Tamas Low Loss Header Series User manual

4516 112 Ave S.E. Calgary, Alberta • Tel: (403) 279 0020 • Fax: (403) 279 0747
www.tamashydronic.com
Tamas Hydronic Panels
User Guide
Low Loss Header Series
Installaon and Commissioning Guide
Version 1.0

4516 112 Ave S.E. Calgary, Alberta • Tel: (403) 279 0020 • Fax: (403) 279 0747
www.tamashydronic.com Page 2
Tamas Hydronic Panels
Low Loss Header Series
Table of Contents
Introduction................................................................................................................................ 4
Components................................................................................................................................5-7
Operation.................................................................................................................................... 8
Technical Data............................................................................................................................ 9-12
Wiring...........................................................................................................................................13
Commissioning........................................................................................................................... 14
Warranty......................................................................................................................................15
This User Guide is Applicable to:
Table of Contents
Low Loss Header Boiler Panels (DHW Priority)
T-LL-BD-1100 Low Loss Header Panel with UPS 15-58 Pumps, (1) Boiler Pump and (1) DHW Zone with Priority
T-LL-BD-1110 Low Loss Header Panel with UPS 15-58 Pumps, (1) Boiler Pump, (1) High Temp Zone and (1) Low Temp Zone
T-LL-BD-2100 Low Loss Header Panel with (1) 26-99 Boiler Pump and (1) DHW Zone
T-LL-BD-2100 26-99 Low Loss Header Panel with (1) 26-99 Boiler Pump and (1) 26-99 DHW Zone
T-LL-BD-2110 Low Loss Header Panel with (1) 26-99 Boiler Pump, (1) DHW Zone with Priority and (1) Low Temp Zone
T-LL-BD-2200 Low Loss Header Panel with (1) 26-99 Boiler Pump and (1) DHW Zone
Low Loss Header Boiler Panels (DHW Priority)
T-LL-BO-1010 Low Loss Header Panel with UPS 15-58 Pumps, (1) Boiler Pump and (1) Low Temp Zone
T-LL-BO-1020 Low Loss Header Panel with UPS 15-58 Pumps, (1) Boiler Pump and (2) Low Temp Zones
T-LL-BO-1100 Low Loss Header Panel with UPS 15-58 Pumps, (1) Boiler Pump and (1) High Temp Zone
T-LL-BO-1200 Low Loss Header Panel with UPS 15-58 Pumps, (1) Boiler Pump and (2) High Temp Zone
T-LL-BO-1300 Low Loss Header Panel with UPS 15-58 Pumps, (1) Boiler Pump and (3) High Temp Zone
T-LL-BO-1110 Low Loss Header Panel with UPS 15-58 Pumps, (1) Boiler Pump, (1) High Temp Zone and (1) Low Temp Zone (1) TMV
T-LL-BO-2010 Low Loss Header Panel with (1) 26-99 Boiler Pump and (1) Low Temp Zone
T-LL-BO-2020 Low Loss Header Panel with (1) 26-99 Boiler Pump and (2) Low Temp Zones
Low Loss Header Panels
T-LL-0D-0100 Low Loss Header Panel with (1) DHW Zone
T-LL-0D-0110 Low Loss Header Panel with (1) High Temp Zone and (1) Low Temp Zone
T-LL-0D-0120 Low Loss Header Panel with (1) TMV, (1) DHW Zone with Priority and (2) Low Temp Zones
T-LL-0D-0130 Low Loss Header Panel with (1) DHW Zone with Priority and (3) Low Temp Zones
T-LL-0D-0200 Low Loss Header Panel with (1) DHW Zone with Priority and (1) High Temp Zones
T-LL-0D-0210 Low Loss Header Panel with (1) TMV, (1) DHW Zone with Priority, (1) Hi Temp Zone and (1) Low Temp Zone
T-LL-00-0110 Low Loss Header Panel with (1) High Temp Zone and (1) Low Temp Zone
T-LL-00-0120 Low Loss Header Panel with (1) High Temp Zone and (2) Low Temp Zones
T-LL-00-0210 Low Loss Header Panel with (2) High Temp Zones and (1) Low Temp Zone
T-LL-00-0100 Low Loss Header Panel with (1) High Temp Zone
T-LL-00-0200 Low Loss Header Panel with (2) High Temp Zones
T-LL-00-0300 Low Loss Header Panel with (3) High Temp Zones
T-LL-00-0400 Low Loss Header Panel with (4) High Temp Zones

4516 112 Ave S.E. Calgary, Alberta • Tel: (403) 279 0020 • Fax: (403) 279 0747
www.tamashydronic.com Page 3
Tamas Hydronic Panels
Low Loss Header Series
Low Loss Header Panels with an Expansion Module
T-LL-EX-0100 Low Loss Header with an Expansion Module and (1) Hi Temp Zone
T-LL-EX-0200 Low Loss Header with an Expansion Module and (2) Hi Temp Zones
T-LL-EX-0300 Low Loss Header with an Expansion Module and (3) Hi Temp Zones
T-LL-EX-0400 Low Loss Header with an Expansion Module and (4) Hi Temp Zones
T-LL-EX-0010 Low Loss Header with an Expansion Module and (1) Low Temp Zone
T-LL-EX-0020 Low Loss Header with an Expansion Module and (2) Low Temp Zones
T-LL-EX-0030 Low Loss Header with an Expansion Module and (3) Low Temp Zones
T-LL-EX-0040 Low Loss Header with an Expansion Module and (4) Low Temp Zones
T-LL-EX-0110 Low Loss Header with an Expansion Module, (1) High Temp Zone and (1) Low Temp Zone
T-LL-EX-0120 Low Loss Header with an Expansion Module, (1) High Temp Zone and (2) Low Temp Zones
T-LL-EX-0130 Low Loss Header with an Expansion Module, (1) High Temp Zone and (3) Low Temp Zones
T-LL-EX-0210 Low Loss Header with an Expansion Module, (2) High Temp Zones and (1) Low Temp Zone
T-LL-EX-0220 Low Loss Header with an Expansion Module, (2) High Temp Zones and (2) Low Temp Zones
T-LL-EX-0310 Low Loss Header with an Expansion Module, (3) High Temp Zones and (1) Low Temp Zone
* Note:
The following parts lists and applicaon drawings are general samplings. Each panel conguraon dictates the required components, including
pump type. See the Technical Data secon of the manual for specic informaon on each part in your parcular variaon of the Tamas Low Loss
Header Panel.
Table of Contents

4516 112 Ave S.E. Calgary, Alberta • Tel: (403) 279 0020 • Fax: (403) 279 0747
www.tamashydronic.com Page 4
Tamas Hydronic Panels
Low Loss Header Series
Overview, Options and Dimensions
Description
When used in conjuncon with boilers, the low-loss header
acts as hydraulic break, decoupling boiler and system
circuits from each other. The low-loss header increases
operaonal eciency. In addion, the low-loss header
helps eliminate debris from the heang system. The low
loss header panel is congured with expansion ports
designed to accept input signals from future auxiliary
panel. The panel is designed to hydronically isolate the
primary boiler loop from the secondary zone loop.
Oponal secondary injecon mixing components, as well
as low and high temperature zones can be added to the
system. This enables the panel to accommodate DHW
priority or fan coil applicaons. The panel can support a
maximum of 5 pumps, including the DHW priority pump.
Installation
Prior to mounng the panel, ensure the wall is capable of
supporng the weight of the panel. Ensure that an 115V
receptacle is within reach of the 5-foot cord and plug.
Main Features
• Pre-designed and assembled
• Funcon & pressure tested
• Packaged, compact design
• Cered to CSA C22.2 No. 14-95
• Conforms to UL Standard 598A
Technical Data
• Flow Range: 0-17 US GPM
• Head Range: 0-19 Feet
• Motors: 2 Pole, Single Phase
• Max. Operang Temperature: 93°C/200°F
• Max. Ambient Temperature: 49°C/120°F
• Max. Operang Pressure: 10 Bar/145 PSI
Low Loss Header Panel
T-LL-00-1400 Model Shown
Low Loss Header Expansion Panel
T-LL-EX-0120 Model Shown
Low Loss Header Boiler Panel
T-LL-BD-2110 Model Shown
Introduction

4516 112 Ave S.E. Calgary, Alberta • Tel: (403) 279 0020 • Fax: (403) 279 0747
www.tamashydronic.com Page 5
Tamas Hydronic Panels
Low Loss Header Series
Components
122” x 26” Galvanized Backpan
2Tamas Control Box with 5’ Power Cable
3Zone Pumps UPS 15-58
424V AC Transformer with Internal Fuse
5Temperature Gauge
6Tamas Ball Valves
7Stainless Steel Low Loss Header
8Hose Bib Hook-Up
9Manual Air Vent
Components
1
1
1
1
1
1
2
2
2
2
2
2
3
3
3
3
3
3
6
6
7
7
6
6
7
7
6
6
7
7
8
8
8
8
9
9
9
9
10
10
4
4
4
4
4
4
5
5
5
5
5
5
21.5”
27”
21.5”
27”
21.5”
27”
Low Loss Header Panel Components
12”

4516 112 Ave S.E. Calgary, Alberta • Tel: (403) 279 0020 • Fax: (403) 279 0747
www.tamashydronic.com Page 6
Tamas Hydronic Panels
Low Loss Header Series
Components
122” x 26” Galvanized Backpan
2Tamas Control Box with 5’ Power Cable
3Zone Pumps UPS 15-58
424V AC Transformer with Internal Fuse
5Temperature Gauge
6Tamas Ball Valves
7Thermostac Mixing Valve
Components
1
1
1
1
1
1
2
2
2
2
2
2
3
3
3
3
3
3
6
6
7
7
6
6
7
7
6
6
7
7
8
8
8
8
9
9
9
9
10
10
4
4
4
4
4
4
5
5
5
5
5
5
21.5”
27”
21.5”
27”
21.5”
27”
Low Loss Header Expansion Panel Components
12”

4516 112 Ave S.E. Calgary, Alberta • Tel: (403) 279 0020 • Fax: (403) 279 0747
www.tamashydronic.com Page 7
Tamas Hydronic Panels
Low Loss Header Series
Components
122” x 26” Galvanized Backpan
2Tamas Control Box with 5’ Power Cable
3Zone Pumps UPS 15-58
424V AC Transformer with Internal Fuse
5Temperature Gauge
6Tamas Ball Valves
7Stainless Steel Low Loss Header
8Hose Bib Hook-Up
9Air Vent
10 Boiler Pump UPS15-58 / UPS 26-99
Components
1
1
1
1
1
1
2
2
2
2
2
2
3
3
3
3
3
3
6
6
7
7
6
6
7
7
6
6
7
7
8
8
8
8
9
9
9
9
10
10
4
4
4
4
4
4
5
5
5
5
5
5
21.5”
27”
21.5”
27”
21.5”
27”
Low Loss Header Boiler Panel Components
12”

4516 112 Ave S.E. Calgary, Alberta • Tel: (403) 279 0020 • Fax: (403) 279 0747
www.tamashydronic.com Page 8
Tamas Hydronic Panels
Low Loss Header Series
Boiler
T-LL-BD-1400
Expansion Connecons
DHW Tank
Fan Coil
Radiant Zone
T-LL-EX-1120
T-LL-BD-1210
Boiler
Fan Coil
Radiant Zone
DHW Tank
Operation
Operaon of the Primary
When a Low Loss Header Panel is connected to a boiler system, the panel regulates the water distribuon quanty to
accommodate demand. If the room or oor temperature falls below the user’s designated seng on a thermostat, for
example (sold separately), the panel iniates a signal which has the control start the boiler pump and zone pumps. When
the room temperature is sased, the thermostat or aquastat disconnects the heat source and pump.
3 Temp Low Loss Header Panel Applicaon
3 Temp Low Loss Header Panel with Expansion Panel Applicaon
Operation
Operaon of the Domesc Hot Water (DHW)
When there is a Domesc Hot Water applicaon, and an
aquastat demand is signaled, the panel disconnects the
acve zone pumps and sends a message to the boiler to
raise the internal boiler water temperature. This water
is heated and distributed as domesc hot water, when
the domesc hot water demand is sased; the system
disconnects the high temperature output and reverts to
the preset zone temperatures that were previously acve.
This method of providing precedence to the domesc hot
water requirements before the space heang load of a
building is known as domesc hot water priority.

4516 112 Ave S.E. Calgary, Alberta • Tel: (403) 279 0020 • Fax: (403) 279 0747
www.tamashydronic.com Page 9
Tamas Hydronic Panels
Low Loss Header Series
Technical Data
Performance
UPS 15-58 3 Speed Pump
230
o
F
slavorppA
)metsysdesolc(pmetdiulfxaM
150
o
F
LTE
)metsysnepo(pmetdiulfxaM
36
o
FMin fluid temp
NSF Std 61
10 Bar Max system pressure
Annex G
HI
MED
LOW
HI
MED
LOW
20
18
16
14
12
10
8
6
4
2
0
80
70
60
50
40
30
20
0
0 2 4 6 8 10 12
2 4 6
GPM
Ft
GPM
Was
8 10 12
UPS 15-58 Three Speed Pump

4516 112 Ave S.E. Calgary, Alberta • Tel: (403) 279 0020 • Fax: (403) 279 0747
www.tamashydronic.com Page 10
Tamas Hydronic Panels
Low Loss Header Series
Technical Data
UPS 26-99 Pump
UPS 26-99FC/BFC SUPERBRUTE
Flow range: 0 - 34 U.S. GPM
Head range: 0 - 30 FEET
esahPelgniS,eloP2:srotoM
Maximum fluid temperature: 230°F (110°C)
Min. fluid temperature: 36°F (2°C)
Maximum working pressure: 145 PSI
0
5
10
15
20
25
30
0 5 10 15 20 25 30 35
Flow (GPM)
Head (ft.)
HI
MED
LOW
Without Check Valve
With Check Valve
MODEL VOLTS AMPS WATTS HP CAPACITOR
Spd. 3 1.8 197 1/6 20mF/180V
Spd. 2 1.5 179 1/6 20mF/180V
Spd. 1 1.3 150 1/6 20mF/180V
Spd. 3 0.9 196 1/6 5mF/400V
Spd. 2 0.8 179 1/6 5mF/400V
Spd. 1 0.7 150 1/6 5mF/400V
115V
230V
Model Type A B C D E F Connection Type and Size
Approximate
Shipping Wt.
(lbs)
UPS26-99FC/BFC 6 1/264 7/8 3 1/2 3 7/16 3 5/32 GF 15/26 Flange - (2) 1/2" Dia. Bolt Holes 10.3
A
B
C
DF
E

4516 112 Ave S.E. Calgary, Alberta • Tel: (403) 279 0020 • Fax: (403) 279 0747
www.tamashydronic.com Page 11
Tamas Hydronic Panels
Low Loss Header Series
Technical Data
Thermostatic mixing valve (ASSE-1017 listed*)
• An-scald funcon.
• Snap-on cover for protecon and to prevent unauthorized adjustment or
tampering.
• Cover label for recording sengs including recorded outlet temperature and
date installed.
• Available temperature ranges:
o 70°F – 110°F (20°C - 45°C)* o 85°F – 120°F (29°C - 49°C)*
o 95°F – 140°F (35°C - 60°C)* o 85°F – 160°F (30°C - 70°C)*(¾” only)
• Available connecons
o Threaded body (FPT). o Union solder.
o Union solder w/ 1 check valve. o Union solder c/w 2 check valves.
o Union CPVC. o Compression (¾” only).
• Maximum working pressure:150 psi (10 bar)**.
• Maximum system dierenal pressure between hot and cold: 44 psi (3 bar).
• Maximum system dierenal pressure: 72 psi (5 bar).
• Maximum hot water inlet temperature: 194°F (90°C).
• Minimum required ow***: 0.5 US gpm.
The thermostac mixing valve will provide a mixed water temperature according to the table below. The
outlet temperatures stated are approximate, based on given hot water supply temperature and a cold
water supply of 50°F (10°C). For other cold water temperatures correct the outlet temperature by 1°F for
every 10°F (or 1°C for every 10°C) deviaon from 50°F (10°C), up or down.
* Only ranges 85-120°F and 95-140°F are listed to ASSE-1017 standard
**Max. working pressure for CPVC: 80 psi (5.5 bar)
***For Correct temperature control
2
0
0204
06
0
4
6
8
10
12
14
16
Flow (USgpm)
Pressure Drop (psi)
All 1/2" & 3/4" Compression 3/4" FPT & Union Body
D
C
B
A
A
B
C
D
CAD GENERATED DRAWING,
DO NOT MANUALLY UPDATE
SCALE
SIZE
DWG. NO.
B
SHEET
1
OF
1
REV.
ESB 1 G with seal and nut 2
DATE
APPROVALS
DRAWN
CHECKED
APR
UNLESS OTHERWISE SPECIFIED
DIMENSIONS ARE IN INCHES
MATERIAL
DO NOT SCALE DRAWING
1
2
3
4
5
6
7
8
8
7
6
5
4
3
2
1
REVISIONS
REV.
DESCRIPTION
DATE
APPROVED
TH
PROPRIETARY INFORMATION:
THE INFORMATION CONTAINED IN THIS DOCUMENT IS THE PPOPERTY OF TAMAS HYDRONIC SYSTEMS INC. EXCEPT AS
SPECIFICALLY AUTHORIZED IN WRITING TAMS HYDRONIC SYSTEMS INC. THE HOLDER OF THIS CDOCUMENT: (1) SHALL
KEEP ALL INFORMATION CONTAINED HEREIN CONFIDENTIAL AND SHALL PROTECT SAME IN WHOLE OR IN PART FROM
DISCLOSURE AND DISSEMINATION TO ALL THIRD PARTIES AND (2) SHALL USE SAME FOROPERATION AND MAINTENANCE
PURPOSES ONLY.
1:2
6/7/2013
4516 112 Ave S.E.
Calgary Alberta
T2C 2K2

4516 112 Ave S.E. Calgary, Alberta • Tel: (403) 279 0020 • Fax: (403) 279 0747
www.tamashydronic.com Page 12
Tamas Hydronic Panels
Low Loss Header Series
Technical Data
Tamas Low Loss Header
Delta T Max Flow Rate BTU Load
20 24.2GPM 242000
25 24.2GPM 280000
30 24.2GPM 365000
35 24.2GPM 420000
40 24.2GPM 475000
Dimensions
514
460
56
300
25
84
1" NPT thread
1/2 " NPT thread
Top
Bottom

4516 112 Ave S.E. Calgary, Alberta • Tel: (403) 279 0020 • Fax: (403) 279 0747
www.tamashydronic.com Page 13
Tamas Hydronic Panels
Low Loss Header Series
Thermostat Connections
Connect the thermostat for a space heang zone to the terminal block on the Tamas Panel. Do not supply 24V power to
the thermostat circuits or aempt to supply 24V AC for any other applicaon.
For the thermostats that require connuous 24V AC power source, connect the thermostat power input to the 24V AC
terminal on the Tamas Panel.
T-LO-TP-0010
Field Connections
Notes:
This is not an
engineered drawing
and does not
necessarily include
all the components
for an entire system.
It is intended as a
representative
sample of how the
control may be wired
for a sample
application. It is the
responsibilityof the
installer to seek
professional advice
and/or install the the
system to meet all
necessary codes for
the jurisdiction of the
actual installation.
Title
Drawn:
Date:
T-LO-TP-0010
1 ZONE LOW
TEMP PANEL
Notes:
This is not an
engineered drawing
and does not
necessarily include
all the components
for an entire system.
It is intended as a
representative
sample of how the
control may be wired
for a sample
application. It is the
responsibility of the
installer to seek
professional advice
and/or install the the
system to meet all
necessary codes for
the jurisdiction of the
actual installation.
Title
Drawn:
Date:
Thermostat
24 V AC 30VA Max
3 Wire Thermostat
4 Wire Thermostat
TH
THERMOSTAT
Thermostat
24 V AC 30VA Max
TH
THERMOSTAT
TH
THERMOSTAT
24 V AC 30VA Max
Thermostat
2 Wire Thermostat
Thermostat Wiring Options
See reverse for
Thermostat Wiring Options
76.0°F
TARGET
ROOM
85°F
OFF
76.0°F
TARGET
ROOM
85°F
OFF
76.0°F
TARGET
ROOM
85°F
OFF
T-LO-TP-0010
Field Connections
Notes:
This is not an
engineered drawing
and does not
necessarily include
all the components
for an entire system.
It is intended as a
representative
sample of how the
control may be wired
for a sample
application. It is the
responsibilityof the
installer to seek
professional advice
and/or install the the
system to meet all
necessary codes for
the jurisdiction of the
actual installation.
Title
Drawn:
Date:
T-LO-TP-0010
1 ZONE LOW
TEMP PANEL
Notes:
This is not an
engineered drawing
and does not
necessarily include
all the components
for an entire system.
It is intended as a
representative
sample of how the
control may be wired
for a sample
application. It is the
responsibility of the
installer to seek
professional advice
and/or install the the
system to meet all
necessary codes for
the jurisdiction of the
actual installation.
Title
Drawn:
Date:
Thermostat
24 V AC 30VA Max
3 Wire Thermostat
4 Wire Thermostat
TH
THERMOSTAT
Thermostat
24 V AC 30VA Max
TH
THERMOSTAT
TH
THERMOSTAT
24 V AC 30VA Max
Thermostat
2 Wire Thermostat
Thermostat Wiring Options
See reverse for
Thermostat Wiring Options
76.0°F
TARGET
ROOM
85°F
OFF
76.0°F
TARGET
ROOM
85°F
OFF
76.0°F
TARGET
ROOM
85°F
OFF
T-LO-TP-0010
Field Connections
Notes:
This is not an
engineered drawing
and does not
necessarily include
all the components
for an entire system.
It is intended as a
representative
sample of how the
control may be wired
for a sample
application. It is the
responsibilityof the
installer to seek
professional advice
and/or install the the
system to meet all
necessary codes for
the jurisdiction of the
actual installation.
Title
Drawn:
Date:
T-LO-TP-0010
1 ZONE LOW
TEMP PANEL
Notes:
This is not an
engineered drawing
and does not
necessarily include
all the components
for an entire system.
It is intended as a
representative
sample of how the
control may be wired
for a sample
application. It is the
responsibility of the
installer to seek
professional advice
and/or install the the
system to meet all
necessary codes for
the jurisdiction of the
actual installation.
Title
Drawn:
Date:
Thermostat
24 V AC 30VA Max
3 Wire Thermostat
4 Wire Thermostat
TH
THERMOSTAT
Thermostat
24 V AC 30VA Max
TH
THERMOSTAT
TH
THERMOSTAT
24 V AC 30VA Max
Thermostat
2 Wire Thermostat
Thermostat Wiring Options
See reverse for
Thermostat Wiring Options
76.0°F
TARGET
ROOM
85°F
OFF
76.0°F
TARGET
ROOM
85°F
OFF
76.0°F
TARGET
ROOM
85°F
OFF
4 Wire Thermostat3 Wire Thermostat2 Wire Thermostat
Wiring
Wiring
All electrical wiring to the panel (including grounding) must conform to local electrical codes and/or Naonal Electrical
Code, ANS/NFPA No. 70-latest edion, or the Canadian Electrical Code, C22.1- Part 1.
Connections Boiler Panel – Boiler
Field Wiring for T-LL-OO-0200
TH-1
Boiler
LOW Temperature Zones 1-2
TH TH
TH-2
Thermostat 2
Thermostat 1
W
R
W
R
C
R
Boiler Demand
24 V AC 30VA Max
Notes:
This is not an
engineered drawing
and does not
necessarily include
all the components
for an entire system.
It is intended as a
representative
sample of how the
control may be wired
for a sample
application. It is the
responsibility of the
installer to seek
professional advice
and/or install the the
system to meet all
necessary codes for
the jurisdiction of the
actual installation.
Title
Drawn:
Date:
See reverse for Thermostat Wiring Options
NOTE: a panel specic wiring diagram
is included with each panel.

4516 112 Ave S.E. Calgary, Alberta • Tel: (403) 279 0020 • Fax: (403) 279 0747
www.tamashydronic.com Page 14
Tamas Hydronic Panels
Low Loss Header Series
Commissioning
System Filling Procedure
1. Disconnect power from the Tamas Hydronic panel
2. Close all isolaon valves to the zones
3. Begin lling the panel through the provided hose bib connecon on the panel
4. Open the supply isolaon valve on the panel for the rst zone
5. Begin lling the system
6. Slowly open the Purging Valve (eld supplied) on the return side of the zone line to let the air out
of the system
7. Once the air has been eliminated from the zone, close the air purging valve
8. Finally close all the valves to isolate the zone from the panel before moving on to the next zone.
9. Repeat this procedure based on the amount of zones on the board
10. Once all the zones have been purged, you can open all the isolaon valves
*IMPORTANT* This procedure applies to filling the system one zone at a time.
Isolaon Valve
Hose Bib
Hook-Up

4516 112 Ave S.E. Calgary, Alberta • Tel: (403) 279 0020 • Fax: (403) 279 0747
www.tamashydronic.com Page 15
Tamas Hydronic Panels
Low Loss Header Series
Limited Warranty
Limited Warranty
Tamas Hydronic Systems Inc. warrants each of its products to be free from defects in workmanship and materials under normal use and service for a
period of 24 months from date of purchase from a Tamas Hydronic Systems inc. authorized Dealer.
If the product proves to be defecve within the applicable warranty period, Tamas Hydronic Systems inc. on its sole discreon will repair or
replace said product. Replacement product may be new or refurbished of equivalent or beer specicaons, relave to the defecve product.
Replacement product need not be of idencal design or model. Any repair or replacement product pursuant to this warranty shall be warranted for
not less than 90 days from date of such repair, irrespecve of any earlier expiraon of original warranty period. When Tamas Hydronic Systems Inc.
Provides replacement, the defecve product becomes the property of Tamas Hydronic Systems Inc.
Warranty Service, within the applicable warranty period, may be obtained by contacng your nearest Tamas Hydronics Systems inc. oce via the
original Authorized Agent and requesng a Return Material Authorizaon Number (RMA #). Proof of purchase in the form a dated invoice/receipt
must be provided to expedite the issuance of a Factory RMA.
Aer an RMA number has been issued, the defecve product must be packaged securely in the original or other suitable shipping package to ensure
that it will not be damaged in transit. The RMA number must be visible on the outside of the package and a copy included inside the package. The
package must be mailed or otherwise shipped back to Tamas Hydronic Systems Inc. with all costs of mailing/shipping/insurance prepaid by the
warranty claimant.
Any package/s returned to Tamas Hydronic Systems Inc. without an approved and visible RMA number will be rejected and shipped back to
purchaser at purchaser’s expense. Tamas Hydronic Systems Inc. Reserves the right, if deemed necessary, to charge a reasonable levy for costs
incurred, addional to mailing or shipping costs.
Limitation of Warranties.
If the Tamas Hydronic Systems Inc. product does not operate as warranted above the purchasers sole remedy shall be, at Tamas Hydronic Systems
Inc.’ s opon, repair or replacement. The foregoing warranes and remedies are exclusive and in lieu of all other warranes, expressed or implied,
either in fact or by operaon of law, statutory or otherwise, including warranes of merchantability and tness for a parcular purpose/applicaon.
Tamas Hydronic Systems Inc. neither assumes nor authorizes any other person to assume for it any other liability in connecon with the sale,
installaon maintenance or use of Tamas Hydronic Systems Inc. products.
Tamas Hydronic Systems Inc. shall not be liable under this warranty; if its tesng and examinaon discloses that the alleged defect in the product
does not exist or was caused by the purchasers or third persons misuse, neglect, improper installaon or tesng, unauthorized aempts to repair or
any other cause beyond the range of intended use, or by accident, re, lightning or other hazard.
Limitation of Liability.
In no event will Tamas Hydronic Systems Inc. be liable for any damages, including loss of data, loss of prots, costs of cover or other incidental,
consequenal or indirect damages arising out of the installaon, maintenance, commissioning, performance, failure or interrupon of a Tamas
Hydronic Systems Inc. product, however caused and on any theory of liability. This limitaon will apply even if Tamas Hydronic Systems Inc. has
been advised of the possibility of such damage.
Local Law.
This limited warranty statement gives the purchaser specic legal rights. The purchaser may also have other rights which vary from state to state in
the United States, from Province to Province in Canada and from Country to Country elsewhere in the world.
To the extent this Limited Warranty Statement is inconsistent with local law, this statement shall be deemed modied to be consistent with such
local law. Under such local law, certain disclaimers and limitaons of this statement may not apply to the purchaser. For example, some states in
the United States, as well as some governments outside the United States (including Canadian Provinces), may:
Preclude the disclaimers and limitaons in this statement from liming the statutory rights of a consumer (e.g. United Kingdom);
Otherwise restrict the ability of a manufacturer to enforce such disclaimers or limitaons; or
Grant the purchaser addional warranty rights which the manufacturer cannot disclaim, or not allow limitaons on the duraon of implied
warranes.
Warranty

Custom, Reliable Hydronic Systems
Tamas Hydronic Systems Inc. Phone: 1 (403) 279 0020
4516 112 Avenue SE Fax: 1 (403) 279 0747
Calgary, Alberta T2C 2K2 info@tamashydronic.com
/TamasHydronicSystems
/TamasHydronic