Sauter Components LRA 4 Series User manual

45.016/1
Sauter Components
LRA 4**: Electronic room operating unit (868 MHz)
How energy efficiency is improved
Individual, optimised energy use through precise adherence to setpoint.
Areas of use
For single-room control in residential and commercial properties, with wireless, bi-directional data
transmission.
Features
•Room operating unit with bi-directional wireless transmission for heating/cooling
•Transmission frequency 868 MHz, encoded
•NTC sensor
•Easy addressing, parameterisation and monitoring using sensor buttons
•Large TFT LCD, black on grey, 32 × 38 mm
•Integrated and configurable time programme
•Heating/cooling change-over using a room operating unit or via the input on the controller
•Party function and additional functions can be selected
•Room operating unit can be configured as an additional sensor
•Connection for floor, room or outside-temperature sensor
•Contemporary design
Technical description
•Flat housing of white (RAL9016) or black (RAL9005) thermoplastic
•Temperature range 5…30 °C
•With settable frost-protection facility, factory setting 8 °C
•Suitable for wall mounting and recessed junction box
•Standard battery 2 × 1.5 V AAA
T
Y10164
Type
Colour
Humidity range
% rh
LRA420R K104
white
–
LRA420R K124
black
–
LRA450R K104
white
5…95
LRA450R K124
black
5…95
Setting range
5...30 °C
Perm. ambient temperature
0...55 °C
Setting accuracy
±0.1 K
Perm. ambient humidity
5…80% rh
Sensor
NTC 10 kΩ
Weight
0.13 kg
Humidity accuracy
±3.5% rh at 55% rh, 23 °C
Hysteresis (average)
> 3% rh
Ingress protection
IP 20 (EN 60529)
Protection class
III (EN 60730)
Radio frequency
868.3 MHz
CE conformity as per:
Transmission power
13 mW (self-adjusting)
R&TTE 1999/5/EG
EN 300220-1
Range 1)
approx. 50 m
EN 300220-3
Data transmission
every 10 minutes
Power supply
2 × AAA 1.5 V 2)
Dimension drawing
M11485
Cover plate
M11487
Outside-temperature
sensor
M11492
Fitting instructions
P100009964
1)
In standard buildings or houses, depending on the ambient conditions, 40 m in buildings, 200...300 m in open areas (depending on obstruc-
tions and local sources of interference)
2)
Supplied with the unit
Accessories
0313367001
Cable-type NTC sensor, 10 kΩ, 1.5 m, for floor or outside temperature, max. 70 °C
0313367003
Cable-type NTC sensor, 10 kΩ, 3 m, for floor or outside temperature, max. 70 °C
0450232001
Outside-temperature NTC sensor, 10 kΩ, in housing, -50…+90 °C, IP43, connected via two
screw terminals, see fitting instructions P100011523
0450241001
Cover plate, white (RAL 9016), dimensions 138 mm × 72.5 mm
0450541021
Cover plate, black (RAL 9005), dimensions 138 mm × 72.5 mm
*)
Dimension drawing or wiring diagram is available under the same number
7145016003 01

45.016/2 LRA4**
Sauter Components
Operation
The LRA4 electronic room operating unit is a component of the radio system in combination with the
LET4 bi-directional wireless controller. The room temperature is measured by a precision temperature
sensor and compared with the current setpoint. Depending on the control offset and
the control characteristic, the output is regulated on the wireless controller, thereby increasing or
decreasing the heating/cooling in the room. Therefore, the required room temperature can be kept
constant.
Using the weekly programme to select an individual temperature profile for each day ensures the
optimal comfort level with minimal energy consumption. There are three different time programmes
stored in the controller. Additional time programmes can be programmed for temperature require-
ments that differ from these.
The operating status of the system is shown on the display (LCD) with visual symbols and a numeri-
cal field. Programming mode is used to enter an individual switching program
temperature profile that differs from the factory setting.
Service mode is available for adapting the device to the installation etc. The following can be parame-
terised: control characteristic; setpoint limitation; operating modes; inputs and outputs of the wireless
controller and their priorities; output (NC or NO) of the thermal actuators; parameters of the room
operating units; local parameters for the room operating unit, such as cooling lock, bypass functions,
master and wireless controller parameters; see the parameter list.
The room operating units and wireless controllers are configured ex works so that underfloor heating
control is possible without any additional settings. If a cooling command is entered on the controller
via the C/O input, cooling control starts automatically. The 'cooling' symbol is displayed on the room
operating unit.
Other applications, such as cooling via the master room operating unit and special function settings
for hotels or public buildings, can be set by means of the service parameters.
Engineering and fitting notes
The unit should be fitted approx. 1.5 m above the floor, and protected from direct sunlight, draughts
and sources of heat and cold.
The room operating unit should be installed in a readily accessible location so that the temperature of
the room can be easily set.
Additional technical data
CE conformity as per:
Radio
EN 300220
RTTE immunity
EN 301489-3
RTTE emission
EN 300220-3
Serviceable life and replacement of batteries
The serviceable life of the battery is approx. two years, though it depends on the transmission dis-
tance to the controller. The transmission strength is constantly adjusted to provide optimal power. This
keeps the transmission output as low as possible.
The batteries should be replaced as soon as the 'battery' symbol appears in the display. If 'Batt' lights
up in the display, the battery is so low that a signal cannot be sent to the controller. No settings are
lost when the batteries are replaced. When installing batteries, ensure that batteries of the same type
are used and that both of them are new. Do not mix old and new batteries.
Notes on the use of the LRA450 with humidity sensor
In general, humidity sensors are subject to increased ageing if they are used in very contaminated air
or aggressive gases. The sensor may start to drift prematurely under these conditions. If the sensor is
used in very contaminated air, the warranty does not cover the replacement of the complete sen-
sor.
7145016003 01

LRA4** 45.016/3
Sauter Components
Addressing the room operating units on the wireless controller
When the system is put into operation for the first time, the radio connection must be set up between
the room operating unit and the wireless controller. Addressing is not lost when batteries are replaced.
After the desired channel (one or more) has been selected on the wireless controller, the 'OK' and
'Escape' buttons must be pressed for 5 s. 'Pair' appears briefly on the display, denoting that the con-
nection between the thermostat and the controller has been established.
To test the connection, these two buttons can be pressed again for 5 s. During the 5 s, 'Pair' briefly
lights up on the display, followed by 'Test', along with the relevant channel LED on the controller.
After the addressing, the time and date must be entered as follows: hours, minutes, year, month and
day. The '+' and '-' buttons are used to change the values, and each step should be confirmed with the
'OK' button. When the time has been entered in the first room operating unit, this time is forwarded to
all room operating units in the system (master controller to slave controller). If the time has not been
entered on the first addressed unit, this is queried on the next unit. If the 'OK' button is pressed for 10
s, the time and date can be called up and changed. An automatic summertime/wintertime change-
over is stored. This can be deactivated in service mode using parameters.
Basic functions
After the addressing, the device switches to sleep mode after 10 s. The display shows the actual
temperature, the radio transmission, the ECO symbol, the day and, if the battery is low, the battery
symbol. Pressing any button switches the device on, and the device obtains the current data from the
wireless controller. The unit must be switched on before any entry, parameterisation or function
change can be made.
The setpoint can be set by pressing the '+' or '-' button again. After 5 s, or immediately after the 'OK'
button is pressed, the selected setpoint is automatically sent to the wireless controller and saved
there. After that, the actual temperature value is retrieved every 10 minutes.
By pressing the 'Menu' button again, it is possible to switch between the frost protection mode (Off),
ECO, normal operation or the time programme. If the room operating unit is configured so that
change-over between heating and cooling was programmed, these two modes are also available.
The button lock is activated by pressing the '+' and '-' buttons for 5 s. The 'button lock' symbol appears
on the display, also in sleep mode. The lock is removed by pressing both buttons again for 5 s.
If the 'Menu' button is pressed again for 5 s, the display shows the first level of the parameter settings.
If the 'Menu' button is briefly pressed again, the parameters up to P-SE, parameters of the service
level, are shown.
Time programmes
Stored in the wireless controller are three time programmes that can be altered using the wireless
room control unit. Whenever a time programme is altered, it is adopted by all the other room operating
units that use the same profile.
Time programme I:
A profile for all days of the week; three switching points are available. Time programme I includes only
one profile; the profile is identical for every day.
Time programme II:
A profile for the working days of Monday to Friday and a profile for the weekend. Three switching
points are available for all working days, and three additional switching points are available for the
weekend.
Time programme III:
A profile for every day; three switching points are available for each day. With time programme III, you
can choose different profiles for each day.
A switching point always consists of two change-over points. A time must be specified for each
change-over point. For the first change-over point, the time for the change from 'Reduced Mode' to
'Normal Mode' is set. For the second change-over point, the time for the switch from 'Normal Mode' to
'Reduced Mode' is set.
7145016003 01

45.016/4 LRA4**
Sauter Components
Overview of display and sensor buttons
1 General information such as battery status, energy-saving mode, alarms for dew point and window
contacts, radio connection, general alarm, locking, weekdays for time programme
2 Temperature setpoint and actual value, time, time programme, indoor, outdoor and floor temperature
3 Auxiliary texts for parameterisation
4 Operating modes
5 Confirm changed values, confirm selection
6 Activate menu mode, select menus and parameters
7 Change setpoints, time, date and other values; select the time programme
8 Function button, can be set using parameter P-10
9 Cancel: leave current parameter or menu
Sensor buttons Description
Activate operation with any sensor button.
Selection button
Activate menu mode.
Select operating mode. Possible operating modes: frost protection, reduced
operation, normal operation, time programme, heating or cooling
Select parameter (menu mode).
Change setpoint.
Save value.
Confirm selection.
Change time.
Cancel.
Addressing.
Test addressing.
Lock/unlock manual operation.
Select function or display directly
Function:
Heating or cooling (party function) has priority over all other functions. Over-
ride is active for the time set here, between 1 hour and 9 hours. On the
display, P appears in front of the actual value.
Function/display:
Depending on the setting selected for parameter P-10, pressing the sensor
button executes one of the following functions:
•Immediate change-over between heating and cooling, and display of
room temperature.
•Immediate display of the floor temperature.
•Immediate display of the outside temperature.
•Immediate display of the relative humidity (optional).
If a function other than the 'party function' is set using parameter P-10, this
function still becomes active by pressing the sensor button for 5 seconds.
7145016003 01

LRA4** 45.016/5
Sauter Components
Description of parameters
Changing and confirming the operation for parameters
•The first parameter is displayed by touching the 'Menu' button for 5 s
•Briefly touching the 'Menu' button switches from one parameter to the next
•Touching the 'OK' button causes the selected parameter to be ready for changing
•The parameter is changed using the '+' or '-' button; several important parameters also need
to be confirmed with 'yes' or 'no'
•Touching the 'OK' button causes the changed parameter to be confirmed
•Touching the 'Escape' button causes the unit to be switched to a lower level and the change
to be communicated on the wireless controller
Parameter used
Factory setting
P-01 Adjust the standby display: actual value or time Room temperature
P-02 Specify the setpoint for the minimum floor temperature 15 °C
P-03 Specify the limitation of the setpoint temperature 30 °C / 5 °C
P-04 Change the time programme
P-05 Reset the time programme to the factory setting –
P-06 Specify the display for standby mode
(max. battery-saving mode)
On
P-07 Activate or deactivate button tone On
P-08 ID number of the wireless room operating unit –
P-09 ID number of the wireless controller –
P-10 Set the parameter for the function of the sensor button 0
P-11 Specify the limitation of the setpoint humidity (optinal with room
operating units with integrated humidity sensor)
65 % / 55 %
P-SE Service parameters
The service parameters are protected by a password (set at 1-2-3-4 at the factory). Parameter P-SE
comes after parameter P-11. If the 'OK' button is pressed, the code is queried. Each number must be
confirmed by pressing 'OK'. The first service parameter is P-20. If you press the 'OK' button, you are
taken to the P-20 parameter list. Pressing the 'Escape' button takes you out of the P-20 parameter list
and straight to the next parameter list, P-30. See the description for making changes in each parame-
ter list.
General parameters
Factory setting
P-SE Access only with service code (factory setting '1-2-3-4') –
P-21 Display the software version of the wireless room operating unit –
P-22 Display the software version of the wireless controller –
P-23 Display the current status of the wireless controller and the I/O box –
P-24 Reset the parameters to the factory setting –
Parameters for all room operating units
Factory setting
P-31 Specify the increment for the setpoint temperature 0: 0,5 K
P-32 Specify the temperature for the frost-protection facility 8.0 °C
P-33 Specify the temperature unit 0: °C
P-34 Specify the value for the dead zone for heating/cooling change-
over
0: 2 K
P-35 Change the service code for the service menu 1234
P-36 Change the access code for public buildings 1234
P-37 Activate or deactivate the 'summertime/wintertime' function 0: activated
Parameters for individual room operating units
Factory setting
P-41 Compensate for the influence of the wall temperature for the 0 K
7145016003 01

45.016/6 LRA4**
Sauter Components
wireless room operating unit
P-42 Compensate for the floor temperature 0
P-43 Specify the maximum value for the floor temperature 35 °C
P-44 Specify the setback temperature for the 'Eco' function 3 K
P-45 Activate or deactivate the cooling lock and/or bypass, e.g. for a
heat pump
0
P-46 Activate or deactivate the 'Make common use of a setpoint
within a zone' function
0: deactivated
P-47 Activate the lock for public buildings or hotels 0: deactivated
P-48 Activate or deactivate the master function for a wireless room
operating unit
0: deactivated
P-49 Specify the function of the external temperature sensor. An
optional external temperature sensor must be connected to
the wireless room operating unit
0
Parameters that are specific to the installation and the topology
Factory setting
P-51 Set priorities for the 'heating/cooling' change-over and for the
'heating/cooling' output or burner control
0
P-52 Activate or deactivate the 'Optimised time programme' function 0: deactivated
P-53 Set the type of communication between wireless controllers
(options: radio or bus)
0
Control parameters
Factory setting
P-61 Configure ECO or N/R input 0
P-62 Configure c/o in or temp. limit input 2
P-63
Select 'local' pump activation or activation through the 'master
wireless controller' (only for communication between wireless
controllers)
0
P-64 Select function NC or NO for thermal actuators 0: NC
P-65 Select control algorithm 0: ON/OFF
P-66 Activate the 'Optimised actuator control' function 0: deaktiviert
P-67 Select the initial controlled floor heating 0: deaktiviert
Dimension drawing
7145016003 01

LRA4** 45.016/7
Sauter Components
Cover plate Outside-temperature sensor
Printed in Switzerland
Subject to changes
© Fr. Sauter AG, CH-4016 Basle
7145016003 01
This manual suits for next models
4
Table of contents
Popular Control Unit manuals by other brands

H3C
H3C PSR150-A1 manual

Adesys
Adesys SVL Series manual

HP
HP 6600-A FIP-600 FlexIntfPltfrm Rtr Mod Product End-of-Life Disassembly Instructions

Aprimatic
Aprimatic WING NK Mechanical installation instructions

Baker Hughes
Baker Hughes Masoneilan SteamForm 84003 Series installation guide

Laird
Laird BTM521 user manual

Bosch
Bosch KTS 5a Series Original instructions

Novus
Novus DigiRail Connect Series instruction manual

LEGRAND
LEGRAND adorne Night Light installation instructions

AVK
AVK 145 Series Installation, operation and maintenance manual

Fort Vale
Fort Vale 0R3/ 006 Series Maintenance manual

NETGEAR
NETGEAR AXM762 Installation