Smitec FLXMOD HMI D1 User manual

HMI D1
Process control unit with graphical interface
Datasheet
Description
Process control unit with graphical display and keypad. Main characteristics:
•Equipped with 32 bit Renesas RX62 processor with 96kbytes RAM and 512kbits Flash
inside
•64 kbit non-volatile RAM, 16 Mbit flash ROM and 128 Mbit SDRAM
•1 USB host port
•2 FLXIO / RS 485 ports
•4.3” LCD display with 24 bits color depth (16.7M colors)
•13 buttons keypad with 3 LED lamps
•customizable features on demand (keyboard layout, memories sizes, ethernet, RTC, SD
card reader, and more)
DK400150 rev. 0 ─ 18/04/2013 1/8
bottom side connectors
4.3” display
keyboard

Ordering information
Products SMITEC part number
HMI D1 module KZ010367
Accessories SMITEC part number
RTC CR2032 replacement battery TB010554
Documentation SMITEC part number
Datasheet for HMI D1 (english) DK400150
FLXMOD system integration manual (english) DK400076
DK400150 rev. 0 ─ 18/04/2013 2/8

Technical data
General data
Housing dimensions (width x height x depth) 210 mm x 170 mm x 34.3 mm
Weight 520 g (without connectors)
Permissible operating temperature +5° to +55°C
Permissible storage and transport temperature -25° to +85°C
Permissible humidity 10% to 95%, not condensing
Permissible air pressure (operation) 80 to 106 kPa (up to 2000 m above sea level)
Permissible air pressure (storage and transport) 70 to 106 kPa (up to 3000 m above sea level)
Degree of protection IP65 according to IEC 60529 (when flush mounted)
Connection method for power connector Spring cage terminals
Conductor cross-section for power connector 0.14 to 1.5 mm2 (26 ÷ 16 AWG)
Functional earth connection By fast-on terminal on rear-panel
Mode state visual indicators Two green LED lamps for FLXIO ports status
Power suppl
Main power supply Vm24 V DC (-15% ÷ + 20% according to IEC 61131-2)
Maximum allowed ripple 5% of supply voltage (according to IEC 61131-2)
Current consumption from main supply 0.5 A max.
Supply overvoltage protection Bidirectional Zener clamp (Vz > 30 V)
Supply reverse polarity protection Protection diode and safety fuse
Supply fuse 2 A time-delayed
CPU characteristics
Microcontroller type Renesas Technology type RX62
Microcontroller architecture Harvard 32 bit
Microcontroller RAM size 96 kbytes
Microcontroller FLASH size 512 kbytes
Board external RAM 128 Mbits SDRAM
Board external non-volatile RAM 64 kbits
Board external ROM 16 Mbits FLASH
Displa characteristics
Display type TFT LCD
Display size 4.3” (diagonal)
Color depth 24 bits (16.7M colors)
DK400150 rev. 0 ─ 18/04/2013 3/8

Communication ports
FLXIO ports 2 on RJ45 connectors, useable also as EIA RS-485
ports
FLXIO ports speed Up to 2.5 Mbps
USB host ports 1 on standard type A female connector
Other characteristics
USB host output current 250 mA max.
Acoustic peripherals 1 buzzer
DK400150 rev. 0 ─ 18/04/2013 4/8

Mechanical drawing
The image below depicts the mechanical dimensions of the device (base version shown):
DK400150 rev. 0 ─ 18/04/2013 5/8

Connections
The module has several connectors for power supply and peripherals, all located on the
bottom side of the module (see illustration below).
Warning: HMI D1 module is an electronic high technology device with numerous
connectors; for these reasons it results an ESD sensitive device. Observe ESD
mitigation techniques or damage might occur.
Power connector
The power connector is located on the bottom side of the module; the pinout is shown in the
illustration aside.
Warning: Use a cable with cross-
section suited to the current involved. A
wire smaller than necessary could cause
risk of fire and unwanted voltage drops.
Warning: To ensure conformance with
EMC directive 89/336/EEC, the length
of the cables must not exceed 30 m.
For EMC reasons, a secure connection to earth is
always required; a suitable fast-on terminal is provided for the purpose (labelled as FE in the
illustration).
DK400150 rev. 0 ─ 18/04/2013 /8
1 2
124V
2GND
FE

SD card connector
This device (depending on versions), is provided with a peripheral for interfacing SD cards.
These could be used for storing large data or for updating software.
A suitable connector is provided on the bottom side of the module, able to accommodate
standard SD cards.
USB device connector
This port (depending on versions), provided with a standard type mini B connector located on
the bottom side of the module, is useable as a communication port for connection with a
computer; the main purpose is data exchanging.
USB host connector
This port, provided with a standard type A connector located on the bottom side of the
module, is thought for connecting USB flash disks. Any different use should be avoided.
Warning: ever connect a device absorbing a current beyond the rating of the
device, or internal damage might occur.
FLXIO / RS485 connectors
The device can act as a dual-channel FLXIO master, and two RJ45 connectors are provided
for the purpose on the bottom side of the module. The
illustration aside shows the pinout of each connector;
use standard CAT 5E Ethernet cable to wire the buses.
Refer to the FLXMOD System Integration Manual for
bus wiring topology.
Depending on the configuration of the device, these two
ports could be used also as general purpose EIA RS485;
the maximum transmission speed is 2.5 Mbps. Even if
not mandatory, the
use of shielded
cable is highly recommended, particularly when
transmission speed is high.
ear each connector a green LED lamp is provided to
indicate the status of the bus; the following table
resumes all the possible states.
DK400150 rev. 0 ─ 18/04/2013 7/8
81DATA+
2DATA-
3GND
4NC
5NC
6NC
7NC
8NC
1
status LEDs

LED BEH VIOUR SYSTEM ST TUS
Blinking slowly System initialization
Searching modules on the bus
FW updating
Off (fixed) No slaves found on the bus
On (fixed) Bus operating correctly
Blinking fast Bus error
DK400150 rev. 0 ─ 18/04/2013 8/8