Push button
ENTER
Display for
programming and
indication
Push button
for level select
67
157,5
117
132
166
80
107
55
66
~ 180
170
213
Dimensions in mm
Supply
24 VAC/DC
Safe area
P+ P−
Relay output
250 VAC/0,1 A 30 V/0,5 A
PA
1 2 3 4
~
−
~
+
24 VAC/DC
PE
SW-IN (GND)
5 6
SW-Ch1
AUB
Relay output
250 VAC 0,1 A / 220 VDC 0,1 A
30 VAC/DC / 0,5 A
InBin-P-100 SB 1.0
function normal close (nc) or
normal open (no) can be
selected via menu
If supply voltage 24 VAC/DC
differs from the relay voltage
different or double isolated
cables must be used.
Wiring diagram InBin-P-100
3 / 6
InBin-P-100 switches are equipped with a 24 VAC/DC power supply. The supply has to
be connected at terminal 1 (−/~) and 2 (+/~). The electrical wiring must be realized via
integrated junction box.
If supply voltage 24 VAC/DC differs from the relay voltage different or double isolated cables
must be used.The starting bypass delay can be activated by a short circuit of terminal 2
and teminal 3 (AUB). An active bypass delay is indicated with green blinking LEDs.
Attention: Do not open covers when circuits are alive!
Electrical connection
The default / delivery setup is 0000. In this configuration the password input is not activated.
To activate a password change the 4 digits into your chosen numbers (e.g. 1234) and press
Enter. Please keep your password in mind for next parameter change!
Due to a new parameter setup the password is requested.
Password input
To change from operation to parametrisation mode push the enter button for
minimum 3 seconds. Back over the menu save.
A blinking unit in the display shows that data is received and the device is working.
Change operation-/parametrisation mode
Indication of data logging
Display and buttons
Dimensions/ drillings
D.IB-P100-02.01-en
23-Aug-2012
Important information for installation and operation
A. Installation, commissioning, maintenance
The cable has to be drawn through the cable gland. After electrical connection the
cable gland must be fixed tighten. IP66 must be fulfilled. In acc. with operation InBin
switches are maintenance free. The sensors must not be opened by the customer.
For electrical connection use the internal junction box.
Attention: Before opening the internal junction box cut off the power supply.
B. Supply and Contact
Wires from safety extra low voltage must be separated from others. Only at 24 VAC/DC
supply and signal wires in one cable is permitted. All others use separate or double
isolated cables. Install overload protection fuse < 10 A.
C. Pressure sensors
After mounting and installation, a zero point compensation must be done, because
the offset value depends on the installation position. Have a look at parametrisation.
D. Long cabling
For using long signal wires, shielded cables are recommended. The shield must be
connected to the InBin-P switch inside the terminal box.
E. Separate ground wires
Use for supply and signal wires a separate ground.
For a InBin-P-100 pressure switch installation a zero point compensation should be
performed to adjust value deviations of the module‘s installation position. Therefore the
pressure nipples P+ / P−must be connected with a short circuit tube and the zero point
compensation accomplished by following the menu.
Before starting the compensation the device should be connected to the power supply for
minimum of 15 minutes to reach the working temperature!
Zero point compensation for pressure transmitter
Installation
▪Maintenance must comply with regional standards, rules and regulations
▪Do not open covers when circuits are alive
▪For electrical connection use the integrated junction box
▪The cable must be installed in a fixed position and protected against mechanical
and thermical damage
▪Connect protection earth
▪Avoid thermal transfer from sensor probe to transducer (ensure max. ambient temperature).
▪Ambient temperature −20…+50 °C
▪Close all covers, entries with min. IP66
▪All transducers are maintenance free
▪For outdoor installation a protective housing against rain, snow and sun should be applied
▪Only wet cleaning