Schlage PIM400-TD2 User manual

*P516-096*
P516-096
PIM400-TD2
User guide for Panel Interface Module PIM400-TD2
Para el idioma español, navegue hacia www.allegion.com/us
Pour la portion française, veuillez consulter le site www.allegion.com/us

2 • Schlage • PIM400-TD2 user guide
Contents
Overview...........................................................................................................................3
Getting started ..................................................................................................................4
Features and components ................................................................................................5
Model specications .........................................................................................................6
Installation.........................................................................................................................6
Determine the location ..................................................................................................6
Pre-installation test........................................................................................................6
Installation.....................................................................................................................7
Mount the PIM400-TD2.................................................................................................7
Wire routing...................................................................................................................8
Cable/wire specications ..............................................................................................8
PIM400-TD2 to ACP connection.......................................................................................9
Typical PIM400-TD2 to ACP wiring diagram .................................................................9
Optional remote antenna ................................................................................................12
Link mode .......................................................................................................................12
Schlage Utility Software (SUS) .......................................................................................12
Reset to factory defaults .................................................................................................12
DC power........................................................................................................................13
Complete the installation ................................................................................................13
Troubleshooting ..............................................................................................................13
FCC/IC statements.........................................................................................................14
To comply with FCC and Industry Canada RF radiation exposure limits for general population,
the antenna(s) used for this transmitter must be installed such that a minimum separation
distance of 20cm is maintained between the radiator (antenna) and all persons at all times
and must not be co-located or operating in conjunction with any other antenna or transmitter.
This product is compliant of UL 294 and ULC S319 standard. This product’s compliance
would be invalidated through the use of any add-on, expansion, memory or other module
that has not yet been evaluated for compatibility for use with this UL Listed product, in
accordance with the requirements of the Standards UL 294 and ULC S319. This product has
been evaluated for ULC-S319 Class I.

3 • Schlage • PIM400-TD2 user guide
Overview
This manual describes the operation and interaction of the Schlage PIM400-TD2 with Access
Control Panels (ACPs) and Wireless Access Point Modules (WAPMs). The PIM400-TD2 is a
product in the AD-400 Wireless Panel Interface Module (WPIM) category. The PIM400-TD2
is wired to the Access Control Panel.
• Connect the PIM400-TD2 to external power using a UL294 listed power supply for
UL installations, and a ULC S318/ULC S319 listed power supply for cUL installations.
Example power supplies include Schlage PS902, PS904, PS906.
• Installation location is determined by the location of the WAPM. The PIM400-TD2 is
ideally installed very close to the access control panel.
• The PIM400-TD2 communicates to the WAPM(s) using radio frequency (RF).
• The WAPM is installed at the access point where access will be controlled and/or
monitored.
• The PIM400-TD2 enclosure is NEMA type 4.
Access Point 1
Status Signals
(J10)
Access Point 2
Control Signals
(J7)
Access Point 1
Control Signals (J8)
Access Point 2
Status Signals
(J11)
Power/Tamper LED (D3) Link 2
Button
Link 1 Button
Tamper Switch
Connector (J1) J19/J20
not used
Power
Connector (J2)
Reset
(S1)
USB Connector (J9)
J5 not used
Tamper
Switch
Internal Antenna
Antenna Module
Receive
LED (D4)
Transmit
LED (D5)
PIM400-TD2 printed circuit board assembly (PCBA)

4 • Schlage • PIM400-TD2 user guide
Getting started
The following is an overview of the steps required to set up the PIM400-TD2:
1. Install the WAPM (AD-400, WPR400, etc). See the installation guide that came with the
WAPM or visit www.allegion.com/us (see Support>Schlage Electronics>Electronic Locks
Technical Library) for more information.
2. Make sure the PIM400-TD2 is located to allow for optimum RF signal transmission.
See Determine the location on page 6 for more information.
3. Before installing the PIM400-TD2, check for proper communication function and linking
with WAPM(s). See Pre-installation test on page 6 for more information.
4. The PIM400-TD2 has been evaluated for UL compliance in indoor applications only.
5. Make sure to follow unique installation procedures if installing on an indoor metallic
wall. Refer to Mount the PIM400-TD2 on page 7 for more information. Consult the
Schlage Utility Software (SUS) user guide for information about conguring the
PIM400-TD2 and the WAPM.
6. Familiarize yourself with the information contained in this user guide.
This user guide is for the PIM400-TD2 only.
Save this user guide for future reference.

5 • Schlage • PIM400-TD2 user guide
Features and components
Feature Description
PIM400-TD2
status
Power and tamper status is indicated at the PWR/Tamper LED (D3).
The LED is steady green when power is on and the tamper is inactive (cover
is on), and blinking green when the tamper switch is activated (cover is off).
Access point
link and
status
The PIM400-TD2 overall status is communicated by a red/green LED for
each access point.
Red LEDs communicate real time and trouble status. The LED is off when
the WAPM is linked; the LED is on when the WAPM is not linked.
Real time status: D40 = access point 1, D43 = access point 2
Trouble status: D1 = access point 1, D2 = access point 2
The PCB is marked with LED locators D1, D2, D40 and D43.
Each access point has clock (CLK) and data (DATA) LEDs that indicate card
and keypad data communication from the PIM400-TD2 to the ACP.
Reset switch Press the reset switch (S1) if the PIM400-TD2 does not seem to operate
properly.
Tamper
switch
The tamper switch senses if the PIM400-TD2 enclosure cover is open or closed.
If closed, the D3 LED is steady green and extended unlock works, if enabled.
If open, the D3 LED is blinking green and extended unlock does not work
even if enabled.
Component Description
Access
control panel
connection
The PIM400-TD2 connects two WAPMs to the ACP.
WAPM (Door) 1 connects through the access point 1 connections on J8 and
J10 to the ACP, and WAPM (Door) 2 connects through the access point 2
connections on J7 and J11.
Power
connector
The PIM400-TD2 power input (J2) is non-polarized. If power is lost or cycled,
upon restoring power, the PIM400-TD2 will continue operation with the same
conguration and linking information. There is no need to re-congure
or re-link.

6 • Schlage • PIM400-TD2 user guide
Model specications
Maximum number of WAPMs Location ACP interface/description
2 Indoor/outdoor Magnetic (clock & data) or
Wiegand (data 1/data 0)
Installation
Determine the location
The PIM400-TD2 communicates with WAPM(s) using radio frequency (RF) signals.
RF signals are diminished by walls, distance, metal objects or barriers. Consider the
following when placing the PIM400-TD2:
• Mount the PIM400-TD2 within 200 horizontal feet of each WAPM. When clear line-of-
sight is available, communication may be possible up to 1000 feet.
• Do not mount the WAPM(s) and the PIM400-TD2 on different oors. The signal may be
degraded and functionality could be severely limited.
• Do not mount the PIM400-TD2 on a metal surface. A separation of at least one inch
must be maintained in all directions from any metal.
• Signal will not pass through metal walls or metal mesh in the walls (stucco). Use a
remote antenna module located outside the room when necessary.
• Moving vehicles will interrupt the signal. Placement distance should be reduced by half
when vehicles may temporarily block the signal.
• Mount the PIM400-TD2 or the remote antenna so that the antenna is vertical for
optimal communication.
Pre-installation test
Once locations for a PIM400-TD2 and WAPM(s) are determined, check performance prior
to installation.
LIf using a remote antenna module, install the antenna as indicated in the ANT400
optional remote antenna module user guide.
1. As close as possible to its exact mounting location, temporarily mount the WAPM to the
access control point (i.e. door, gate, elevator). Do not connect power yet.
LThe WPR400 may be used as a portable range tester to facilitate properly locating
the PIM400-TD2.
2. Temporarily mount the PIM400-TD2 in the exact location and orientation it will be
mounted.
3. Power the PIM400-TD2 with a 12 or 24 VDC supply capable of delivering 250 mA.
4. Put the PIM400-TD2 into link mode. Refer to Link mode on page 12.
5. Go to the access point being tested. Make sure the access point is secure (closed).
6. Connect the battery, or connect to a compatible UL294 or ULC S318/ULC S319 listed
power supply.
7. Verify that linking has occurred, indicated at the WAPM by the green LED ashing and
optionally by an internal sounder beeping. The number of green ashes and audible
beeps should be the same as the channel number to which the PIM400-TD2 is set.

7 • Schlage • PIM400-TD2 user guide
Installation
1. If linking occurred successfully, install the PIM400-TD2. Install and link additional WAPMs.
2. If linking was not successful, move the PIM400-TD2 six to ten inches (15.2 to 25.4 cm)
in any convenient direction and repeat pre-installation test step 7 (see page 6), until
all WAPMs link successfully. If still not successful, move the PIM400-TD2 closer to the
WAPMs and repeat, or add more PIM400-TD2s.
If still not successful, RF interference may be the cause. Refer to the SUS user guide for
information on changing the RF channel.
Mount the PIM400-TD2
1. Remove the cover and place the PIM400-TD2 against the wall in the orientation where it
successfully passed the pre-installation test.
2. Mark the four (4) mounting hole locations on the wall with a pencil using the PIM400-
TD2 enclosure as a template.
3. Remove the PIM400-TD2 from the wall and drill the four holes (Z\zn” diameter drill bit
recommended).
LIf the wall does not adequately support the PIM400-TD2, wall anchors should be
used.
4. If mounted on a non-metallic surface or where no metal is within 1 inch (25 mm) of the
back of the PIM400-TD2, use the #8 x 1Z\x” screws provided.
5. If mounted on a metallic surface or where metal is within 1 inch (25 mm) of the back of
the PIM400-TD2, attach the PIM400-TD2 1 inch (25 mm) from the wall.
LIf a remote antenna is to be used, refer to the ANT400 optional remote antenna
module user guide.

8 • Schlage • PIM400-TD2 user guide
Wire routing
IMPORTANT: When drilling holes in the PIM400-TD2 to accommodate connectors, ensure
that the drill bit does not damage any electronics inside the enclosure. Use light drill
pressure to prevent the bit from entering the enclosure very far. The electronics may be
removed before drilling holes. To remove electronics, remove only the four screws holding
the circuit board to the enclosure. Do not loosen or remove any screws securing the
electronics to the circuit board.
When using the internal antenna, attention to wire routing is very important. Improper wire
routing will reduce the RF range. Wires inside the enclosure should be as short as possible
(i.e. do not coil any excess wire inside the enclosure).
Drill hole(s) in the PIM400-TD2 enclosure to accommodate the size and number of entry/
exit connectors to be used. Holes in the top of the PIM400-TD2 are for remote antenna
installation only. Do not run signal or power wiring through the top of the PIM400-TD2
enclosure.
Internal antenna
Improper wire routing Proper wire routing
Cable/wire specications
Application Part number AWG Description Max distance
DC power input Belden 8760 or equivalent 18 2 conductor 1000 Feet
PIM400-TD2 to ACP Alpha 1298C or equivalent 22 8 conductor
shielded 500 Feet

9 • Schlage • PIM400-TD2 user guide
PIM400-TD2 to ACP connection
Review Features and components on page 5 before connecting the PIM400-TD2
to an ACP.
CAUTION: Disconnect the ACP power and batteries while wiring the PIM400-TD2 to the ACP.
WARNING: Because every ACP is different, always check the panel’s instruction manual for
appropriate interface wiring.
• Use shielded cables for the signal wiring between the PIM400-TD2 and the ACP. For
maximum wire lengths and cable specications, refer to Cable/wire specications above.
• For compliance with UL 294 or ULC S319, product must be used with a UL 294 or
ULC S319 Listed access control panel or unit, respectively.
• Must be used with a UL294 or ULC S318/ULC S319 listed Power Supply capable of
sourcing at least 250mA @12 or 24 VDC (Schlage models PS902, PS904, PS906).
Typical PIM400-TD2 to ACP wiring diagram
Note: Only AP 1 is shown connected.
AP 2 should be connected the same way.
Access Control Panel
Power Supply
12 or 24 VDC
250 mA
+ −
Strike Input
Strike Input Gnd
D1/CLK
D0/DATA
GND
Req. to Enter
Req. to Enter Gnd
Trouble
Trouble Gnd
Status
Status Gnd
Req. toExit
Req. to Exit Gnd
Panel Interface Module (PIM400-TD2)
Access Control Panel (ACP)
J2
J8 J10J7 J11
Earth
Ground
If required by local code
or site requirement, run
shielded cable through
grounded conduit.
DO NOT
connect cable
shields at
PIM400-TD2
18 AWG, 1000 feet
max run length
LUnsupervised, ground switched inputs to panel shown. Some ACPs require
supervised inputs and/or “dry/contact” isolated inputs. The optional Schlage dry
contact relay board (RLBD) is available for these applications.
LThe PIM400-TD2 can also be powered by the ACP power supply or a separate
external power supply.

10 • Schlage • PIM400-TD2 user guide
ACCESS CONTROL PANEL CONNECTIONS
Connector
PIM400-TD2
signal ACP signal Description/Explanation
J2 12V+ 12 or 24 VDC
PIM400-TD2 inputs for 12 or 24
VDC power.
Draws 250mA max.
If the Access Control Panel
(ACP) reader power outputs do
not source enough current for
the PIM400-TD2, use the ACP
main regulated 12 VDC power
supply or a separate UL294 or
ULCS318/ULCS319 listed 12 or
24 VDC power supply.
Power input is non polarized.
J10 for
Access
Point A
J11 for
Access
Point B
J10/J11
(1)
REQ TO
ENTER
Request to Enter
input signal
PIM400-TD2 output indicating
when the access point exterior
door handle is making a request
to enter.
Connect to the ACP request to
enter input.
Connect only if the access point
needs to have Request to Enter
function.
The request to enter signal
polarity may be congured using
the sus. This setting is shared
with the request to exit signal.
Output is pulled-up to 5 VDC and
can sink 50mA.
J10/J11
(2)
Request to Enter
common contact
(GND)
J10/J11
(3)
TROUBLE
General purpose
alarm input signal
PIM400-TD2 output indicating
trouble is reported by the access
point.
Logic polarity is congurable
using the SUS.
Output is pulled-up to 5 VDC and
can sink 50mA.
General purpose
alarm common
contact (GND)
J10/J11
(4)
J10/J11
(5)
DOOR 1/2
STATUS
Door Status input
signal
PIM400-TD2 output indicates
the position of the access point
portal, open or closed.
Connect only if the ACP needs
to know the access point portal
state.
Logic polarity is congurable
using the SUS.
Output is pulled-up to 3.6 VDC
and can sink 50mA.
J10/J11
(6) Door Status input
common contact
(GND)

11 • Schlage • PIM400-TD2 user guide
ACCESS CONTROL PANEL CONNECTIONS
Connector
PIM400-TD2
signal ACP signal Description/Explanation
J10 for
Access
Point A
J11 for
Access
Point B
J10/J11
(7)
REQ TO EXIT
Request to Exit input
PIM400-TD2 output indicating
when the access point interior
door handle is making a request
to exit.
Connect to the ACP request to
exit input.
Connect only if the access point
needs to have request to exit
function.
The request to exit signal polarity
can be congured using the
SUS. This setting is shared with
the request to enter signal.
Output is pulled-up to 5 VDC and
can sink 50mA.
J10/J11
(8)
Request to Exit
common contact
(GND)
J11 (9) +5V 5 VDC
RESERVED
5 VDC power supply pin for the
RLBD, dry contact relay board.
J8 for
Access
Point A
J7 for
Access
Point B
J8/J7 (1)
STRIKE
INPUT
Normally Open
strike relay contact
Strike input monitors the access
panel strike relay.
Connect the STRIKE signal to
the normally open terminal of the
strike relay.
Connect the GROUND signal
to the common terminal of the
strike relay.
Connect only if the access point
needs to be unlocked (door) or
raised (gate).
J8/J7 (2) Common strike relay
contact
J8/J7 (3) D1/CLK Clock or Data 1
output
PIM400-TD2 outputs used to
present card data to the ACP.
For an access point with a
magnetic reader, will present
clock and data signals to the ACP.
For an access point with a
Wiegand or proximity reader, will
present data1 and data0 signals
to the ACP.
If initial hookup fails to operate,
switch wires at these terminals.
Output is pulled-up to 3.6 VDC
and can sink 50mA.
J8/J7 (4) DATA Data or Data 0 input
J8/J7 (5) GND Signal ground
Common signal ground for
the EXIT REQ, DOOR STAT,
TROUBLE, DATA/D0 and CLK/
D1 signals.

12 • Schlage • PIM400-TD2 user guide
Optional remote antenna
The PIM400-TD2 may be used with a remote antenna if:
• the PIM400-TD2 must be located in a remote, more serviceable or secure area, or
• it is necessary to increase the RF range.
Optional remote antenna models are shown below. For more information on remote antenna
use and installation, refer to the ANT400 optional remote antenna user guide.
Optional remote antenna models
Model Enclosure Location Description
ANT400-REM-CEILING Indoor Optional remote omni-directional
antenna (0 DB gain)
ANT400-REM-I/O NEMA 4 Indoor/outdoor Optional remote omni-directional
antenna (0 DB gain)
ANT400-REM-HALL Indoor Optional remote bi-directional
antenna (3.5 DB gain)
ANT400-REM-I/O+6dB NEMA 4 Indoor/outdoor Optional remote directional
antenna (6 DB gain)
Link mode
1. Press and release LINK 1 switch (SW2) to link access point 1, or LINK 2 (SW3) to link
access point 2. The corresponding LED (LED1 for LINK1; LED2 for LINK2) ashes red
and green. This indicates that the PIM400-TD2 is in link mode. To abort link mode, press
the same switch again.
2. When the PIM400-TD2 is powered and in link mode, the system is ready for the WAPM
to initiate linking.
Refer to the “Link” section of the user guide for the desired WAPM.
Schlage Utility Software (SUS)
LThe Schlage utility software (SUS) is used for programming and setup only.
The SUS is used to congure this device’s links and outputs. For information about the SUS,
see the Schlage utility software user guide.
Reset to factory defaults
LAll conguration information will be deleted and the PIM400-TD2 will be reset to
factory defaults!
1. Remove the main cover.
2. Press and hold both link buttons for over 3 seconds.
3. Release both link buttons. The PIM400-TD2 will blink the red lights beside each link
button while conguration reset takes place.
4. The two green lights beside the link buttons will blink 3 times when the reset is
complete.
5. Replace the main cover.

13 • Schlage • PIM400-TD2 user guide
DC power
This connection is always required regardless of the system application or conguration.
Refer to page 7 through page 9 for how to connect DC power to the PIM400-TD2.
Complete the installation
After all required connections have been made, connect the power and ACP standby
batteries (optional) to the panel.
Troubleshooting
Problem Possible cause(s) Solution
The PIM400-TD2 does
not communicate with
the Access Control
Panel (ACP).
Signal wiring
connections with
the ACP may not be
properly connected.
Ensure that signal wiring at the
PIM400-TD2 and at the ACP is
properly connected. Refer to PIM400-
TD2 to ACP connection on page 9
through page 11.
Check the ACP’s instruction manual
for appropriate interface wiring.
Note: Some ACPs require supervised
inputs and/or “dry/contact” isolated
inputs. The optional Schlage dry
contact relay board (RLBD) is
available for these applications.
The PIM400-TD2 does
not communicate with
Wireless Access Point
Modules (WAPMs)
The antenna module
may not be properly
installed.
Ensure that the antenna module is
installed and properly seated.
Wiring may cause
interference with the
internal antenna on the
antenna module.
Check to ensure that wiring is properly
routed in the PIM400-TD2 enclosure
and the area around the internal
antenna is clear of any wire. See
Wire routing on page 7 for more
information.
The PIM400-TD2 may
not be linked to the
WAPM(s).
Link the PIM400-TD2 to the WAPM.
See Link mode on page 12 for more
information. Also refer to the WAPM’s
user guide for link instructions.

14 • Schlage • PIM400-TD2 user guide
FCC/IC statements
The communication module is a 900 MHz transceiver for electronic locks and non-lock devices. The communication
module links the access device to the Access Control Management System, with feedback control to the Access
Device via a wireless means. The module contains the embedded rmware implementing the radio physical and
data layers. There are 5 antennas approved for use with this module:
Approved antenna list:
The required antenna impedance is 50 ohms.
1. PCB trace antenna with a 5.7dBi maximum gain
2. p/n: 23520587, dual beam antenna with a 3.5dBi gain (ANT400-REM-HALL)
3. p/n: 23530579, multi band directional panel antenna with 8.5dBi gain (ANT400-REM-I/O+dB)
4. p/n: 23530553, dual band quasi-omni panel antenna with 4.5dBi gain (ANT400-REM-I/O)
5. p/n: 23520561, multi band omni antenna with 2dBi gain (ANT400-REM-CEILING)
Antennas having a gain greater than the antenna type approved in the list are strictly prohibited for use with this
device. However, antennas of the same type with a gain equal to or less may be used. Examples of this may include:
• a directional panel antenna with a gain equal to or less than 8.5 dBi may be used with this module
• an omni-directional antenna with a gain equal to or less than 2.0 dBi may be used with this module
Specications of the radio module:
Power output: 18.6 dBm
Modulation: BPSK-40
Operating frequency: 906 -924 MHz
Note: The intended use of this module is not for the general public. It is generally for industry/commercial use only.
This transceiver is to be professionally installed in the end product by Allegion, and not by a third party. The Schlage
XPB-COMAD400V2 900 MHz Communication Board Module will not be sold to third parties via retail, general public
or mail order. In the case of a repair, the transceiver will be replaced by a professional Installer.
Federal Communication Commission interference statement
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part
15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a
residential installation. This equipment generates uses and can radiate radio frequency energy and, if not installed
and used in accordance with the instructions, may cause harmful interference to radio communication. However,
there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful
interference to radio or television reception, which can be determined by turning the equipment off and on, the user
is encouraged to try to correct the interference by one of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
• Consult the dealer or an experienced radio/TV technician for help.
This device complies with Part 15 of the FCC Rules.
Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and
(2) this device must accept any interference received, including interference that may cause undesired operation.
FCC/IC caution
Any changes or modications not expressly approved by the party responsible for compliance could void the user’s
authority to operate this equipment.
To comply with FCC/IC RF exposure limits for general population/uncontrolled exposure, the antenna(s) used for
this transmitter must be installed to provide a separation distance of at least 20 cm from all persons and must not be
collocated or operating in conjunction with any other antenna or transmitter.
Industry Canada statements
This Device complies with Industry Canada License-exempt RSS standard(s). Operation is subject to the following
two conditions:
(1) this device may not cause interference, and
(2) this device must accept any interference, including interference that may cause undesired operation of the device.
Under Industry Canada regulations, this radio transmitter may only operate using an antenna of a type and
maximum (or lesser) gain approved for the transmitter by Industry Canada. To reduce potential radio interference
to other users, the antenna type and its gain should be so chosen that the equivalent isotropically radiated power
(e.i.r.p.) is not more than that permitted for successful communication.
This radio transmitter, 8053B-COMAD400V2, has been approved by Industry Canada to operate with the
antenna types listed below with the maximum permissible gain and required antenna impedance for each
antenna type indicated.

15 • Schlage • PIM400-TD2 user guide
Approved antenna list:
The required antenna impedance is 50 ohms.
1. PCB trace antenna with a 5.7dBi maximum gain
2. p/n: 23520587, Dual Beam Antenna with a 3.5dBi gain (ANT400-REM-HALL)
3. p/n: 23530579, Multi band Directional Panel antenna with 8.5dBi gain (ANT400-REM-I/O+dB)
4. p/n: 23530553, Dual Band Quasi-Omni Panel Antenna with 4.5dBi gain (ANT400-REM-I/O)
5. p/n: 23520561, Multi band Omni Antenna with 2dBi gain (ANT400-REM-CEILING)
Antennas having a gain greater than the antenna type approved in the list are strictly prohibited for use with this
device. However, antennas of the same type with a gain equal to or less may be used. Examples of this may include:
• a directional panel antenna with a gain equal to or less than 8.5 dBi may be used with this module
• an omni-directional antenna with a gain equal to or less than 2.0 dBi may be used with this module.
To comply with IC RF exposure limits for general population/uncontrolled exposure, the antenna(s) used for this
transmitter must be installed to provide a separation distance of at least 20 cm from all persons and must not be
collocated or operating in conjunction with any other antenna or transmitter.

Customer Service
1-877-671-7011 www.allegion.com/us
© Allegion 2015
P516-096 Rev. 12/15-f