
8
The ZX300/ZX310 provides an option for including
Wireless(orRF) Devices. TheRFDevices may con-
sist of RF Zone Devices (Universals, Door Con-
tacts,Glassbreaks,PIRsand SmokeDetectors)and
RF User Devices (Handhelds). These RF Devices
require that an RF Gateway be attached to the sys-
tem. The ZX300/ZX310 is compatible with either a
model4710or 4720 RFGatewaywhich areULlisted
for household fire and burglary and commercial fire.
If a 4720 RF Gateway is used, it must be set to ad-
dress ‘1’. Refer to the RF Gateway instructions for
address selection.
• 4710 RF Gateway - provides up to 8 RF Zone
Devices and up to 8 RF User Devices. It can
only provide for zones 9-16.
• 4720 RF Gateway - provides up to 16 RF Zone
Devices and up to 8 RF User Devices. It can
provide for zones 1-16.
MounttheRFGateway asdescribedinthe RFGate-
way instructions. Wire the local data bus to the ter-
minals: +12V - RED; DATA A - GREEN; DATA B -
WHITE; NEG - BLACK. Set Address switch. Rein-
stall the cover.
See Installer Level Programming - Programming RF
Data Into the RF Gateway.An RF User Device must
be mapped to a valid user passcode by program-
ming.
The RF Gateway and RF Zone Devices should be
temporarily mounted in their desired locations until
theyhavebeentested with theControlPanel. These
devices may need to be re-oriented or moved to
achieve optimal reception. After testing has been
completed, they should be permanently mounted.
To test the Received Signal Strength of each RF
Zone Device, use Test 6 - RF Signal Strength Test.
From the Control Station press the “8” key, followed
by the Installer Code (9632) and then press the “6”
key. Next press the RF Zone Device Number (1-16).
The Control Station will display and sound the Re-
WIRELESS DEVICES
Wireless Devices
ceived Signal Strength of the last transmission sent
by the RF Zone Device. See results below:
Strong Signal (5 Control Station beeps): a strong or
high level RF signal was measured by the receiver
for that location of the transmitter. This is a good
location for the transmitter and receiver.
Acceptable (3 Control Station beeps): a normal or
acceptable level of RF signal was measured by the
receiver for that location of the transmitter. This is a
good location for the transmitter and receiver.
Low Signal (1 Control Station beep): a low or not
acceptable level of RF signal was measured by the
receiver for that location of the transmitter. Make
multipletesttransmissions,makingsure thatobstruc-
tions between the transmitter and receiver are nor-
mal but minimized (hands away from units, metal
ladders away from receiver, etc.) during these tests.
The transmitter and/or receiver will need to be relo-
cated to obtain ACCEPTABLE level readings.
No Signal (1 long Control Station beep): no RF sig-
nal or an extremely low RF signal was measured by
the receiver for that location of the transmitter. Bring
the transmitter to the RF Gateway and activate the
transmitter. The red LED on the RF Gateway should
blink. If it does not, then the transmitter is not work-
ing. If the red LED does blink, but the signal strength
is still NO SIGNAL, then a programming error ex-
ists. Check the programming of the zone in the RF
Gateway. If the signal strength is STRONG or AC-
CEPTABLE,thenthe transmitter and/or receiverwill
need to be relocated to obtain ACCEPTABLE level
readings. Be sure to power down the control to clear
out all signal strength levels before testing the trans-
mitter at its new location.
After testing has been completed, the RF Gateway
andRFZoneDevicesshouldbepermanentlymounted.
NOTE
Series 4000 RF Gateways and transmitters
whicharenotULlabeledarenot allowedin
UL Certificated installations.