Perry Electric TE540 User manual

PE - DETIPE023 06/17
Battery-operated
Winter / Summer
2 temperature levels + antifreeze
Input for remote contact
Input for remote temperature probe
DIGITAL THERMOSTAT
MENU DRIVEN with BACKLIT DISPLAY
Recessed installation
(not included)
2x 1,5V dc LR6-AA
Set
Mod. TE540
www.perry.it
PERRY ELECTRIC Srl
Via Milanese, 11
22070 VENIANO (Como) ITALY

INDICE
pag. 3
5.2 - Installation rules
pag. 4
pag. 5
pag. 6
pag. 7
pag. 8
pag. 8
pag. 8
pag. 9
pag. 10
pag. 12
pag. 13
pag. 14
pag. 15
pag. 16
pag. 16
pag. 16
pag. 17
pag. 18
pag. 18
pag. 18
pag. 19
pag. 19
pag. 20
pag. 20
pag. 20
pag. 21
pag. 21
pag. 23
pag. 23
pag. 24
pag. 24
pag. 25
pag. 25
pag. 26
pag. 27
pag. 27
pag. 28
pag. 28
pag. 28
pag. 29
pag. 29
pag. 29
pag. 13
pag. 13
pag. 13
pag. 14
pag. 17
pag. 17 pag. 30
pag. 30
pag. 31
pag. 3
2 - FACTORY SETTINGS
WARNINGS
DEVICE PRESENTATION
1 - TECHNICAL DATA
3 - KEY FUNCTIONS
4 - DISPLAY FEATURES
5 - INSTALLATION
5.1 - Overall dimensions
5.4 - Electrical connections
5.6 - Signalling batteries low or down
7 - USE OF THE THERMOSTAT
8 - STRUCTURE OF THE MAIN MENUS (use and configuration)
9 - ACCESS TO MENUS
10 - USER MENU
10.1 - Set WINTER or SUMMER mode
10.2 - Modification or disabling of set antifreeze temperature
5.2 - Installation example
6 - START THE THERMOSTAT
5.5 - Removing and inserting the thermostat (e.g. battery replacement)
)
10.3 - USER PASSWORD Menu (user)
10.3.2 - Password modification or cancellation
10.3.1 - Entering the user password
7.1 - Temperature adjustment from COMFORT to ECONOMY
(energy saving) and vice-versa
7.2 - Modification of T Set temperature set
7.3 - Temperature control pause
7.4 - OFF (disabling the thermostat)
pag. 17
pag. 17
11.1 - Access to configuration menu
11.2 - Change set language
11.3 - Type of temperature adjustment mode
11.3.1 - Selection of the temperature adjustment mode
(differential on/off or proportional)
11 - CONFIGURATION MENU (installer)
11.3.2 - Setting hysteresis for thermal differential ON-OFF
11.3.3 - Setting period duration for modulating Proportional
11.4 - Change unit of measure for temperature reading
11.5 - Correction of room temperature reading
11.6 - Max and min set temperature lock (winter and summer mode)
11.7 - Probe menu
11.7.1 - No connection to separate probe
11.7.2 - Setting separate remote probe
11.7.3 - Setting floor probe
11.8 - Connection to external contact for remote
thermostat switching on/off
11.7.4 - Setting separate external probe
11.8.1 - Activation / disabling with a Telephone Programmer
11.8.2 - NO Duty - for normally open contact
11.8.3 - NC Duty - for normally closed contact
11.9 - Descaling cycle
11.10 - Display contrast adjustment
11.11 - Backlighting
11.12 - Entering and managing password
11.12.1 - Entering new password
11.12.2 - Password modification or cancellation
11.13 - Restore (Reset)
11.14 - System software information
12 - POSSIBLE PROBLEMS AND SOLUTIONS
2
COMPATIBILITY TO THE MOST COMMON RESIDENTIAL SERIES PLATES
IMPORTANT: for the assembly procedure of the thermostat with the chosen residential plate,
follow instructions contained in the specific compatibility sheet contained in the package.
IMPORTANT: for the assembly procedure of the thermostat with the chosen residential plate,
follow instructions contained in the specific compatibility sheet contained in the package.

Read this manual carefully before using the product as it provides important guidelines regarding safety, installation and use.
The manual must be preserved with care for future reference.
The installation and electrical connection of the programmable thermostat must be implemented by qualifiedonly a
electrician and in conformity with current laws and regulations.
The thermostat is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or by
those with a lack of experience and knowledge of the instructions, unless they are supervised or have received the necessary
instructions concerning use of the device by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the device.
If (+23°F or + 99.9 °F) room temperature flashes on the display, the measured temperature is beyond the scale.-5 °C or +37.7 °C
If flashes on the display, it indicates faulty probe: any temperature control activity is suspended."Err"
Use 2 stilo 1.5V batteries type AA (LR6). Batteries not included.alkaline
N.B.: the product has been tested and its characteristics are guaranteed when alkaline DURACELL or ENERGIZER batteries are used.
If necessary, gently clean the thermostat and the display with a soft, dry cloth.
The manufacturer reserves the right to introduce any technical and/or constructive changes deemed necessary, with no prior notice.
WARNINGS!
3
PRESENTATION
Dear Customer, thank you for choosing our product.
The thermostat, suitable for all heating and/or cooling system, is fitted with a large and clear backlit display to keep all its functions under
control in real time. The fundamental feature is its easy to use menu navigation, which makes it extremely user-friendly despite its
comprehensive range of functions. The thermostat is factory-set to adjust temperature in a Differential ON/OFF manner and hysteresis
can be set from 0.2°C to 1.2°C to adapt to the thermal inertia of your specific installation. Alternatively, modulating Proportional operation
may be selected with settable duration cycles (from 7 to 20 minutes): this system ensures the desired temperature is maintained more
stable, increasing user comfort and is particularly suitable for installations with high thermal inertia such as, for instance, for underfloor
radiant panels. The set temperature scale is in degrees Centigrade (Celsius) with the option to calibrate room temperature measurement
setting a correction value (from -3 to +3 °C). The thermostat can be connected to a separate remote controllable temperature probe
(optional) which may then be set according to one's installation needs: remote, floor, external.
Special attention was devoted to energy saving: pausing for household cleaning, optional Set temperature (MAX/MIN) lock, adjustable
anti-freeze temperature value, control through an external contact (e.g. optional telephone programmer), are conducive to avoiding
wasting energy with consequent savings. See the following pages for a description of these as well as of other features.
&

1 - TECHNICAL DATA
Power supply:
Autonomy:
Battery life after the "battery low" symbol starts
flashing on the display:
White color backlight:
Type of action, disconnection and device:
Type of output:
Software:
Rated impulse voltage:
Cross-section of wires to terminals:
Input for remote contact ON/OFF:
Input for separate remote probe:
Type of insulation:
Degree of protection:
Pollution rating:
Number of temperature levels:
Ambient temperature display range:
Floor probe threshold display range:
External probe display range:
Relay ON signal:
Room temperature indicator resolution:
Temperature Set adjustment range:
Setting temperature Set:
Temperature correction (Offset):
Antifreeze temperature: (t ):
Type of temperature adjustment:
- DIFFERENTIAL ON/OFF (default)
- PROPORTIONAL WITH CONTROL PERIOD
Thermal gradient:
Temperature reading tolerance:
Operating temperature limits:
Storing temperature limits:
Reference regulations for CE markings:
n° 2 batteries 1,5 V type AA (LR6)Alkaline
Approx. 2 years
Approx. 15 days
timed 6 sec. (default) / always off
1 / B / U / Electronic
voltage free relay with COM / NO / NC changeover contact,
max 5(3)A/250 V ~
class A
4 kV
1,5 mm ÷ 2,5 mm
22
for NO or NC contact free from potential
yes - probe may be set depending on use: remote, floor, external
class II
I30P
normal
n° 2 « = COMFORT», « = ECONOMY» + t antifreezet1 t2
- 5.0 °C ÷ + 37.7 °C (+ 23 °F ÷ +99.9 °F)
- 0.0 °C ÷ + 60.0 °C (+ 32 °F ÷ +140 °F)
- 9.9 °C ÷ + 60.0 °C ( +14.2 °F ÷ +140 °F)
0.1 °C (0.1 °F)
+5 °C ÷ +37.7 °C (+41.0°F ÷ +99.9 °F) limitable
adjustable by 0.1 °C / 0.1 °F sets
adjustable from -3.0 °C (5.4°F) to +3.0 °C (5.4°F) default 0.0 °C/0,0 °F
adjustable + 5 °C ÷ <t2 (41,0 °F ÷ <t2) default 6 °C (42.8 °F)
adjustable from 0.2 °C to 1.2 °C (from 0,3 °F to 2.1 °F) default 0,3 °C (0,4°F)
cycles adjustable from 7 to 20 minutes (default 10 minutes)
max 1°K / 15 min
± 0,5°C (± 0,9°F)
0 °C ÷ +45 °C
-10 °C ÷ +60 °C
LVD - EMC EN60730-2-7 EN60730-2-9
Flashing + ON (winter) or + ON (summer)
ErP classificaenergy tion: ErP Class I; 1% (Reg. EU 811/2013)
4

2 - FACTORY SETTINGS
5
FACTORY SETTINGS TABLE (default)
Parameter Default
Language
Active season
Temperature unit of measure
Set t1 COMFORT Winter
Set t2 ECONOMY Winter
Set t antifreeze (Winter)T
Set t1 COMFORT Summer
Set t2 ECONOMY Summer
Temp. locks Winter
Temp. locks Summer
Temp. adjustment mode
Differential hysteresis
Modulating proportional
Modulating period
Room temp. correction
Room temp. correction
Anti-scale protection cycle
Display contrast
Display back-lighting
Winter
°C (celsius)
20.0°C
18.0°C
6.0°C
24.0°C
27.0°C
Disabled
Disabled
DIFF. ON/OFF
0.3°C
Prop (not active)
10 min. (not active)
0,0 °C
0,0 °C
Disabled
Level 6
Timed 6 sec.
Restore «reset»
IT (Italian)
Default
Last value
Default
Default
Default
Default
Default
Default
Default
Default
Default
Default
Default
Last value
Default
Default
Remote Probe
External Input
User Password
Installer Password
Password reset code
(not active)
(not active)
none
none
0927
Last value
Last value
Default
Default
Default
RESTORE «Installer RESET»
Restore many factory settings (default)
RESTORE brings the thermostat back to factory settings with the
exception of some items as shown in the table; to perform the
operation follow the instructions in paragraph 11.13.
Default
Default
Press simultaneously for 4 seconds
To confirm
Menù
back
SetT
Set
OK
Menù
back
SetT
02 4 6810 12 14 16 18 20 22
Set
The data entered in the thermostat called «FACTORY SETTINGS» refer to operation defined as «Standard».
The following chapters describe all customisable functions, in order to satisfy any ambient comfort need.
RESTART
Should the thermostat feature malfunctioning, wrong displays or other
incorrect conditions, perform a .«User reset»
Simultaneously press for 4 secs. the and keys.Menu
The thermostat resumes normal operation.
It does not cancel the entered settings

3 - KEY FUNCTIONS
6
AMultifunction Key Menu/back,
its use changes depending on function or active menu:
Menu = press briefly to switch temperature from comfort to economy and vice-versa,
press and hold (3 sec.) access to menus
back = exit from menusgo back to previous item,
B
C
increases the desired Set temperature;Key
navigation through the menus: to increase a setting value;
Key decreases the desired Set temperature;
navigation through the menus: to decrease a setting value;
Press the pulse arrow key to
increase/decrease per unit
and keep pressed to
increase/decrease rapidly.
DMultifunction Key OK
thermostat in OFF (disabled temperature control)
current program pause for household cleaning
access to selected menu / confirm function or set value (within the menus)
OK
Touching any key activates back-lighting, displaying the
words selection and navigation, press the desired key
within 6 sec. to vary the settings (touching any key
reactivates a 6 secs. time-out).
Backlit display
Note: more particular button functions are described
in the specific paragraphs.
Set
OK
Menù
back
SetT
C
B
AD

4 - DISPLAY FEATURES
Note: further displays
are described in the
specific operation
paragraphs
1
6
7
8
9
Detected room temperature
Signalling operating user = and flashingON (e.g. boiler on)
(e.g. conditioner on)
Signalling operating user = and flashingON
Heating mode ( Winter) active
T
10
3
2
Display Set temperature
4
T
Currently active set temperature depending on the desired setting:
Comfort or Economy (saving) or antifreezet1 t2 t
Batteries low signal
8
8
Cooling mode ( Summer) active
T
5Info and thermostat operating mode, menu items
7
Current program pause (example: for household cleaning)
8
6
Set
7
2
3
4
5
10
1
9
Enabling thermostat from remote control

5 - INSTALLAZIONE
5 - INSTALLATION
5.3 - INSTALLATION EXAMPLE
5.1 - DIMENSIONS
The installation and electrical connection of the programmable
thermostat must be implemented by qualified electrician and inonly a
conformity with current laws and regulations. The manufacturer
declines all liability in connection with the use of products subject to
special environmental and/or installation standards.
Thermostat installation: independent - fixed
recessed in rectangular box 3 modules.
Install the thermostat at a height of 1.50 to 1. 0 m from the floor, far from7
sources of heat, windows and anything that may alter its operation.
Warning: before installing, deactivate
the mains voltage of the device to be controlled.
Examples of installation in heating systems with a
thermostat that controls:
A) Wall mounted boiler
B) Burner or Circulation pump or Motorized solenoid valve
C) solenoid valveZone
(example for floor system or other)
N.B.: the examples contained in this documentation are in principle..
IMPORTANT: for the assembly procedure of
the thermostat with the chosen residential
plate, follow instructions contained in the
specific compatibility sheet contained in the
package.
5.2 - INSTALLATION REGULATIONS
C C
AB BB
!
h 1,5 m
8
battery
thermostat module
3965 20 13
43,5
47

5 - INSTALLATION
5.4 - ELECTRICAL CONNECTIONS
Disconnect the 230V~ mains voltage that powers the devices to be controlled
!terminals may be connected to12and
a telephone programmer (or switch)
for remote thermostat enabling (see
paragraph 11.8 for external contact
setting)
!terminals may be connectedand13 14
to a separate temperature probe
!(see paragraph 11.7 to set the probe)
Note: maximum cable length 4 m
AUX 1 Terminals (remote probe) AUX 2 Terminals (remote contact)
Examples of electrical connections
1
2
AUX 2
example: Telephone programmer (optional)
BOILER
Contact for remote
thermostat control
2
AUX 2
example: Telephone programmer (optional)
N
L
Contact for remote
thermostat control
LOAD
opens
closes
230V~
Connection
to a boiler
Connection to a
motorized valve
AUX 1
230V~ N
L
1
Separate
temperature
probe
(optional)
!connect the device to be controlled
to the terminals
5- common (C)
- normally open contact (NO)6
- normally closed contact (NC)7
Relay terminals
C
NO
NC
C
NO
NC
AUX 1
Separate
temperature
probe
(optional)
9

5 - INSTALLATION
5.5 - THERMOSTAT REMOVAL AND INSERTION
(es. battery replacement, programming)
Insert or replace with 2 1.5V AA-LR6 batteries paying attention
to polarity.
ONLY USE GOOD QUALITY ALKALINE BATTERIES
(Duracell or Energizer batteries are recommended)
Reinsert the thermostat
module fully into the
recessed base.
Remove the
thermostat module
by grasping it with
your fingers in the
appropriate seats.
1°
ALKALINE
ALKALINE
2°
3°
Attention: battery life may be more than 2 years.
However, it is recommended to replace them at least every 24 months to avoid
them running out when you are away (e.g. Christmas holidays, etc.)
Dispose of flat
batteries in
appropriate containers
and as required by the
environmental
protection regulations.
ON
Convenient programming
Attention!
All setting operations may be performed before
inserting the thermostat module to the
recessed base; this means setting may be
carried out while comfortably seated.
The flashing indication with fixed winter orON
summer symbol indicates that the thermostat
is detached from the recessed base.
If programming of the thermostat module takes place before fixing
to the recessed base, upon completing installation the ON
indication (off or flashing) on the display might not correspond to
the actual relay status.
Within 1 minute at the most the insertion of the thermostat module
to the recessed base, the relay activates with the indication (offON
or flashing) displayed.
10
Set
Important: if the display shows the message , itNO RELAY
indicates that the thermostat module has not been correctly
inserted all the way into the recessed relay base.

5.6 - SIGNALLING BATTERIES LOW OR DOWN
When the symbol blinks, this indicates that the batteries are running out and
as from this moment there are 15 days to replace them.
All thermoregulation is suspended and all settings are saved to be restored when
the new batteries are inserted.
Note: the backlight of the display is automatically deactivated.
If the discharged batteries are not replaced within this time the display will
completely turn off.
Set
5 - INSTALLATION
11

5 - INSTALLAZIONE
6 - START THE THERMOSTAT
Winter mode (heating)
ON + flashing = e.g. operating boiler
Press twice
the back key
Select the desired language by scrolling through
the available languages using the keys.
Confirm pressing the key.OK
The selectable languages are:
ITALIAN ENGLISH FRENCH(default)=It , =En,
=, =Fr = dE, ES.GERMAN SPANISH
Press 2 time the key.back
The thermostat is operative, Winterdisplaying: «heating» mode, the temperature Set at 20°C COMFORT, room temperature
detected.
From normal thermostat operation in stand-by, pressing a key lights up the display (unless back-lighting has been disabled)
and the words selection and navigation appear. Within 6 secs., a variation is made the second time the desired key is pressed.
See use of the thermostat to the next chapter.
Upon first insertion of the batteries, the thermostat performs a lamp-test by switching on all display segments, displaying the
installed software version for a few seconds.
When this phase is over, the thermostat asks to select the language of use.
OK
1° 2°
Set
02 4 6810 12 14 16 18 20 22
OK
Set
12

7 - USE OF THE THERMOSTAT
7.1 - MODIFICATION of temperature from COMFORT to ECONOMY
(energy saving) and vice-versa
Press the MENU key briefly
The thermostat allows temperature values that satisfy the following
conditions:
Winter: t1 t2 tgreater than or equal to greater than or equal to
Summer: t2 t1greater than or equal to
7.2 - MODIFICATION OF T TEMPERATURE SETSet
Directly press the keys.
WINTER= heating (factory setting)
With COMFORT temperature
Every time the keys are pressed, it changes by 0.1 degrees;or
pressing and holding enables you to scroll through the values rapidly.
Range: +5 °C to +37,7°C (+41,0°F ÷ 99,9°F).
7.3 - TEMPERATURE CONTROL PAUSE (example for household cleaning)
Pressing the key connected user will switch off for a max 3-
hour period during which the thermostat will enter antifreeze
mode ( ).t
After 3 hours the thermostat temperature control will resume.
It is possible to restart temperature control before the 3 hours
have elapsed, press « »: the word disappears.back «CLEANING»
In the presence of max and min. temperature locks (see
paragraph 11.6) it is not possible to set a higher or lowerSet t
than the entered locks. The display will signal impossibility to
perform the operation by displaying .
Note: in the event antifreeze temperature has been permanently disabled
or in "Summer" operation, the connected user (e.g. boiler or air conditioner) will remain disabled for 3 hours maximum.
IMPORTANT!
Set Set
Set Set
Set Set
OK
OK
13

8 - STRUCTURE OF THE MAIN MENUS (use and configuration)
The Menus are arranged in sequential order
-LANGUAGE (selection of the desired language)
-RULE (selection of temperature control mode)
4 CONFIGUR
Installer or skilled user menu:
7.4 - OFF (disabling the thermostat)
This setting has the purpose of locking thermostat functions
when heating or cooling must remain off.
2- The display shows , to indicate that the thermostat is disabled and all functions are inactive; the
OFF
display only shows room temperature reading, the descaling function, if enabled and (in WINTER
mode) the temperature Set plus the antifreeze protection symbol .t
in WINTER mode with antifreeze temperature disabled or in Summer mode, the symbol will nott
be visible.
3- to reactivate the thermostatPress key .
7 - USE OF THE THERMOSTAT
1- In «CLEANING» mode, press the button briefly to
set the thermostat to and consequentlyOFF «Switch off
the system».
Set
OK
OK
OK
OK
14
1 SEASON (Winter or Summer mode)
2 SET TEMP
(modification or disabling of Set antifreeze temperature)
3 USER PASSWORD (set user password)
User Menu:
T
-UNIT (selection of temperature unit of measure °C/°F)
-OFFSET (correction of detected room temperature)
-BLOCKS (it lets you limit the value of set temperature points)
-PROBE (setting a remote temperature probe)
-INPUT (setting an external contact for remotely enabling / disabling
the programmable thermostat)
-PUMP ON (disabling / enabling the descaling function)
-CONTRAST (to change display contrast)
-BACKLIGHT (to enable/disable display backlighting)
-PASSWORD (to restrict the use of user and/or installer
functions of the thermostat)
-RESTORE (RESET operation)
-INFO SW (information about the firmware version installed)

9 - ACCESSO AI MENU
9 - ACCESS TO MENUS
the 1st menuCONFIGUR
item is accessed after
entering the installer
password (see par 11.1)
the 1st user menu is accessed after
entering the user password
(see next paragraph)
From normal thermostat operation, press the key for 3 sec . to access the first available menu.Menu s
The keys are used to scroll through the menus: press to enter the selected menu, press
OK back
to go back to the previous item. Settings in the menus must be confirmed by pressing the key whereOK
required, otherwise, after 3 minutes have elapsed, the thermostat goes back to normal stand-by operation
and changes will not be saved.
Or, if a secret user and/or installer access code , follow the steps below to access the user or installer menus.has been previously entered
password entry example
no password entered
with user password only
with the user and installer password
1°
main screen
for
3 sec .s
Set
OK
2°
OK
OK
1° 2°
OK
1° 2°
OK
Set
02 4 6810 12 14 16 18 20 22
OK
Set
02 4 6810 12 14 16 18 20 22
OK
15
is displayed
for a few seconds after
pressing the key to
OK
indicate incorrect
password.

10.2 - MODIFICATION OR DISABLING OF SET ANTIFREEZE TEMPERATURE
10 - USER MENU
10.1 - SET WINTER OR SUMMER MODE
Under item confirm with .SEASON SEt OK
Select with the keys the WINTER (heating) or
SUMMER (cooling) mode and confirm with OK.
To disable antifreeze temperature t , go below +5.0 °C .(41.0 °F)
Set
Set
disabled antifreeze temperature
From normal thermostat operation, access the menus
by pressing and holding the « » key.Menu
From normal thermostat operation, access the menus
by pressing and holding the « » key.Menu
Use the keys to select item .SET TEMP Set
Press to confirm.OK
The screen displays .ANTIFREEZE
Press to confirm.OK
Use the keys to set the desired antifreeze
temperature.
Confirm with Press the key to exit.OK. «back»
Press the key to exit.«back»
Every time the keys are pressed, it changes by 0.1 degrees;or
pressing and holding enables you to scroll through the values rapidly.
Range: +5 °C a +12°C
Set
02 4 6810 12 14 16 18 20 22
OK
Set
02 4 6810 12 14 16 18 20 22
OK
Set
02 4 6810 12 14 16 18 20 22
OK
02 4 6810 12 14 16 18 20 22
OK
Set
02 4 6810 12 14 16 18 20 22
OK
Set
02 4 6810 12 14 16 18 20 22
OK
2°
1°
16
T

10 - USER MENU
10.3 - USER PASSWORD Menu
No code is set in the factory configuration.
1- Select item with the keysUSER PASSWORD Set
and confirm with .OK
2- Use the , keys enter 4 digits (dashes not
included) between and , individually0000 9999
confirm them with «OK».
10.3.2 - Password modification or cancellation
10.3.1 - Entering the user password
From now on, the password will be required for any
variation on the thermostat.
Press and enter the previously set password; follow the procedureMENU for 3 secs.,
described above to access the menu:User PASSWORD SEt
- set 4 hyphens (- - - -), the password will be cancelled,
- set another number and it will be modified.
The thermostat enters normal operation.
From normal thermostat operation, access the
menus by pressing and holding the « » key.Menu
password entry example
Set
02 4 6810 12 14 16 18 20 22
OK
Set
02 4 6810 12 14 16 18 20 22
OK
1° 2°
Set
02 4 6810 12 14 16 18 20 22
OK
1° 2°
Set
02 4 6810 12 14 16 18 20 22
OK
17

11.1 - ACCESS TO CONFIGURATION MENU
Select with the keys the item andCONFIGUR Set
confirm with access the 1st item ofOK: LANGUAGE SEt
the menu (see chapter 8 the list of sub-menus to the item
CONFIGUR).
ATTENTION: access to the configuration menu is recommended since thefor the installer or experienced users
modification of some settings might affect correct system operation.
If only an installer password was entered
the display requests entering the 4 digits,
which may be selected using the ;
keys; individually confirm them with «OK».
11.2 - CHANGE SET LANGUAGE
When is displayed, press to confirm.LANGUAGE SEt OK
•Use the keys to select the desired language
scrolling through available ones.
•Confirm by pressing OK.
•Press the « » key to exit.back
The selectable languages are:
ITALIAN ENGLISH FRENCH GERMAN SPANISH(default) = , == It , = En, Fr = dE, ES.
From normal thermostat operation, access the menus by
pressing and holding the « » key.Menu
Set
02 4 6810 12 14 16 18 20 22
OK
Set
02 4 6810 12 14 16 18 20 22
OK
1° 2°
Set
02 4 6810 12 14 16 18 20 22
OK
Set
02 4 6810 12 14 16 18 20 22
OK
1° 2°
11 - ACCESS TO CONFIGURATION MENU (installer)
18

11 - ACCESS TO CONFIGURATION MENU (installer)
11.3 - TYPE TEMPERATURE ADJUSTMENT METHODS
The thermostat is factory set to work in modeTHERMAL DIFFERENTIAL
ON/OFF with a preset thermal differential value (Hysteresis) of 0,3 °C.
Note: adjustable from 0,2 °C to 1,2 °C (from 0,3 °F to 2,1 °F).
The hysteresis value must be set according to the system's thermal
inertia; a low value is recommended for systems with radiators made of
e.g. cast iron and a high value for systems with fan coils.
As opposed to the thermal differential, the temperature can be adjusted
MODULATING PROPORTIONALLY (PROP) setting cycles from 7 to 20
minutes (default 10 minutes).
This system maintains the desired temperature more stable, whilst
increasing the user's comfort sensation and saving on energy
consumption.
A long cycle is recommended for systems with high thermal inertia (cast
iron radiators, floor systems) and a short cycle for systems with low
thermal inertia (fan coils).
time
T SET
hysteresis
thermal inertia over temperature
of the heating element
ON ON
OFF
OFF
°C/°F
ON OFF ON OFF ON
T SET
thermal inertia over temperature
of the heating element
time
°C/°F
example of modulating proportional adjustment
example of differential adjustment
OFF
With the keys select la item RULE Set.
Press to confirm.OK
It will be possible to select temperature adjustment mode
between factory setting orThermal differential (On:OFF)
Modulating proportional (PrOP) operation.
Use the keys to select the desired temperature adjustment
mode. After making your choice press to confirm and displayOK
the screen to set if you have opted for or toHYSTERESIS On:OFF,
set the if you have opted for (see next paragraphs:PERIOD PrOP
11.3.2 and 11.3.3).
11.3.1 - SELECTION OF THE TEMPERATURE ADJUSTMENT MODE (DIFFERENTIAL ON/OFF OR PROPORTIONAL)
From normal thermostat operation, access the menus by pressing and holding the « » key, select press to confirm.Menu OKCONFIGUR Set,
Set
02 4 6810 12 14 16 18 20 22
OK
Set
02 4 6810 12 14 16 18 20 22
OK
Set
02 4 6810 12 14 16 18 20 22
OK
19

11 - ACCESS TO CONFIGURATION MENU (installer)
11.4 - CHANGE UNIT OF MEASURE FOR TEMPERATURE READING
•Through the path then press .CONFIGUR SEt -> UNIT SEtselect OK
•Select the desired unit of measure with the keys: °C or °F,
then press to confirm.
OK
All temperature set points will be updated according to the new scale.
•Press the key to exit.
back
The thermostat is pre-set in the factory to display temperatures in degrees Centigrade (Celsius), it is
possible to switch to the Fahrenheit scale or vice versa with the following procedure:
11.3.2 -Setting hysteresis for thermal differential ON-OFF
•Through the path then press .CONFIGUR SEt -> RULE SEt -> On:OFselect , OK
•With the keys enter the desired hysteresis value
(values may be set from 0.2 °C to 1.2 °C / from 0.3 °F to 2.1 °F - default 0.3 °C/0.4 °F).
•Press to confirm.OK
•Pressthe keytoexit.back
11.3.3 - Setting period duration for modulating Proportional
•Through the path then press .CONFIGUR SEt -> RULE SEt -> PrOP,select OK
•With the keys enter the duration of the desired period
(settable from 7 to 20 minutes, default 10 min.).
•Press to confirm.OK
•Press the key to exit.back
From normal thermostat operation, access the menus by pressing and holding the « » key.Menu
Dal normale funzionamento del termostato, accedere ai menu tenendo premuto tasto « ».Menu
From normal thermostat operation, access the menus by pressing and holding the « » key.Menu
Set
02 4 68
10 12 14 16 18 20 22
OK
OK
Set
02 4 6810 12 14 16 18 20 22
OK
1° 2°
Set
02 4 6810
SetSet
02 4 6810 12 14 16 18 20 22
OK
1° 2°
OK
OK
Set
02 4 6810 12 14 16 18 20 22
OK
Set
Set
20
Table of contents
Other Perry Electric Thermostat manuals

Perry Electric
Perry Electric MODULE Series User manual

Perry Electric
Perry Electric 1TX CR028WIFI Guide

Perry Electric
Perry Electric V002 Series Guide

Perry Electric
Perry Electric TE541 User manual

Perry Electric
Perry Electric RECESS Series User manual

Perry Electric
Perry Electric TE542 User manual

Perry Electric
Perry Electric Recess Series User manual