A1 – RED – VELOCITY SENSOR WIRE (HEATED ELEMENT)
A2 – NO WIRE
A3 – RED – VELOCITY SENSOR WIRE (HEATED ELEMENT)
A4 – WHITE – TEMPERATURE SENSOR WIRE
A5 – NO WIRE
A6 – WHITE – TEMPERATURE SENSOR WIRE
B3 – JUNCTION OR ISOLATED PULSE
B4 – 4-20 mA RETURN (–) AND PULSE SOURCE
B5 – VDC IN – VOLTAGE DC – POSITIVE (+)
B6 – VDC GND – VOLTAGE DC – GROUND (–)1
C1 – COM – RS485 MODBUS GROUND1,2
C2 – B(+)–RS485_D1
C3 – A(–)–RS485_D0
C4 – 24 VDC PULSE – 0 TO 24 VDC PULSE OUTPUT3,4
C5 – 4-20 mA – 4 TO 20 mA SIGNAL DRIVE5
C6 – VDC GND – VOLTAGE DC – GROUND (–)
24
O
24
O

S A G E M E T E R I N G , I N C . O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
20
AC Powered Prime Integral Terminals (Series SIP)6
1RED AC1 COM 1
2S1 AC2 B + 2
3RED SPARE A – 3
4WHITE
4-20mA PWR
4
5S2 4-20mA 5
6WHITE VDC GND 6
A B C
24 VDC
PULSE
VDC IN
+
VDC GND
–
INTEGRAL
INSIDE COVER VIEW
NOTE: The Sage Prime
draws 2.4 watts maximum
(i.e. ≅ 100ma @24VDC)
–+
CUS TO ME R
RET U R N
EXT E R N A L LY P OWER E D
4–20 mA BY C US TO MER +
*B4 and B5 UMPER
Remove jumper for Externally Sourced 4-20
mA. In this mode, user supplies 9-27 Volts to
externally power the 4-20 mA loop, and the
4-20 mA loop becomes optically isolated.
1Specify the Sage Prime PLUS option in order to have the Modbus Ground (Terminal C1 COM) isolated
from the 24 VDC Sage Power Supply Ground (Terminal B6). All other features of Prime PLUS are
identical to the standard Sage Prime except other voltage available. (See footnote 8)
2It is important to connect the Ground when using Modbus communications or ground loop problems
may develop. Improper wiring can also damage internal circuitry
3Note, if customer externally powers the 4-20 mA by removing the jumper the Pulse voltage output
is also effected: The voltage output of the Pulse will follow the customer power (i.e. 24 VDC external
power will result in a 24 VDC Pulse [maximum of 50 mA]; 12 VDC external power will result in a
12 VDC Pulse)
4Pulse width 250 msec default (adjustable with Addresser software)
5Using Sage Addresser a Low Flow Cutoff (LFC) commonly referred to as Min Cutoff or Zero Cutoff
can be entered into the FLOW MIN Functions. In Versions 1.82 or higher the Low Flow Cutoff and
the 4-20 mA Scaling are independent of each other. For example: A Low Flow Cutoff (LFC) of
10 SCFM on a Meter with a Full Scale of 100 SCFM will report 0 on the Display and 4 mA on the
output. The output will remain at 4 mA until the LFC is exceeded: (ie: 25 SCFM=8 mA). Thus the
4 mA will always be zero based
6This version does not have Hazard Approvals
724 VDC ±10%
8Other DC voltages (5 VDC 12 VDC 48 VDC) available on Prime PLUS. Contact Sage
9Assumes the 4-20 mA is Externally Powered
10 Modbus Ground becomes isolated from the B6 Power Supply Ground only on Prime PLUS version
(specify “PLUS”)
INSIDE BODY VIEW
1/2" NPT
User Entry
for Wiring
3/4" NPT for
Remote Cable
(ON REMOTE STY E SRP)
Grounding
ug
**
**
A1 – RED – VELOCITY SENSOR WIRE (HEATED ELEMENT)
A2 – NO WIRE
A3 – RED – VELOCITY SENSOR WIRE (HEATED ELEMENT)
A4 – WHITE – TEMPERATURE SENSOR WIRE
A5 – NO WIRE
A6 – WHITE – TEMPERATURE SENSOR WIRE
B1 – AC1 – AC VOLTAGE
B2 – AC2 – AC VOLTAGE
B3 – JUNCTION OR ISOLATED PULSE
B4 – 4-20 mA RETURN (–) AND PULSE SOURCE
B5 – VDC IN – VOLTAGE DC – POSITIVE (+)
B6 – VDC GND – VOLTAGE DC – GROUND (–)1
C1 – COM – RS485 MODBUS GROUND1,2
C2 – B(+)–RS485_D1
C3 – A(–)–RS485_D0
C4 – 24 VDC PULSE – 0 TO 24 VDC PULSE OUTPUT3,4
C5 – 4-20 mA – 4 TO 20 mA SIGNAL DRIVE5
C6 – VDC GND – VOLTAGE DC – GROUND (–)
24
O
24
O
DESCR PT ON TERM NALS NOTES
AC nput Power: B1 B2 Connect Ground Wire
115 VAC/230 VAC AC1 AC2 to Grounding Lug
DC nput Power: B5 B6
24 VDC7,8 + VDC – VDC G D
nternally Powered: C5 C6 Do not remove
4-20 mA 4-20 mA Return any Jumpers
SIG AL DRIVE
nternally Powered: C4 C6 Do not remove
Pulsed Output G D any Jumpers
Externally Powered: C5 B4 Remove B4 & B5
4-20 mA 4-20 mA 4-20 mA Jumper
SIG AL DRIVE EXTER AL SOURCE
Externally Powered9:C4 B3 Remove B4 & B5
Pulsed Output JU CTIO FOR Jumper and Connect
PULSE RETUR C4 Resistive Jumper
to B3
MODBUS C2 C3 C1 Modbus Ground10
RS485(+) RS485(–) MODBUS GROU D
(REQ’D)
*
**Note, Flow Meter is supplied with a 10K
(1/2 watt) metal film resistor (Resistive
umper) connected across Terminals C4 and
C6. For externally powered operation, in
addition to removing B4 & B5 umpers, it
is necessary to connect C4 Resistive umper
to Terminal B3 instead of C6. Note, B3 must
be connected to the External Sources com-
mon in order to enable the optically isolated
pulse output. In this mode, Pulse Output is
optically isolated. Pulsed Output voltage will
depend on customer source voltage. Use
Sage Resistive umper only!
This manual suits for next models
3
Table of contents
Other Sage Measuring Instrument manuals