Field Service Procedure – Replacement Level Cage Motor Kit, XX04 &
6003A/6004
Page1of5
Document No
135290 Rev B
Copyright © Sea Tel, Inc 2011 - The information contained in this document is proprietary to Sea
Tel, Inc.. This document may not be reproduced or distributed in any form without prior written
consent of Sea Tel, Inc.
1. BriefSummary:
TroubleshootingdocumentfordiagnosingafaultwithandreplacingthelevelcagemotorontheXX04and6003A/6004
seriesantennas.
2. Checklist:
VerifyInitialization
VerifyPointing
VerifyTargeting
3. TheoryofOperation:
ElevationdriveoccursfromoffsettingthelevelcagewhichintroduceserrorintothePCU’scontrolloop,theelevation
motorwillthendrivetheaxistobringthelevelcagebacktolevel,removingtheerrorandinturnchangingtheelevation
lookangleoftheantenna.Ifthelevelcagemotorisdefectiveitwillpreventthesystemfromtargetingthecorrect
elevation,bynotoffsettingthelevelcagethecorrectamountandthereforecausingtheelevationtargetingerror.
Asignthatthelevelcagemotorisfaultyisthesystemkeepsfindingthesatelliteatdifferentelevationpositionsandthe
trimsneedadjustingtocompensateforthis.Anotheristhesystemmis‐pointscompletelyandthelookangleofthe
antennadoesn’tcorrespondwiththevaluedisplayedontheDAC.Whatisactuallyhappeningisthemotorisn’toffsetting
thelevelcageproperly,thereforethesystemisn’ttargetingcorrectlyTheDAC,however,willdisplaythedesiredtarget
positionasthereisnolivefeedback.
4. VerifyInitialization:
Powercyclethepedestal
1. Levelcagedrivestoitsendstop,thenbacksoffexactly45degrees
2. Elevationaxisdrivestolevelbasedonthelevelcage’shorizonreference
3. Crosslevelaxisdrivestolevelbasedonthelevelcage’shorizonreference
4. Limitedazimuthsystemsdriveclockwiseintotheazimuthendstop,thenbackoffto630degreesof
relative
Verifyifthelevelcagemotordrivescorrectly,ifnotthenthesystemwon’ttarget45degreesofelevationduringthe
initializationprocess.
IftheACUreportsmodel"xx03/xx04",theantennasN0parameterneedscalibratingandverifyingthatthePCUsavesit
correctly.Adriveissueorpedestalerror(error8)requiresfurthertroubleshooting.