schmalenberger fluvo LuchsNT User manual

LuchsNT RGB / LED
Operator´s Manual
Translation of the original
27142 – A.1
GB

OPERATOR'S MANUAL
2
Subject to technical changes
Schmalenberger GmbH + Co. KG
D-72072 Tübingen / Germany LuchsNT
Version: 27142-A.1
Table of Contents
1Introduction.....................................................................................................3
1.1 General Information ....................................................................................................3
1.2 Safety Instructions.......................................................................................................3
1.3 Packaging contents.....................................................................................................4
2Functional features.........................................................................................5
2.1 LuchsNT RGB control unit interface............................................................................5
2.2 LuchsNT LED control unit interface ............................................................................5
2.3 Functional sequence after mains voltage ON.............................................................5
2.4 Switching the spotlights ON / OFF..............................................................................5
3Connections and adjusters............................................................................6
3.1 Terminal compartment overview.................................................................................6
3.2 Terminal compartment disconnection.........................................................................7
3.3 Mains power connection .............................................................................................7
3.4 Spotlights connection area..........................................................................................7
3.5 Configuration via DIP switch.......................................................................................8
3.6 "Analog" control terminal.............................................................................................9
3.7 "DMX" control terminal................................................................................................9
3.8 "BUS" control terminal...............................................................................................10
3.9 DIAG system diagnosis button..................................................................................11
3.10 Sensor button connection diagram ...........................................................................12
4Functional Description.................................................................................13
4.1 Operating mode ........................................................................................................13
4.2 LED display...............................................................................................................14
4.3 Synchronisation of several LED control units............................................................14
4.4 Individual control of the RGB spotlights....................................................................15
4.5 Colour light control with customer-specific DMX control unit....................................15
4.6 External sensor button via converter box 3.0............................................................16
5Luchs-NT RGB and LED-white spotlights...................................................18
5.1 Standard....................................................................................................................18
6Installation of LuchsNT lighting unit...........................................................19
6.1 Installation instructions..............................................................................................19
6.2 Spotlights – LED control unit connecting cable.........................................................19
7Technical data...............................................................................................20
7.1 Technical specification..............................................................................................20
7.2 Dimensions ...............................................................................................................21
7.3 Device installation.....................................................................................................22
7.4 Type plate .................................................................................................................23
7.5 Guarantee seal..........................................................................................................23

OPERATOR'S MANUAL
LuchsNT
Version: 27142-A.1
Subject to technical changes
Schmalenberger GmbH + Co. KG
D-72072 Tübingen / Germany 3
Electronic devices are not regular household waste. In accordance with Directive 2002/96/EC of
the European Parliament and Council of January 27, 2003 regarding electrical and old
electronic devices, they must be disposed of properly. Please drop these devices off at public
collection points provided for that purpose when you have finished using them.
In addition, the notes and information in the LuchsNT (27134)
assembly instructions apply.
1 Introduction
The LuchsNT spotlights is an independent lighting unit for illuminating swimming pools.
The LuchsNT lighting unit consists of the spotlights and control unit. It is available in
LED-white and RGB versions. The light intensity of the LED-white version can be
controlled via a 0-10V interface. The RGB colour light is controlled via the DMX
interface. The 2-wire technology makes it possible to operate RGB spotlights with only 2
wires. All spotlights are connected in parallel.
1.1 General Information
For your own safety and to protect the product, please read the
Operator's Manual carefully before starting with the installation and
settings!
All persons involved in setting up, commissioning, operating, maintaining, and repairing
this device must:
be appropriately qualified
meticulously observe the operator's manual
consider the operator's manual to be part of the product
keep the operator's manual in a safe place throughout the service life of the product
forward the operator's manual to each successive owner or user of the product
ensure that all additions that are received are inserted into the operator's manual
observe all legal requirements
1.2 Safety Instructions
Danger of lethal electrical current!
Electrical connections must only be made by a professional electrician in
accordance with VDE Regulation 0100. Observe the local requirements of
the responsible electrical power provider as well as standards and safety
requirements for electrical systems in swimming pools.
In case of damage caused by failure to observe the information provided in these
operator's manual, all claims under warranty shall be void. The manufacturer cannot
accept any liability for resulting consequential damages.
The LuchsNT spotlights must only be operated with the control unit
designed for it by the manufacturer.

OPERATOR'S MANUAL
4
Subject to technical changes
Schmalenberger GmbH + Co. KG
D-72072 Tübingen / Germany LuchsNT
Version: 27142-A.1
Attention: The NT control unit is still capable of conducting dangerous voltages for a
short time after it is turned off.
The LuchsNT spotlights must only be operated under water.
The device must only be used when it is in flawless technical condition.
Eliminate malfunctions without delay.
Check the device and the electrical power line at regular intervals for damage.
The L/N/PE connection of the power supply voltage must be made in accordance with
VDE 0100 and VDE 0160.
A protective and isolating device must be provided for turning off the power supply.
Before beginning installation and service work, the power supply connection must be
switched off.
The device does not contain any components that require servicing by the user.
The housing cover may only be opened by the manufacturer. (guarantee seal)
In the event of a malfunction we recommend contacting the supplier.
Attention:
Failure to observe the safety instructions, for example touching live parts while the
device is open or handling the device in an improper manner is hazardous with
potentially fatal consequences.
If the guarantee seal is destroyed, the guarantee and manufacturer's warranty shall be
rendered null and void
If the values listed in the technical data are exceeded there is danger of the device
overheating, which can destroy the power supply and adversely affect electrical safety.
1.3 Packaging contents
Control input
Jumper at control terminal
Operator’s Manual

OPERATOR'S MANUAL
LuchsNT
Version: 27142-A.1
Subject to technical changes
Schmalenberger GmbH + Co. KG
D-72072 Tübingen / Germany 5
2 Functional features
2.1 LuchsNT RGB control unit interface
DMX interface colour light control
0-10V analog interface light intensity control 0-100 %
6 fixed colours
1 fixed colour gradient
Synchronisation bus for synchronous control of several control units
Control bus for optional functional enhancement
2.2 LuchsNT LED control unit interface
0-10V analog interface light intensity control 0-100 %
Synchronisation bus for synchronous control of several control units
Control bus for optional functional enhancement
2.3 Functional sequence after mains voltage ON
The system (control unit + spotlights) boots.
The system is ready for operation after 2 seconds. This means that after 2 seconds
the spotlights are lit, depending on activation and assignment of the interface.
2.4 Switching the spotlights ON / OFF
via START / STOP input
The input can be set to latching or momentarily via DIP switch 3
Delivery condition: latching with bridge
The connected buttons and switches must be potential-free
For a detailed functional description, see section 3.4
If the spotlights are OFF via the STOP input or control input Analog IN=0V or DMX
control input, this is detected by the device and after 60 seconds the output terminals
LED + and LED – are disconnected via a relay. If the spotlights are switched ON, a relay
switches the voltage back to the output terminal.

OPERATOR'S MANUAL
6
Subject to technical changes
Schmalenberger GmbH + Co. KG
D-72072 Tübingen / Germany LuchsNT
Version: 27142-A.1
3 Connections and adjusters
3.1 Terminal compartment overview
The control unit has the following connections and adjusters marked on the printed
circuit board in the terminal compartment:
L, N and PE: Mains input.
LED+, LED-: Spotlights connection 24 V
1: "0..10V: Standard signal input 0..10V with potentiometer power supply 10 V
2: DMX OUT: DMX output for series operation
3: SYNC OUT: Bus control unit synchronisation output
4: BUS: Manchester bus interface
5: DMX PWR: DMX 24V power supply for i-light
6: DMX IN: DMX input for series operation
7: SYNC IN: Control unit synchronisation input
8: LED: RGB lighting "START/STOP" piezo button
9: START/STOP Sensor button input on/off
10: COLOR Sensor button input colour selection
11: DIAG: Button and 2 LEDs for diagnostic purposes
12: ADDR: Manchester bus and DMX interfaces: Address setting
13: KONFIG: Device configuration
Notice: Rotary and dip switches 12 and 13 are read in once when the device is started.
A change of switch positions during operation is therefore not accepted until the next
device start.
Terminal compartment
disconnection

OPERATOR'S MANUAL
LuchsNT
Version: 27142-A.1
Subject to technical changes
Schmalenberger GmbH + Co. KG
D-72072 Tübingen / Germany 7
3.2 Terminal compartment disconnection
Safety instruction:
Two terminal compartment disconnects are provided for the connection
areas of the spotlights and the piezo buttons. They are designed to
prevent loose connecting lines from setting the piezo button under mains
voltage.
The terminal chamber disconnects are inserted and can be removed for easier wiring as
follows:
Terminal compartment disconnection
Installation is in the opposite order.
3.3 Mains power connection
The L/N/PE connection of the power supply voltage
must be made in accordance with VDE 0100 and
VDE 0160.
A protective and isolating device must be provided
for turning off the power supply.
Terminal "PE" must always be connected to a
protective ground!!
Screw terminal wire cross-section 0.2 to 2.5 mm²
Operation on circuit breaker 16A
Trip characteristic B: for 3 control units
Trip characteristic C: for 6 control units
3.4 Spotlights connection area
Screw terminals for wire cross-section
0.2 to 2.5 mm²
4 pin: connection 2xLED+
2xLED-

OPERATOR'S MANUAL
8
Subject to technical changes
Schmalenberger GmbH + Co. KG
D-72072 Tübingen / Germany LuchsNT
Version: 27142-A.1
3.5 Configuration via DIP switch
Notice: Rotary and dip switches 12 and 13 are read in once when the device is started.
A change of switch positions during operation is therefore not accepted until the next
device start.
The operating mode is set with switch position 1-2
Function MODE Pos.1 Pos.2 Note
Analog OFF OFF Delivery condition
DMX ON OFF
Piezo OFF ON
fixed colours + colour
gradient
unassigned ON ON
Notice: The functions under positions 1 and 2 can only be actively selected with the
RGB control unit version. In the LED control unit version, the "Analog" function is always
active regardless of position 1 and 2.
Position 3 determines whether input 9 "START/STOP" is to be used for a button or a
latching switch:
Function Pos.3 Note
Button ON the device switches for each signal pulse
latching switch OFF the device is switched as long as the signal
is present
Position 4 determines whether a single-colour or an RGB button is connected to input 8
"LED".
Function Pos.4 Note
Sensor button RGB ON Multicoloured visual feedback
Single-coloured sensor
button OFF Single-coloured visual feedback
Position 5 determines whether the device works as MASTER or SLAVE in synchronous
mode
Function Pos.5 Note
SYNC Slave ON
SYNC Master OFF Delivery condition
Position 6 defines the BUS communication with the converter box via terminal
connection 4.
Function Pos.6 Note
BUS Master ON Control unit with converter box 3.0
BUS Slave OFF Normal operation

OPERATOR'S MANUAL
LuchsNT
Version: 27142-A.1
Subject to technical changes
Schmalenberger GmbH + Co. KG
D-72072 Tübingen / Germany
9
Position 7 is unassigned.
Position 8 defines the termination of the DMX bus.
Function Pos.8 Note
DMX terminating resistor
active ON Device identified as BUS terminal device
DMX terminating resistor
inactive OFF
3.6 "Analog" control terminal
Used to control the light intensity.
The control function is always active for the LED-white control unit
Or for the RGB control unit in operating mode
Analog
Piezo
The standard signal input 0...10V has the following connection terminals:
10V Power supply voltage for potentiometer
IN Signal input
GND
Note:
Min. potentiometer resistance value 1 k-
typically 100 k(optional accessories)
A defined signal must be present at signal
input IN.
Delivery condition: Wire jumper between IN
and 10V
3.7 "DMX" control terminal
+ Line "A" or "+"
– Line "B" or „–“
GND / shield
DMX signal display
LED If the LED lights up, a DMX signal is
present at the input
Note:
The interface is electrically isolated
For the bus installation, shielded cables twisted in pairs must be used. E.g. CAT6
network cable
Ensure that the polarity of the bus connection is correct

OPERATOR'S MANUAL
10
Subject to technical changes
Schmalenberger GmbH + Co. KG
D-72072 Tübingen / Germany LuchsNT
Version: 27142-A.1
If the polarity is reversed, the DMX signal display may light up!
The DMX bus must be terminated at both ends with a line terminator. Make sure that
the terminating resistor is activated correctly, see 3.4 Switch pos.8. Operation without
correct BUS termination can lead to transmission errors.
3.7.1 DMX – Setting the start address
DMX
0 1 2 3 4 5 6 7 8 9 A B C E E F
DMX
start
address 1 1 16 31 46 61 79 91 106 121 136 151 166 181 196 211
Note on switch position 0
Variable, only on request
DMX start address 1 default setting
3.7.2 DMX – Individual control of the LED spotlights
This is optionally available on request. Not included in the standard version.
3.8 "BUS" control terminal
A Line "A"
B Line "B"
DMX signal display
LED If the LED lights up, a BUS signal is
present
Interface for operation via BUS, for connecting optional extras, e.g. external sensor
button via converter box 3.0, see section 4.6
Note:
The connection is protected against polarity reversal
Max. line length 30 m
Recommended control line 2 x 0.5 mm²
BUS address setting
BUS
0 1 2 3 4 5 6 7 8 9 A B C E E F
BUS
address 0x80 0x81 0x82 0x83 0x84 0x85 0x86 0x87 0x88 0x89 0x8A 0x8B 0x8C 0x8D 0x8E 0x8F

OPERATOR'S MANUAL
LuchsNT
Version: 27142-A.1
Subject to technical changes
Schmalenberger GmbH + Co. KG
D-72072 Tübingen / Germany 11
3.9 DIAG system diagnosis button
A basic diagnosis is started via button 11 DIAG as follows:
Basic diagnosis: brief push of the button (shorter than 5 s)
The diagnostic mode can be terminated at the end of the diagnosis by pressing the
button again.
3.9.1 Basic diagnosis
The basic diagnosis includes the following procedure: After the start of the diagnosis,
connected spotlights are searched for. The diagnostic LED 1 flashes during the
spotlights search. After completion of the search, diagnostic LED 1 lights up
permanently, diagnostic LED 2 flashes indicating the number of spotlights found. In
addition, the spotlights are cyclically controlled alternating every 2 s as follows:
white + red + green + blue
white
red
green
blue

OPERATOR'S MANUAL
12
Subject to technical changes
Schmalenberger GmbH + Co. KG
D-72072 Tübingen / Germany LuchsNT
Version: 27142-A.1
3.10 Sensor button connection diagram
LED control unit
ON/OFF
In the delivery state, the "Start/Stop" input 9
is switched via DIP3 = OFF as a
latching input.
Delivery condition: Wire jumper between 24 V and
If "Start/Stop" input 9
is switched via DIP3 = ON as a
button input, then the spotlights can be switched
ON/OFF via a potential-free sensor button.
RGB control unit
ON/OFF
With piezo operating mode
For the LED-white control unit or analog operation, the
sensor button illumination can be connected to LED1
as shown in the picture on the left. The switching
operation is reported back.
For the RGB control unit, an RGB button can be
optionally connected which visually reports back the
spotlights colours.
In order to control the "Piezo" function of fixed colours
and colour gradients, an additional sensor button must
be connected to the "COLOR" input. The keying
pulses at the "COLOR" input are used to switch
between the individual moods.
Functional description, see section 4.1.3
The 27138 "Sensor button" operator's manual applies here
3.10.1 Sensor button - connection assignment
Wire colour Functions
White Switching contact S1
Brown Switching contact 24 V
Grey LED1
Yellow LED2
Green LED3
3.10.2 Sensor button - technical information
Effect of switching: Pulse activated one time
Electrical function: normally open / N/O contact
Electrical data: Imax = 200 mA / UB = 24 V DC

OPERATOR'S MANUAL
LuchsNT
Version: 27142-A.1
Subject to technical changes
Schmalenberger GmbH + Co. KG
D-72072 Tübingen / Germany 13
4 Functional Description
4.1 Operating mode
The 3 possible operating modes are described below:
4.1.1 Analog input mode DIP1=OFF / DIP2=OFF
All LEDs of a spotlights are controlled with the same intensity. The intensity can be set
via the standard signal input . They are enabled via the "START/STOP" input
according to the setting on dip switch 3 (latching/momentarily).
4.1.2 DMX mode DIP1=ON / DIP2=OFF
RGBW LEDs of a spotlights are controlled according to DMX. They are enabled via the
"START/STOP" input according to the setting on dip switch 3 (latching/momentarily).
4.1.3 Piezo mode DIP1=OFF / DIP2=OFF
RGBW-LEDs of a spotlights are controlled according to the program selection. They are
enabled via the "START/STOP" input according to the setting on dip switch 3
(latching/momentarily).
The program is selected via the keying pulse at the "COLOR" input.
The following programs are stored:
Program 1 2 3 4 5 6 7
Colour Turquoise Red Yellow Green Light
blue Dark
blue Colour
gradient
For the colour gradient, the colours are selected in sequence 1-6 one after the other.
The idle time per colour is 120 sec and the fade time is 20 sec.
The RGB lighting of the sensor button connected to connection 8 shows the currently
selected colour. In this case, the RGB lighting of the button flashes to indicate the
selection of the colour gradient program.
For a sensor button with single-colour lighting, the button lighting is briefly dimmed when
the colour change button is pressed if the dip switch is set accordingly.
Notice: Rotary and dip switches 12 and 13 are read in once when the device is started.
A change of switch positions during operation is therefore not accepted until the next
device start.

OPERATOR'S MANUAL
14
Subject to technical changes
Schmalenberger GmbH + Co. KG
D-72072 Tübingen / Germany LuchsNT
Version: 27142-A.1
4.2 LED display
The control unit on the front indicates the current device status. A
green LED flashing once every second indicates that a device is
ready for operation. The green LED is lit continuously when
spotlights are active.
In the event of an error, the error is indicated by a flashing code on
the red LED. The following errors are defined:
Error Flash
code Cause
Internal error 1
Excess temperature 2 Unit temperature exceeds shut-off
temperature
Spotlights power supply
module 3 Spotlights power supply does not supply
voltage
Power supply module relay 4 Output relay does not switch
The flash code indicates how often the red LED flashes in succession.
If several errors are present at the same time, they are displayed one after the other.
After the last error is displayed, the first active error is displayed again.
4.3 Synchronisation of several LED control units
The synchronisation bus is available for the operation of several control units with the
same control signal. A device is operated as a MASTER to which the control signals are
connected. The remaining devices are operated as SLAVE.
The MASTER [OFF] / SLAVE [ON] setting
is configured via pos. 5
A SLAVE device uses only the brightness information from the synchronisation bus.
Each LED control unit has one input and one output for synchronisation. This involves an
RS485 bus. The input and output are connected in parallel and are therefore electrically
equivalent.
An LED control unit can be configured as either a master or slave via DIP switch 5. Up to
32 slaves can be connected to one master. The total cable length of the synchronisation
cable should not exceed a total length of 30 m. For longer lengths, a 120 ohm
termination must be provided at both ends of the synchronisation bus.
The following terminal connections must be made for synchronous operation of several
control units:
SYNC A => SYNC A
SYNC B => SYNC B
SYNC GND => SYNC GND
The terminal groups "IN" and "OUT" are connected in parallel on the
printed circuit board and are therefore equivalent.

OPERATOR'S MANUAL
LuchsNT
Version: 27142-A.1
Subject to technical changes
Schmalenberger GmbH + Co. KG
D-72072 Tübingen / Germany
15
4.4 Individual control of the RGB spotlights
This is optionally available on request. Not included in the standard version.
4.5 Colour light control with customer-specific DMX control unit
The coloured light can be controlled via a customer-specific DMX control unit, e.g.
central house control. Several different DMX receivers, e.g. pool lighting, room and hall
lighting, can be connected to each other via the DMX bus. The termination of the DMX
bus terminating resistor must be set correctly. Whether a signal is present at the DMX-IN
input terminal is visible via the diagnostic LED in the terminal compartment.
ON / OFF
Analog
DMX
DIP5 : OFF DIP5 : ON DIP5 : ON

OPERATOR'S MANUAL
16
Subject to technical changes
Schmalenberger GmbH + Co. KG
D-72072 Tübingen / Germany LuchsNT
Version: 27142-A.1
4.6 External sensor button via converter box 3.0
Sensor buttons connected to the converter box (optional accessory) behave in the same
way as the ON/OFF sensor buttons connected to the control unit. The total of four
possible buttons are OR-linked to each other. When a sensor button is confirmed, all
connected sensor buttons give visual feedback, provided they are illuminated.
The button lighting lights up when the spotlights are ON and light up.
It is unlit when spotlights are OFF.
The LEDs go out during the blocking time.
In the connected converter box, the LED display and digital outputs DOUT1 to DOUT3
show the following status of the switch box:
DOUT4 is switched when spotlights are switched on.
The status of the digital outputs DOUT1 to DOUT3 is displayed via the green LEDs in
the converter box. The output is then active when the green LED lights up.
Connection cable
4 x 0.5 mm² max. 30 m
BUS control line
Power supply voltage
Sensor button 1-3
Lit 1x
Rotary switch
Mode A

OPERATOR'S MANUAL
LuchsNT
Version: 27142-A.1
Subject to technical changes
Schmalenberger GmbH + Co. KG
D-72072 Tübingen / Germany
17
Configuration
Control unit setting:
Position 6: ON
Position 3: ON
Function: BUS Master
Function: Button
Converter box 3.0 setting
Rotary switch: MODE A Requirement: SW 0.23 or higher
BUS
LED The communication between converter box and switch box is active when
the yellow BUS-LED in the converter box lights up.
POWER
LED The 24V operating voltage is applied in the converter box when the red
POWER LED lights up. The converter box is ready for operation.
The LuchsNT LED control unit is connected to the converter box via a 4-wire cable.
BUS: two wires, any polarity.
Power supply voltage: two wires
If the converter box is connected with mode A, no further bus subscribers can be
connected.
External buttons via the converter box can also be connected in the synchronous mode
of several control units. The connection is made to the SYNC-MASTER device.

OPERATOR'S MANUAL
18
Subject to technical changes
Schmalenberger GmbH + Co. KG
D-72072 Tübingen / Germany LuchsNT
Version: 27142-A.1
5 Luchs-NT RGB and LED-white spotlights
5.1 Standard
Operation only possible together with LuchsNT control unit.
Dimensions / connection cable / type of installation are the same for LED-
white and RGB.
Connection cable
2-wire sheathed cable
Standard length 3 m; other lengths on request
Cable outer diameterø 5.80 mm
Wire cross-section 1.5 mm² / AWG24
Colour code of cable wires
red -Power supply voltage VCC +
black -Power supply voltage GND –
Maximum electrical power per spotlights 33 W
The spotlights must only be operated under water
The spotlights is fitted with temperature protection.

OPERATOR'S MANUAL
LuchsNT
Version: 27142-A.1
Subject to technical changes
Schmalenberger GmbH + Co. KG
D-72072 Tübingen / Germany
19
6 Installation of LuchsNT lighting unit
6.1 Installation instructions
The connecting cable between spotlights and LED control unit, as well as connectible
control lines, is a communication cable. It is essential to ensure that power supply cables
and communication cable are separated. In addition to the requirements for ensuring
the electric separation of the systems in accordance with DIN VDE 0100-520 "Wiring
Systems", electromagnetic interference must also be taken into account. In order to
avoid interference, observe the specifications for communication cabling according to
DIN EN 50173 and DIN EN 50174 (VDE 0800-174).
The maximum cable length between spotlights and LED control unit is 30m.
Pay attention to the cable cross-section.
6.2 Spotlights – LED control unit connecting cable
Applies to LED-white and LED-RGB
Connecting cable
Cable length <10 m cable cross-section 2.5 mm²
Cable length >10 m cable cross-section 4.0 mm²
Spotlights connecting cable
3 m / 10 m / 20 m with cable cross-section 1.5 mm²
Connecting cable
Connecting cable
Spotlights
connectin
g
cable
Spotlights
connectin
g
Connection
p
oint
Connection point

OPERATOR'S MANUAL
20
Subject to technical changes
Schmalenberger GmbH + Co. KG
D-72072 Tübingen / Germany LuchsNT
Version: 27142-A.1
7 Technical data
7.1 Technical specification
Dimensions max. W x H x D (in mm)
Weight 205 x 130 x 270
approx. 3.2 kg
Mains input (L, N, PE)
Nominal voltage Uin
Input voltage range UN
Nominal input current IN max.
Standby power /standby losses
230 V AC, 50 Hz 1~
100 … 264 V AC 50/60 Hz
1.5 A for 230 V AC or 2.2 A for 115 V AC
5 W
Output (0 V, 24 V)
Nominal voltage Uout
Output current Iout max.
Efficienc
y
t
y
pe
24 V DC SELV
5.5 A / 8.5 A
90 %
Protection and monitoring
Mains input fuse F1
Current limitation
Overload-proof
Open-circuit proof
Excess temperature
T1.6 (250V)
continuously short-circuit proof
yes
yes
Power derating Tamb> 50°C
Shut-off Tamb> 70°C
Safety
Output:
Protection class
VDE 0805/EN60950/IEC950
Safety extra-low voltage SELV
Class I
EMC
EN55011
EN61000-6-1
Ambient temperature
Operation
Storage
-30°C to +50C
-40C to 70C
Degree of protection IP65 Only if unused cable screw
connections are sealed with plugs
Mains / LED connection terminals
Rigid cable cross-section
Flexible cable cross-section
with ferrule
max. 4.0 mm²
max. 2.5 mm²
Feedback /control contact connection terminals
Rigid cable cross-section
Flexible cable cross-section
with ferrule
0.5 … 1.5 mm²
0.5 … 1.0 mm²
Piezo button
Voltage on button and LED
Switching threshold for button
LED current
22.5 … 25.5 V DC
10 … 14 V DC
max. 30m A DC
Display LED – GREEN
LED - RED Operation
Service
Table of contents
Other schmalenberger Lighting Equipment manuals