Seabreeze STS11 User manual

STS11 Touchscreen
Programmable Thermostat
950-0118revD August 28, 2009
Room
Running As SCHED
SYSTEM
MORE SCHED HOLD CLOCK SCREEN
AUTO
FAN
WED
PM
AUTO
HEAT
STS11 Touchscreen Pro
g
rammable Thermo
s
tat
Contents
Application/Features...............................................................................................................2
Specifications ..................................................................................... ...................................4
Installation .............................................................................................................................14
Wiring....................................................................................................................................18
Power the Thermostat...........................................................................................................30
Installer Setup .......................................................................................................................43
Installer System Test .............................................................................................................53
User Manual ...................... ...................................................................................................56
Programming.........................................................................................................................62
Troubleshooting.....................................................................................................................86
1
`

PRODUCT DATA
APPLICATION
The STS11 Touchscreen Programmable Thermostat is an effortless, 7-Day programmable
thermostat that provides universal system compatibility, precise comfort control and is
easy-to-program.
The STS11 Thermostats provide temperature control for gas, oil, electric and heat pump for 1
heat /1 cool systems including dual fuel operation.
STS11 Touchscreen Pro
g
rammable Thermostat
2
FEATURES
·Large, clear display with backlight shows the current and set temperature and
thermostat in the dark.
·Menu-driven programming make setup effortless.
·Beautiful ergonomic design is smart andsophisticated to match your customer
lifestyle.
·Touchscreen interaction
·Real-time clock keeps time during power failures and automatically updates to
daylight savings.
·"Saving Changes" notification lets you know when the schedule changes have been
saved.
·Change/check reminders let you know when to service or replace filters or batteries
·Various Hold options allow you to override the program schedule, as desired.
·Armchair programming allows you to remove the thermostat from the wall for
programming.
STS11 Touchscreen Pro
g
rammable Thermostat
3

STS11 Touchscreen Pro
g
rammable Thermostat
SPECIFICATIONS
Thermostat Description:
Feature Description
Powering methods Common wire with battery backup
System types (1 heat/1 cool) ·Gas, oil or electric heat with air conditioning
·Warm air, hot water, high-efficiency furnaces, heat
pump without auxiliary heat, steam and gravity
·Heat on
ly inclu
des power to open and power to
close zone valves and normally-open
zone valves
·Heat only with fan
·Cool only
·750 mV heating systems
Changeover Manual or Auto changeover selectable
System setting HEAT-OFF-COOL-AUTO
Fan setting AUTO-ON-CIRC
4
STS11 Touchscreen Pro
g
rammable Thermostat
Electrical Ratings:
Terminal Voltage (50/60 Hz) Running Current
W Heating 20 - 30 VAC 1 AMP max.
W Heating (Power pile) 750 mVDC 100 mAMP
Y Cooling 20 - 30 VAC 1 AMP max.
G Fan 20 - 30 VAC 1 AMP max.
T
emperature Setting Range:
Heating: 40°F to 90°F(4°C to 32°C).
Cooling: 50°F to 99°F (10°C to 37°C).
Operating Ambient
T
emperature:
32°F to 120°F(0°C to 49°C).
Shipping
T
emperature:
STS11 Thermostats: -30 °F to 150 °F
(-34.4°C to 65.6°C).
5

STS11 Touchscreen Pro
g
rammable Thermostat
Operating Relative Humidity (Non-condensing):
STS11 Thermostats: 5% to 90%.
Cycle Rates (at 50% Load):
Heating: Selectable 1 - 12 cycles per hour.
Cooling: Selectable 1 - 6 cycles per hour.
Clock Accuracy: +/- 1 minute per month.
Batteries:
Two replaceable AA alkaline batteries will power the thermostat when 24VAC common is not
used. A non-replaceable lithium battery with ten-year life is inside the thermostat. Under
normal use the lithium battery will maintain the calendar and time settings. The Alkaline
batteries maintain the calendar and time after lithium battery is no longer functional.
6
STS11 Touchscreen Pro
g
rammable Thermostat
Cool Indication:
STS11 Touchscreen Thermostats show "Cool On" on the screen when Cool is activated.
Heat Indication:
STS11 Touchscreen Thermostats show "
Heat On
" on the screen when Heat is activated.
Calibration:
STS11 Touchscreen Thermostats are factory-calibrated and require no field calibration.
7

STS11 Touchscreen Pro
g
rammable Thermostat
INFORMATION
If you have additional questions, need further information, or would like to comment on our
products or services, please write to: International Refrigeration Products Inc., 700 Corporate
Circle, Toms River, NJ 08755.Technical support phone: (704)504-8590
8
STS11 Touchscreen Pro
g
rammable Thermostat
Nomenclature:
Series System Stages Application
STS11 1H/1C STS11 - Standard
Mounting Means:
STS11 Touchscreen Thermostat: Mounts directly on the wall in the living space using
mounting screws and anchors provided.
Outdoor Sensor: Mounts outside of living space with mounting clip and screws provided.
Remote Indoor Sensor: Mounts directly on the wall using mounting screws and anchors
provided.
Dimensions:
1. STS11 Touchscreen Thermostat: see Fig 1.
2. STS11 Touchscreen Thermostat Back Case: see Fig. 2
3. STS11 Outdoor Sensor Mounting Clip: see Fig 3.
4. STS11 Cover Plate: see Fig 4.
9

10
Fig. 1. Touchscreen Thermostat dimensions in inches. (mm).
STS11 Touchscreen Pro
g
rammable Thermostat
5.98 in.(152mm)
4.48in. (114mm)
1.235 in.(30.60mm)
11
Fig. 2. Touchscreen Thermostat Back Case dimensions in inches. (mm).
STS11 Touchscreen Pro
g
rammable Thermostat
1.51 in.(38.5mm) 0.84 in .(21.5mm)
1.77 in.(45mm)
1.67 in.(42.5mm)

STS11 Touchscreen Pro
g
rammable Thermostat
Fig. 3. Outdoor Sensor Mounting Clip dimensions in inches. (mm). 12
R1.6in.(4mm)
1.82 in.(46.3mm)
R0.04in.(1mm)
R0.098 in.(2.5mm)
1.10 in.(28.1mm)
0.62 in.(16mm)
1.56 in .(39.7mm)
0.24 in.(6.2mm)
0.44 in .(11.2mm)
R0.098in.(2.5mm)
0.08 in.(2mm)
1.49 in.(38mm)
0.17in.(4.2mm)
STS11 Touchscreen Pro
g
rammable Thermostat
Fig. 4. Cover Plate dimensions in inches. (mm). 13
3.29 in.(83.5mm)
0.85 in .(21.5mm)
3.29 in.(83.5mm)
5.35 in.(136mm)
4.13 in.(105mm)

STS11 Touchscreen Pro
g
rammable Thermostat
INSTALLATION
When
Installin
g
this
Product...
1. Read these instructions carefully. Failure to follow the instructions can damage the produc
t
or cause a hazardous condition.
2. Check the ratings given in the instructions to make sure the product is suitable for your
application.
3. Installer must be a trained, experienced service technician.
4. After completing installation, use these instructions to check out the product operation.
Selectin
g
Location
Install the thermostat about 5 ft. (1.5m) above the floor in an area with good air circulation at
average temperature. See Fig. 5.
Do not install the thermostat where it can be affected by:
----Drafts or dead spots behind doors and in corners.
----Hot or cold air from ducts.
----Radiant heat from sun or appliances. Concealed pipes and chimneys.
----Unheated (uncooled) areas such as an outside wall behind the thermostat.
14
STS11 Touchscreen Pro
g
rammable Thermostat
Fig. 5. Selecting thermostat location.
15
5 FOOT
1.5METERS

STS11 Touchscreen Pro
g
rammable Thermostat
Installin
g
Wallplate
CAUTION
Electrical Hazard.
Can cause electrical shock or equipment damage.
Disconnect power before wiring.
The thermos
t
at can be mounted horizon
t
ally on the wall
1. Position and level the wallplate (for location only).
2. Use a pencil to mark the mounting holes.
3. Remove the wallplate from the wall and, if drywall, drill two holes in the wall, as marked.
For firmer material such as plaster, drill two holes. Gently tap anchors (provided) into the
drilled holes until flush with the wall.
4. Position the wallplate over the holes, pulling wires through the wiring opening. See Fig. 6
5. Insert the mounting screws into the holes and tighten.
16
STS11 Touchscreen Pro
g
rammable Thermostat
Fig. 6. Mounting wallplate. 17
WALL
WIRES THROUGH
WALL AND WIRE
SLOT
WALL ANCHORS
M0UNTING
HOLES(2)
M0UNTING
SCREWS(2)

STS11 Touchscreen Pro
g
rammable Thermostat
WIRING
(FIG.
9
-
16)
A
ll wiring must comply with local and national electrical codes and ordinances.
1. Select set of terminal identifications (Table 1) that corresponds with system type
(conventional or heat pump in Fig. 7).
2. Loosen the screws for the appropriate system type selected; see Table 1. See Table 2 for
terminal designation descriptions. Insert wires in the terminal block under the loosened
screw. See Fig. 8.
3. Securely tighten each screw.
4. Push excess wire back into the hole.
5. Plug the hole with nonflammable insulation to prevent drafts from affecting the thermostat.
6. See Fig. 9 through 16 for typical wiring hookups.
Fig. 7. Selecting terminal identifications for system type. 18
CONVENTIONAL
HEAT PUMP
SCREW
TERMINALS
S1 S2 C R RC L
S1 S2 C R RC W Y G
O/B Y G
STS11 Touchscreen Pro
g
rammable Thermostat
T
able 1. Selecting
T
erminal Identifications for System
T
ype.
System Type Wallplate Terminal
Identifications Wiring Diagram
Reference
Standard Heat/Cool Conventional 9, 10
Heat Only Conventional 11
Heat Only with Fan Conventional 12
Heat Only Power to open and power to
close zone valves Conventional 13
Normally Open Zone Valves Heat Only Conventional 14
Cool Only Conventional 15
Heat Pump without auxiliary heat Heat Pump 16
19

STS11 Touchscreen Pro
g
rammable Thermostat
IMPO
R
T
AN
T
: Use 18 gauge thermo
s
tat
w
ire.
Fig. 8. Inserting wires in terminal block.
20
STS11 Touchscreen Pro
g
rammable Thermostat
T
able 2.
T
erminal Designation Descriptions.
Terminal Designation Description
RC (see Note 1) Power for cooling--connect to secondary side of cooling
system transformer
R (see Note 1) Power for heating--connect to secondary side of heating
system transformer
C (see Note 2) Common wire from secondary side of cooling system
transformer
WHeat relay
YCompressor contactor
GFan relay
O/B (seeNote 3) Changeover valve for heat pump system
L (see note 4) Equipment monitor for heat pump system
S1, S2 Optional outdoor or indoor remote sensor
21
NOTES:
1. When used in a single-transformer system, leave metal jumper wire in place between RC
and R. If used on a two-transformer system, remove metal jumper wire between RC and R.
2. Common wire is optional when thermostat is used with batteries.
3. If thermostat is configured for a heat pump system in the Installer Setup, configure
changeover valve for cool (O-factory setting) or heat (B).
4. The “L” terminal is an input (system monitor) when the System mode is in the HEAT, OFF,
COOL or AUTO position. When using the “L” terminal connect the 24 VAC Common. See LCD
indications on page 81.

STS11 Touchscreen Pro
g
rammable Thermostat
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2. FACTORY INSTALLED JUMPER.
3. OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE
SEPARATE FROM THE THERMOSTAT CABLE.
Fig. 9. Typical hookup of conventional single-stage heat and cool system with single
transformer(1H/1C conventional). 22
CONVENTIONAL
S1 S2 C R RC W Y G
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
3
COMPRESSOR
CONTACTOR
OPTIONAL
24VAC
COMMON
CONNECTION
RC
1
2
FAN RELAY
HEAT RELAY
STS11 Touchscreen Pro
g
rammable Thermostat
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2. OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE
SEPARATE FROM THE THERMOSTAT CABLE.
3. REMOVE FACTORY INSTALLED JUMPER.
Fig. 10. Typical hookup of conventional single-stage heat and cool system with two
transformers (1H/1C conventional). 23
CONVENTIONAL
S1 S2 C R RC W Y G
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
2R
C1
FAN RELAY
HEAT RELAY
RC1
COMPRESSOR
CONTACTOR
OPTIONAL
24VAC
COMMON
CONNECTION
3

STS11 Touchscreen Pro
g
rammable Thermostat
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2. FACTORY INSTALLED JUMPER.
3. OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE
SEPARATE FROM THE THERMOSTAT CABLE.
Fig. 11.
T
ypical hookup o
f
heat-only system (1H conventional). 24
CONVENTIONAL
S1 S2 C R RC W Y G
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
3
HEAT RELAY
OPTIONAL
24VAC
COMMON
CONNECTION
R
C1
2
STS11 Touchscreen Pro
g
rammable Thermostat
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2. FACTORY INSTALLED JUMPER.
3. OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE
SEPARATE FROM THE THERMOSTAT CABLE.
Fig. 12.
T
ypical hookup of heat only system with fan (1H conventional). 25
CONVENTIONAL
S1 S2 C R RC W Y G
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
3
HEAT RELAY
OPTIONAL
24VAC
COMMON
CONNECTION
RC1
2
FAN RELAY

STS11 Touchscreen Pro
g
rammable Thermostat
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2. FACTORY INSTALLED JUMPER.
3. OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE
SEPARATE FROM THE THERMOSTAT CABLE.
Fig. 13. Typical hookup of heat only power to open and power to close zone valve
system. 26
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
3
RC1
2
W
B
R
TR TR MOTOR OR
VALVE
CONVENTIONAL
S1 S2 C R RC W Y G
STS11 Touchscreen Pro
g
rammable Thermostat
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2. FACTORY INSTALLED JUMPER.
3. OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE
SEPARATE FROM THE THERMOSTAT CABLE.
Fig. 14. Typical hookup of heat only system with normally open zone valves.
27
CONVENTIONAL
S1 S2 C R RC W Y G
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
3
NORMALLY OPEN
ZONE VALVE
OPTIONAL
24VAC
COMMON
CONNECTION
RC1
2
4

STS11 Touchscreen Pro
g
rammable Thermostat
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2. FACTORY INSTALLED JUMPER.
3. OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE
SEPARATE FROM THE THERMOSTAT CABLE.
Fig. 15.
T
ypical hookup of cool only system(1C conventional).
28
STS11 Touchscreen Pro
g
rammable Thermostat
CONVENTIONA
L
S1 S2 C R RC W Y G
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
3
COMPRESSOR
CONTACTOR
OPTIONAL
24VAC
COMMON
CONNECTION
RC1
2
FAN RELAY
29
STS11 Touchscreen Pro
g
rammable Thermostat
1. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2. FACTORY INSTALLED JUMPER.
3. "O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE INSTALLER SETUP.
4. OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE
SEPARATE FROM THE THERMOSTAT CABLE.
Fig. 16. Typical hookup of single-stage heat pump without auxiliary/backup heat
(1H/1C heat pump).
HEAT PUMP
S1 S2 C R RC W Y G
S1 S2 C R RC L Y G
O/B
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
4
2
RC1
CHANGEOVER
VALVE
COMPRESSOR
RELAY
FAN RELAY
OPTIONAL
24VAC
COMMON
CONNECTION
3

STS11 Touchscreen Pro
g
rammable Thermostat
POWER
THE
THERMOSTAT
30
You can choose from three methods to power the thermostat.
·Batteries only (AA alkaline).
·24VAC common wire only.
·24VAC common wire with battery backup (AA alkaline).
Wirin
g
24V
A
C
Common
·Single-Transformer
System:
Conn
ect the common side of the transformer to the C screw terminal of the
thermostat wallplate. Leave the metal jumper wire in place between RC and R.
·
Two Transformer System:
Connect power side of "Cooling" transformer to RC terminal. Remove factory
installed jumper. Connect common side of "Cooling" transformer to the compressor
contactor, relay, etc. Connect power side of "Heating" transformer to the R terminal.
Connect the common side of the Heat relay to the C terminal.
STS11 Touchscreen Pro
g
rammable Thermostat
Installin
g
Batteries
1. Install Two AA alkaline batteries on the
back of the thermostat as marked on the
thermostat. See Fig. 17.
Fig. 17. Installing batteries.
2. Locate and remove the tab. See Fig. 18.
Fig. 18. Remove tab.
31
BATTERIES(2)
-+-+
REMOVE
TAB

STS11 Touchscreen Pro
g
rammable Thermostat
Mount
Thermostat
to
Wallplate
1. Align the terminal screw blocks with the pins on the back of the thermostat. Push the
thermostat strai
g
ht onto the wall
p
late until it sna
p
s into
p
lace. See Fi
g
19.
Fig. 19. Mount thermostat to wallplate. 32
WALLPLATE
TERMINAL SCREW BLOCK
PINS ON BACK OF
THERMOSTAT
STS11 Touchscreen Pro
g
rammable Thermostat
Locate
and
Mount Outdoo
r
Temperature
Sensor
(
Optional
)
Mount the sensor where:
·the settings cannot be tampered with.
·there is good air circulation.
·it can measure true outdoor ambient temperature.
·there is a flat surface.
·maximum distance between outdoor sensor and touchscreen thermostat is 65 ft (20m).
See fig 20.
Do not mount the sensor
·in direct sunlight.
·where hot or cold air blows on the sensor. Discharge line from an outdoor compressor
unit, vent or fan causes inaccurate temperature readings.
·where snow, ice or debris can cover it.
Use the following steps to mount the sensor:
1. Remove the sensor from the mounting clip.
2. Mark the area on the location selected for mounting the sensor mounting clip.
3. Mount the clip.
33

STS11 Touchscreen Pro
g
rammable Thermostat
Fig. 20.
T
ypical locations for 435-0012 Outdoor Sensor. 34
STS11 Touchscreen Pro
g
rammable Thermostat
35
CAUTION- OUTDOOR SENSOR
Electrical Interference (Noise) Hazard.
Can cause erratic system operation.
Keep wiring at least one foot away from large inductive loads such as motors, line
starters, lighting ballasts and large power distribution panels.
Use shielded cable to reduce interference when rerouting is not possible.
IMPO
R
T
AN
T
Erratic temperature readings from a sensor can occur as a result of any of the
wiring practices that are not to local and national electrical standards. Follow
wiring these practices to assure correct operation. Use shielded cable to reduce
interference if rerouting sensor wiring is not possible.

STS11 Touchscreen Pro
g
rammable Thermostat
Be sure wires have a cable separate from the thermostat cable.
Do not route temperature sensor wiring with building power wiring, next to control contactors
or near light dimming circuits, electric motors or welding equipment.
A
void poor wiring connections.
A
void intermittent or missing building earth ground.
CAUTION- OUTDOOR SENSOR
Electrical Shock Hazard.
Can cause electrical shock or equipment damage.
Disconnect power supply before connecting wiring.
Wiring must comply with local and national codes, ordinances and regulations:
1. Wire Outdoor Sensor to S1and S2 terminals on the thermostat. If leadwire provided is not
long enough, you need an extra cable to reach the hole at maximum distance between the
outdoor sensor and the touchscreen thermostat is 65 ft.
a. Using color-coded, 18-gauge thermostat wire is recommended. For example of general
wiring of sensor, see Fig. 21.
b. Pigtail wiring can be used.
2. Mount Sensor in its mounting clip.
3. Plug wiring hole using non-hardening caulk or putty.
36
STS11 Touchscreen Pro
g
rammable Thermostat
1. USE APPROPRIATE MOUNTING MEANS FOR THE TYPE OF STRUCTURE.
2. PLUG WIRING HOLE WITH NON-HARDENING CAULK OR PUTTY.
Fig. 21.
W
ire Outdoor Sensor to the thermostat.
37
1
2
WIRING HOLE
THROUGH
STRUCTURE
435-0012

STS11 Touchscreen Pro
g
rammable Thermostat
38
Locate
and
Mount
Remote
Indoo
r
Temperature
Sensor
(
Optional
)
1. Choose a location (see Fig. 22) for mounting the sensor on an inside wall about 5 ft (1.5m)
above the floor.
2. Be sure wire distance between sensor and thermostatis less than 19.6 ft (6m).
3. Make sure there is good air circulation at average temperature at the chosen location.
A
void the following locations because they can introduce errors in sensor
measurements. See Fig. 22.
Hot areas caused by:
(a) Concealed pipes or ducts.
(b) Drafts from fireplaces or other heat sources.
(c) Convection or radiant heat from the sun or electrical equipment.
Cold areas caused by:
(a) Concealed pipes or ducts.
(b) Drafts from windows and doors.
Unheated areas on the other side of the wall location.
Dead air areas:
(a) Behind doors, furniture and curtains. (b) In corners and alcoves.
4. Mark the area on the wall selected for mounting the Sensor or junction box.
5. Run wire cable to a hole at the selected wall location. Pull approximately three inches of
wire through the opening. Color-coded, 18-gauge thermostat wire is recommended.
STS11 Touchscreen Pro
g
rammable Thermostat
39
Fig. 22.
T
ypical location for 435-0013 Indoor Sensor.
5 FOOT
1.5METERS
Table of contents