Operating instructions
Safety-monitoring module SRB 301LC/B
EN
1.7 Exclusion of liability
We shall accept no liability for damages and malfunctions resulting from
defective mounting or failure to comply with this operating instructions
manual. The manufacturer shall accept no liability for damages resulting
from the use of unauthorised spare parts or accessories.
For safety reasons, invasive work on the device as well as arbitrary re-
pairs, conversions and modications to the device are strictly forbidden;
the manufacturer shall accept no liability for damages resulting from
such invasive work, arbitrary repairs, conversions and/or modications
to the device.
2 Product description
2.1 Ordering code
This operating instructions manual applies to the following types:
SRB 301LC/B
Only if the information described in this operating instructions
manual are realised correctly, the safety function and therefore
the compliance with the Machinery Directive is maintained.
2.2 Special versions
For special versions, which are not listed in the order code below 2.1,
these specications apply accordingly, provided that they correspond to
the standard version.
2.3 Destination and use
The safety-monitoring modules for integration in safety circuits are
designed for tting in control cabinets. They are used for the safe
evaluation of the signals of positive break position switches or magnetic
safety sensors for safety functions on sliding, hinged and removable
safety guards as well as emergency stop control devices and AOPD's.
The safety function is dened as the opening of enabling contacts
13-14, 23-24 and 33-34 when the inputs S11-S12 and/or S11-S22 are
opened. The safety-relevant current paths with output contacts 13-14,
23-24 and 33-34 meet the following requirements under observation
of a B10d value assessment (also refer to “Requirements of
DIN EN ISO 13 849-1“):
– Control category 4 – PL e to DIN EN ISO 13849-1
– SIL 3 to DIN EN 61508-2
– SILCL 3 to DIN EN 62061
(meets the requirements of control category 4 to DIN EN 954-1)
To determine the Performance Level (PL) of the entire safety function
(e.g. sensor, logic, actuator) to DIN EN ISO 13 849-1, an analysis of all
relevant components is required.
2.4 Technical data
General data:
Standards: IEC/EN 60204-1, EN 60947-5-1;
EN ISO 13849-1, IEC/EN 61508
Climate resistance: EN 60068-2-78
Fixation: Snaps onto standard DIN rails to
DIN EN 60715
Terminal designations: EN 60947-1
Material of the enclosure: glass-bre reinforced thermoplastic,
ventilated
Material of the contacts: AgSnO, self-cleaning,
positive drive
Weight: 230 g
Start conditions Automatic or start button
Feedback circuit (Y/N): Yes
ON delay with automatic start: approx. 300 ms
ON delay with reset button: approx. 20 ms
Drop-out delay in case
of emergency stop:
approx. 25 ms
Mechanical data:
Connection type: Screw connection
Min. cable section: 0.25 mm²
Max. cable section: 2.5 mm²
Connecting cable: rigid or exible
Tightening torque for
the terminals:
0.6 Nm
With removable terminals (Y/N): No
Mechanical life: 10 million operations
Electrical life: Derating curve available on request
Resistance to shock: 10 g / 11 ms
Resistance to vibrations
to EN 60068-2-6:
10 ... 55 Hz, amplitude 0.35 mm
Ambient conditions:
Ambient temperature: –25°C … +45°C
Storage and transport
temperature:
–40°C … +85°C
Protection class: Enclosure: IP 40
Terminals: IP 20
Wiring compartment: IP 54
Air clearances and creepage
distances to IEC/EN 60664-1:
4 kV/2 (basic insulation)
EMC rating: conforming to EMC Directive
Electrical data:
Contact resistance in new state: max. 100 mΩ
Power consumption: max. 1.7 W / 1.9 VA
Rated operating voltage Ue: 24 VDC –15%/+20%,
residual ripple max. 10%
24 VAC –15% / +10%
Frequency range: 50 Hz / 60 Hz
Max. fuse rating of the
operating voltage:
internal t 0.5 A (5 x 20 mm)
Monitored inputs:
Short-circuit recognition (Y/N): No
Wire breakage detection (Y/N): Yes
Earth leakage detection (Y/N): Yes
Number of NO contacts: 0
Number of NC contacts: 2
Cable lengths: 1-channel without cross-wire
short detection:
– 1,500 m = 1.5 mm²
– 2,500 m = 2.5 mm²
2-channel without cross-wire
short detection
Conduction resistance: max. 40 Ω
Outputs:
Number of safety contacts: 3
Number of auxiliary contacts: 1
Number of signalling outputs: 0
Switching capacity of the
safety contacts:
13-14; 23-24; 33-34:
max. 250 V, 6 A ohmic (inductive
in case of protective wiring);
min. 10 V / 10 mA
Switching capacity of the
auxiliary contacts:
41-42: 24 VDC / 2 A
Fuse rating of the safety
contacts:
6 A slow blow
Recommended fuse for
the auxiliary contacts:
2 A slow blow
Utilisation category to
EN 60947-5-1:
AC-15 / DC-13: EN 60947-5-1:2007
Dimensions (H/W/D): 100 mm x 22.5 mm x 121 mm
The data specied in this manual are applicable when the component
is operated with rated operating voltage Ue±0%.