Schweitzer Engineering Laboratories SEL-2245-4 User manual

Schweitzer Engineering Laboratories, Inc. SEL-2245-4 Data Sheet
The SEL-2245-4 provides ac metering inputs for the SEL Axion®. Within an Axion node, install as many as sixteen
SEL-2245-4 modules per system in any combination you want.
Front Panel
Figure 1 SEL-2245-4 AC Metering Module
Mechanical Installation
Each SEL-2242 chassis/backplane has four or ten slots,
labeled A–J. Slots B–Jsupport the SEL-2245-4 modules.
Figure 2 Notch for Module Alignment
To install an SEL-2245-4 module, tip the top of the
module away from the chassis, align the notch on the
bottom of the module (shown in Figure 2) with the slot
you want on the chassis, and place the module on the
bottom lip of the chassis as Figure 3 illustrates. The
module is aligned properly when it rests entirely on the
lip of the chassis.
i6316a
SEL-2245-4 AC Metering Module

SEL-2245-4 Data Sheet Schweitzer Engineering Laboratories, Inc.
2
Figure 3 Proper Module Placement
Next, carefully rotate the module into the chassis,
making sure that the alignment tab fits into the
corresponding slot at the top of the chassis (refer to
Figure 4). Finally, press the module firmly into the
chassis and tighten the chassis retaining screw.
Figure 4 Final Module Alignment
Input Connections
The SEL-2245-4 CT/PT analog inputs include a dot next
to the terminal number to indicate the positive
convention. Refer to Specifications for ac analog input
ratings and to Figure 5 for terminal assignments. You can
configure potential transformer (PT) inputs for 5–400 V
and current transformer (CT) inputs for 0–22 A.
Configure inputs by adding a Fieldbus I/O connection for
each module in ACSELERATOR RTAC®SEL-5033
Software. See the EtherCAT®portion in Section 2:
Communications in the SEL-5033 Software Instruction
Manual for details.
Figure 5 CT/PT Analog Inputs
LED Indicators
The LEDs labeled ENABLED and ALARM are related to
EtherCAT network operation. The green ENABLED LED
illuminates when the module is operating normally on
the network. The ALARM LED illuminates during network
initialization or when there is a problem with the
network.
CAUTION
Use supply wires suitable for 60°C (140°F) above ambient. See product
or manual for ratings.
ATTENTION
Utilisez des fils d'alimentation appropriés pour 60°C (140°F) au-dessus
ambiante. Voir le produit ou le manuel pour les valeurs nominales.
i6316a

Schweitzer Engineering Laboratories, Inc. SEL-2245-4 Data Sheet
3
Specifications
Compliance
Designed and manufactured under an ISO 9001 certified quality
management system
UL Listed to U.S. and Canadian safety standards (File E220228;
NRAQ, NRAQ7)
CE Mark
General
Operating Temperature Range:
–40° to +85°C (–40° to +185°F)
Operating Environment
Pollution Degree: 2
Overvoltage Category: II
Insulation Class: 1
Relative Humidity: 5%–95%, noncondensing
Maximum Altitude: 2000 m
AC Metering Inputs (SEL-2245-4)
Frequency: 50/60 Hz
Range: 45–65 Hz
Typical Accuracy: ±0.005 Hz above 20 V
Worst-Case Accuracy: ±0.01 Hz above 20 V
Phase Rotation: ABC, ACB
Input Configuration: 3-Wire Delta, 4-Wire Wye
Update Interval
Fundamental Metering: 200 Hz
RMS Metering: 5 Hz
Current Inputs Phase and Neutral
INOM: 1 A or 5 A (no settings required)
Measurement Range: 0.050–22 A Continuous
22–100 A Symmetrical for 25 s
Thermal Withstand Limit: 500 A for 1 s
Typical Accuracy: ±0.1% Fundamental@ fNOM and > 0.6 A
±0.1% RMS@ fNOM and > 0.6 A
Worst-Case Accuracy: ±2% ± 0.005 A Fundamental
±1% ± 0.005 A RMS
Angle
Range: ±180°
Typical Accuracy: ±0.1° Fundamental @ fNOM and > 0.6 A
Worst-Case Accuracy: ± 2° @ fNOM
Burden: < 0.1 VA @ INOM
Voltage Inputs
VNOM: 300 V
Measurement Range: 5–400 L-N, 9–693 L-L Vac
Fundamental/RMS
5–300 L-N, 9–520 L-L Vac
Fundamental/RMS (UL)
Maximum: 600 L-N, 1039 L-L Vac Fundamental/RMS
for 10 s
Typical Accuracy: ±0.1% Fundamental@ fNOM and > 20 V
±0.1% RMS@ fNOM
Worst-Case Accuracy: ±2% Fundamental@ fNOM
±1% RMS ±0.05 V
Angle
Range: ±180°
Typical Accuracy: ±0.1° @ fNOM and > 20 V
Worst-Case Accuracy: ±2° @ fNOM
Burden: < 0.1 VA
Sequence Components
Values: I0, I1, I2, V0, V1, V2
Typical Accuracy
Magnitude: ±0.2% @ fNOM
Angle: ±0.2° @ fNOM and V > 6.7 V, I > 0.6 A
Worst-Case Accuracy
Magnitude: ±3% @ fNOM and V > 6.7 V, I > 0.6 A
Angle: ±0.2° @ fNOM and V > 6.7 V, I > 0.6A
Power and Power Factor (Per Phase and Three-Phase)
PA, PB, PC, 3P
Typical Accuracy: 0.1% @ PF > 0.1
Worst-Case Accuracy: 2%
QA, QB, QC, 3Q
Typical Accuracy: 0.1% @ PF < 0.9
Worst-Case Accuracy: 2%
SA, SB, SC, 3S
Typical Accuracy: 0.1%
Worst-Case Accuracy: 2%
PFA, PFB, PFC, 3PF
Typical Accuracy: 0.1% @ PF > 0.1
Worst-Case Accuracy: 2%
Synchrophasor
Conformance: IEEE C37.118.1-2011 as amended by
IEEE C37.118.1a-2014
IEEE C37.118.2-2011
Accuracy: Level 1 as specified by IEEE C37.118
Measurements: Software selectable (P or M class)
Voltage: VA, VB, VC, VS
Current: IA, IB, IC, IN
Positive-Sequence: V1, I1
Periodic: Frequency and df/dt
Processing Rate: 120 Hz
Triggered Waveform Recording
Sampling Rates: 1, 2, 4, 8, 24 kHz software selectable
Record Duration: 0.1 second increments from 0.5 s to
specified maximum for each sample rate.
Maximum Record
Duration:
6 s at 24 kHz
18 s at 8 kHz
36 s at 4 kHz
72 s at 2 kHz
144 s at 1 kHz

4
© 2013–2018 by Schweitzer Engineering Laboratories, Inc. All rights reserved.
All brand or product names appearing in this document are the trademark or registered
trademark of their respective holders. No SEL trademarks may be used without written
permission. SEL products appearing in this document may be covered by U.S. and Foreign
patents.
Schweitzer Engineering Laboratories, Inc. reserves all rights and benefits afforded under
federal and international copyright and patent laws in its products, including without lim-
itation software, firmware, and documentation.
The information in this document is provided for informational use only and is subject to
change without notice. Schweitzer Engineering Laboratories, Inc. has approved only the
English language document.
This product is covered by the standard SEL 10-year warranty. For warranty details, visit
selinc.com or contact your customer service representative. *PDS2245-04*
2350 NE Hopkins Court • Pullman, WA 99163-5603 U.S.A.
Tel: +1.509.332.1890 • Fax: +1.509.332.7990
SEL-2245-4 Data Sheet Date Code 20180629
Record Pretrigger: 0.05 s minimum to a maximum of
(record length –0.05) s
Waveform File Format: COMTRADE (IEEE C37.111-1999
compliant)
Type Tests
Environmental Tests
Enclosure Protection: IEC 60529:2001 + CRGD:2003
IP3X excluding the terminal blocks
Vibration Resistance: IEC 60255-21-1:1988
Vibration Endurance, Severity: Class 2
Vibration Response, Severity: Class 2
Shock Resistance: IEC 60255-21-2:1988
Bump Test, Severity: Class 1
Shock Withstand, Severity: Class 1
Shock Response, Severity: Class 2
Seismic: IEC 60255-21-3:1993
Quake Response, Severity: Class 2
Cold: IEC 60068-2-1:2007
–40°C, 16 hours
Dry Heat: IEC 60068-2-2:2007
+85°C, 16 hours
Damp Heat, Cyclic: IEC 60068-2-30:2005
25°C to 55°C, 6 cycles,
95% relative humidity
Dielectric Strength and Impulse Tests
Impulse: IIEC 60255-5:2000
IEEE C37.90-2005
Severity Level:
0.5 Joule, 5 kV CT/PT inputs
Dielectric (HiPot): IEC 60255-5:2000
IEEE C37.90-2005
Severity Level:
2500 Vac CT/PT inputs for 1 minute
RFI and Interference Tests
EMC Immunity
Electrostatic Discharge
Immunity:
IEEE C37.90.3-2001
IEC 60255-22-2:2008
IEC 61000-4-2:2008
Severity Level: 8 kV contact discharge
15 kV air discharge
Radiated RF Immunity: IEEE C37.90.2-2004
Severity Level: 35 V/m
IEC 61000-4-3:2008
IEC 60255-22-3:2007
Severity Level: 10 V/m
Digital Radio Telephone
RF Immunity:
ENV 50204:1995
Severity Level:
10 V/m at 900 MHz and 1.89 GHz
Conducted RF Immunity: IEC 60255-22-6:2001
IEC 61000-4-6:2008
Severity Level: 10 Vrms
Surge Immunity: IEC 60255-22-5:2008
IEC 61000-4-5:2005
Severity Level: 1 kV Line to Line,
2 kV Line to Earth
(202 ms filter on RMS voltages and
frequencies, 33 ms filter on fundamental
frequencies)
Fast Transient, Burst
Immunity:
IEC 60255-22-4:2008
IEC 61000-4-4:2011
Severity Level: Class A: 4 kV, 5 kHz;
2 kV, 5 kHz on communications ports
Magnetic Field
Immunity:
IEC 61000-4-8:2009
Severity Level: 1000 A/m for 3 seconds,
100 A/m for 1 minute
IEC 61000-4-9:2001
Severity Level: 1000 A/m
IEC 61000-4-10:2001
Severity Level: 100 A/m
Surge Withstand
Capability Immunity:
IEC 60255-22-1:2007
Severity Level: 2.5 kV common-mode
1.0 kV differential-mode
IEEE C37.90.1-2002
Severity Level: 2.5 kV Oscillatory
4.0 kV Fast Transient
Oscillatory Waves
Immunity:
IEC 61000-4-12:2006
Severity Level: Ring Wave: 2 kV
common, 1.0 kV differential
Oscillatory: 2.5 kV common,
1.0 kV differential
Common Mode
Disturbance Immunity:
IEC 61000-4-16:2002
Frequency: 0 Hz to 150 Hz
Severity Level: Level 4, Segment 4:
30 Vrms open-circuit, 15 kHz–150 kHz
Emissions
Radiated and Conducted
Emissions:
IEC 60255-25:2000
Severity Level: Class A