2
TECHNICAL FEATURES
1. Oil and/or gas flames can be monitored.
2. The flame detector and indicator control unit are suitable
for operation where the ambient temperature lies within
the range -20°to +60°C. (Please contact the manufac-
turer for information on higher temperatures.)
3. The working contact carries no potential difference,
allowing the flame signal to be transmitted over large
distances.
4. The influence of possible stray light during the pre-purge
phase or the intensity of the flame when the burner is
operating is indicated by the row of 5 LED’s. The status
of the relay is visible at any time.
5. Sensitivity is adjustable.
6. The compact dimensions of the detector allow it to be
installed on any burner.
7. The industrial version differs from the normal version by
having a larger, robust, absolutely waterproof detector.
8. Unlike UV tubes, the IRD 810/820 flicker detector does
not deteriorate with age.
INSTALLATION INSTRUCTIONS
1. The detector probe should be fitted so that it receives the
light which pulsates most strongly. This can be achieved
by positioning the detector as close as possible to the
flame or by directing it at a particular zone of the flame.
2. No stray light must be allowed to fall on the detector (e.g.
through cracks or from a sight glass). Pulsating stray
light (e.g. from fluorescent lighting or light bulbs) could
cause the system to switch to lockout.
3. The infra-red flicker detector should be fitted in such a
way that the ambient temperature cannot under any
circumstances rise above 60°C. At higher temperatures,
there is a risk of incorrect operation and the life expectancy
of the unit could be reduced. In addition, care should be
taken that the detector is not subjected to unusually
harsh vibration and receives no hard knocks.
4. The cable connecting the detector with the indicator
control unit must not be disconnected. It must not,
therefore, be shortened or lengthened.
COMMISSIONING AND MAINTENANCE
During commissioning and after servicing, the flame
monitoring system should be checked for faultless operation
as follows:
1. Check that the detector is connected properly. Wrong
connections are a risk to safety, and could cause damage
to the detector unit or burner system.
2. Adjust to maximum sensitivity and start the burner. After
the start impulse, no LED should light up during the pre-
purge phase.
3. With the system set for normal operation, pull out the
detector probe and cover it up to cut off light. The LED
indicators must go out. The control box should switch to
lockout or attempt to restart the sequence.
4. Attempt to restart with the flame detector covered. There
must be no indication from the LED’s. The burner control
box must switch to lockout at the end of the safety
interval.
5. Attempt to start the burner with the detector exposed to
stray light e.g. from fluorescent lighting, a cigarette
lighter or light bulb (not daylight!). Depending on the type
of control box, it should switch to lockout either
immediately or at the end of the pre-purge, as a result of
stray light.
6. Re-insert the detector into its mount. When the burner is
operating normally, carefully turn back the sensitivity
control until only one LED is lit. The control box must
switch to lockout or restart the sequence.
7. Adjust the sensitivity to maximum. When the burner is
operating normally, turn back the sensitivity control until
only 4 LED’s light continuously.
We recommend this method of adjustment, because in
this way, changes in the burner settings, dirty detector
probe etc. or also the influence of stray light, can be
detected very easily. (The internal relay is activated when
2 LED’s light.)
The flame detection device requires no maintenance of any
kind, and as it is classed as safety equipment, no attempt
should be made to open the housing. The LED indicators
should be checked visually at regular intervals. If a lower
signal strength is indicated, it could mean that the burner
settings have changed or that dirt and dust have reduced
the amount of light reaching the detector.
FAULT FINDING
1. LED’s light up during the pre-purge phase (control box
switches to lockout):
a) Stray light
b) Ignition spark visible to detector (only oil burners)
Correct by preventing direct sight of ignition spark or
install Satronic high-frequency ignition transformer.
c) Interference from ignition cable (lay cables some distance
apart)
d) Live and neutral wired incorrectly
e) Burner not earthed/grounded
f) Detector or indicator control unit defective
2. No indication from LED’s after establishment of flame:
a) Incorrect or faulty wiring
b) Detector probe incorrectly installed („sees“ no light)
c) Detector is dirty
d) Sensitivity set at minimum
e) Detector probe or indicator control unit defective