Sateon Advanc SAT-ADV-C-SNG User manual

Sateon Advance Single-Blade Controller
Installation Guide
Specifi cation
The Advance Single-Blade Controller (Part No: SAT-ADV-C-SNG) is an access control system controller for
use with Sateon host software. It allows the connection of either one 2 Door Blade (Part No: SAT-ADV-BL-2D)
for connecting up to 2 doors and 2 readers, or one I/O Blade (Part No: SAT-ADV-BL-IO16) supporting up to 8
supervised inputs and 8 volt-free relay outputs.
The Single-Blade Controller can be used with diff erent power supplies: a 12V external power supply (up to 5A),
or POE/POE+. It has an integral case with built in optical tamper. The controller supports both IP and RS485 host
communications.
Overview Sateon Advance Single-Blade Controller (max 1 Blade)
Power Input 12V (5A input), POE, POE+
Host Communications Ethernet 10/100 BASE-T or RS485 2-wire 19.2k baud
Battery (optional) 4.2V Lithium Polymer (Grosvenor supplied, part no: SAT-ADV-BAT-S)
Tamper Optical Tamper
USB Dual USB 2.0 Type A (future use)
Operating Temperature 0 to +49°C (32 to 120°F)
Humidity 5-85±5% at 30±2°C (86±4°F)
Weight 495g (including case, but without battery or blade fi tted)
Dimensions 242 x 167 x 46 mm
Page 1
Electromagnetic Compatibility
This product complies with the following standards,
following the provisions of EMC Directive 2014/30/EU:
EN 55022:2010 Class B
EN50130-4:2011 inc A1:2014
IEC 62599-2:2010
WEEE
Please refer to www.grosvenortechnology.com/
legal-info/ for disposal instructions under EU
Directive 2012/19/EU

MAC ADDRESS
0001CE20001
SAT-ADV-C-MLT-00000001
Load/Clear
Status
Reset
!
!
12V 5A MAX
RS-485
A B S
Optical
Tamper
Sateon Single Tampo Printing 1v0
Battery
An optional Lithium
Polymer 6,000mAh
battery may be
used to provide a
battery back-up
service during power
outages.
Only the battery
supplied by
Grosvenor (Part No.
SAT-ADV-BAT-S) may
be used.
See Notes on page 4.
Load/Clear
Used to reset
confi guration data.
Can be used in three
diff erent ways; see
Notes on page 4.
Reset
The Reset button
triggers a complete
system reboot
in the case of an
unresponsive system.
It is recessed to
prevent accidental
activation and can
be depressed using a
suitable tool or a pen.
Warning: Use ony
when requested by
Grosvenor Technical
Support.
Optical Tamper
No connection is
needed; the optical
tamper is operational
when the case is
closed.
RS485 Port
Used for host comms
when RS485 is used to
connect controllers.
See page 5.
Ethernet Port
For IP host comms and
required for confi guration.
10/100 BASE-T
Full duplex, POE/POE+
Ethernet Port indicators
are shown below.
Status LED
The Controller Status
LED reports the
controller state.
See Notes on page 4.
Power In
12V DC 5A Max
For full details of
power options and
requirements, see
page 3.
USB Ports
Two USB 2.0 Type A
ports; intended for
Grosvenor-approved
USB products only.
Can be used to update
controller fi rmware.
Blade Connection
One 2 Door Blade or one I/O
Blade can be installed. See Door
Blade Installation Guide for details
of confi guring doors and locks.
See I/O Blade Installation Guide
for details of confi guring extra
inputs and outputs.
Flashes for
Ethernet activity
No Activity
Amber
O
100 Mbps
No Link
Green
O
Page 2
ConnectionsConnections

The Advance Single-Blade Controller has a
sophisticated power management system with a
choice of input sources. As well as supplying the power
used by the controller, it provides output power to a
single blade which may have various locks, readers
and peripherals connected.
Input Power
Power to the controller may be provided by one of:
12V 5A (60W max) = 2.1mm Circular Jack (centre pin
positive).
PoE (IEEE 802.3.af =12.95W max)
PoE+ (IEEE 802.3.at = 25.5W max)
If fi tted, the 4.2V Lithium Polymer Battery (during
power outage only)
It is the responsibility of the installer to ensure
suffi cient power is available for the system. When
selecting the most suitable power supply, you need
to balance the convenience of PoE against the total
requirements. Ensure you consider the power
requirements for the controller itself and the blade
fi tted, as well as the required locks, readers, etc.
Current
Measure
12V PoE
Current
and Voltage
Measure
Battery
Management
4.2V +> 11V
12V 5 Amp
input
Protection
Circuit
Voltage
Measure
12V => 5V CPU
USB sticks (2)
(500mA total)
12V
4 Amps
Blade
4.2V Lithium
Battery
Although we cater for up to 4A locks, many only
require a few 100mA so could be used with PoE+. Note
that the PoE source could have its own battery backup.
Output Power
Power draw of the controller includes the following:
Single-Blade Controller Quiescent Power = 250 mA
max @ 12V (3.0W)
Battery Charging power (if fi tted, only while battery
depleted) = up to 167 mA max @ 12V (2.0W)
USB Power (future use, if fi tted) = 260mA max @
12V (3.1W)
Blade Power (Door Blade = 1.0 W, I/O Blade = 4.0W)
External Lock Power
For systems with 24V door locks, or locks requiring
more power than the controller can provide, the door
blade can use an External Lock Power Supply. See Door
Blade Installation Guide for details.
Power supply Supplied Used by controller* Remaining for devices
PoE (IEEE 802.3.af ) 11W 0.92A 6.0W 0.5A 5W 417mA
PoE+ (IEEE 802.3.at) 21W 1.75A 6.0W 0.5A 15W 1250mA
12V external power supply (2.5A
plug top)
30.0W 2.5A 6.0W 0.5A 24.0W 2000mA
12V external power supply (PSU3A-
12(B))
36.0W 3.0A 4.0W** 0.33A** 32.0W 2666mA
12V external power supply (5A) 60.0W 5.0A 6.0W 0.5A 54.0W 4500mA
* Indicates the approximate power required by the controller, assuming one door blade fi tted, and allowing for standard
battery charging power.
** Assuming no battery charging provision, as the specifi ed PSU caters for an external battery.
Power Options
Page 3

Notes
Status LED
The Controller Status LED can be monitored during
installation and set up. It is not visible when the case is
closed. The LED reports the controller state as follows:
Yellow medium fl ash Off -line
Yellow fast fl ash Port connected, not online
Green medium fl ash On-line
Blue continuous Controller initialising
Blue medium fl ash Application initialising
Cyan fast fl ash Wants data download
White slow fl ash Firmware update in
progress
White fast fl ash Data download in progress
Red continuous Confi guration button
pressed for less than 5
seconds
Red fast fl ash Confi guration button
pressed for more than 5
seconds
Red slow fl ash Error
Load/Clear Button (Confi g)
This button has three purposes:
To reset
confi guration data
and ask for reload.
Press button, wait for LED
go red, then release button.
To restore the
product to the
factory default
state.
Press button, hold for 5
seconds until LED fl ashes
red, then release button.
To reload the
application that
shipped with the
controller and
delete all data.
Press button while powered
off and then power on,
or press button before
momentarily pressing Reset
button. Hold until LED goes
amber and then fl ashes
amber after a few seconds,
then release button.
The button is recessed to prevent accidental activation.
Battery
An optional lithium polymer 6,000mAh battery may
be used to provide a battery back-up service. Using a
battery ensures continuing power to controller and all
attached devices during power outages. Note though
that all system data is retained in non-volatile memory
indefi nitely even when no battery is fi tted.
Only the battery supplied by Grosvenor may be used
(Part No. SAT-ADV-BAT-S).
The battery operating time is heavily dependent on
loading (i.e. current drain by external readers or door
locks) but will typically be 45 minutes to 2 hours.
During battery operation, the 12V internal supply is
reduced to 11V and the maximum permissible total
current draw for all external sources is 1.5A.
The time required to charge the battery from depleted
to full capacity is dependent on available power (for
example, it may take longer from POE than from
a 5A supply), external current draw and product
temperature. It may take over 24 hours.
Battery Safety Notice
The Single Blade Controller battery electronics contain
multiple safety elements to protect against over-
charge/discharge, short-circuit, over-temperature etc.
However, the following warnings should be observed:
Only fi t the original battery module supplied by
Grosvenor Technology and use only in accordance
with this document.
Do not use module if battery appears deformed or
damaged.
Do not disassemble, crush, pierce or rupture the
battery.
Do not short circuit or reverse polarise the module
nor attempt to charge the battery except in the
controller.
Do not store at a temperature below -20°C (-4°F) or
above +60°C (+140°F).
Observe local regulations when disposing of the
Lithium-polymer battery.
Never dispose of the battery using heat or fi re.
Battery Service Life
A battery service life of 5 years is possible, although
this can be aff ected by a number of factors including: a
prolonged period of storage prior to use, the number
of discharge/charge cycles and the battery operating/
charging temperature.

Page 5
Telephone: +44 (0)1279 838000
Web: www.grosvenortechnology.com
For more information about Sateon, visit the website or contact Technical Support:
RS485 Connections
If RS485 is used, up to 16 Advance controllers can
be daisy-chained together in a line (a combination of
Single-Blade and Multi-Blade controllers can be used).
One controller must be confi gured as a Relay
Controller, which uses both IP and RS485.
Other linked controllers are confi gured as 485 only.
Note that the Relay Controller doesn’t have to be at the
bus end, it can be anywhere. Fit a 120R termination
resistor at either end of the RS485 bus:
Advance 485
Controller
A
S
B
Advance
Relay
Controller
Screen
Advance 485
Controller
A
S
B
A
S
B
RS485 confi guration
Note that all Advance controllers require an Ethernet
connection during the commissioning process.
Use Sateon Quick Start to discover and confi gure the
controllers. Once they are set up as the correct type
and with the correct network settings, the Ethernet
connection can be disconnected from 485 controllers.
485
Controller
Terminate
Here
Terminate
Here
Relay
Controller
485
Controller 485
Controller 485
Controller
Table of contents
Popular Controllers manuals by other brands

Eaton
Eaton EFX48 e-Fuse Series Installation and operation guide

SMC Networks
SMC Networks ITV1000 series Operation manual

CBS ArcSafe
CBS ArcSafe RSK-SPB1 user manual

Emerson
Emerson Bettis Q series Installation, operation and maintenance manual

Honeywell
Honeywell HR 10 F Mounting and operation instructions

Woodward
Woodward PG-EG Installation and operation manual

AMLUX
AMLUX Next Matrix user manual

Delta Electronics
Delta Electronics Programmable Logic Controller DVP-EC3 instruction sheet

ACT
ACT ACTsmart2 1070 Operating and installation

ZILA
ZILA KST-20 Vento Mounting and operating instructions

WIKA
WIKA A2G-100 operating instructions

Alicat
Alicat MC Series operating manual